BA_080_en_2022-01_11.02 Pressure transmitter PASCAL CV4
Page 18/24
6.4.4.2
Submenue "Screen mode"
In the "Screen mode" submenue, you configure the representation of the measured values
and additional information on the display.
With the menue item “Screen layout” you configure the information that is displayed and its
layout. Up to four values can be displayed at the same time. In the additional menue entries
"1st value" to "4th value" you define the contents of the placeholders in the layout.
The various layouts as well as the possible content of the values are described in Chapter
6.2.4.
6.4.5
Menue "Measurement/Output"
Configure the measured value as well as the current output in the "Measurement/output"
menue.
Menue entry
Description
Damping
Setting the damping of the output signal
Output function
Setting the output function
Lower range val.
Setting the pressure value that shall correspond to 4 mA (start of
range)
Upper range val.
Setting the pressure value that shall correspond to 20 mA (end
of range)
Output table
Specifying the points for the table function
Alarm current
Select the alarm current: High (>21 mA) or low (<3.6 mA)
Minimum current
Limit of
the lower output current (3.8…4.0 mA)
Maximum current
Limit of the upper output current (20…21 mA)
Table 13: "Measurement/Output" menue
Independent from the setting of the minimum and maximum current limit, the set measuring
range always corresponds to a current range of 4…20 mA.