3.  CONNECTIONS AND INSTALLATION

 

 

The SET/DM3AL sensor is equipped with a shield-
ed  2-wire  cable.  The  numbered  wires  1  and  2  of 
the cable are connected to the corresponding con-
nectors  (1  =  +,  2  =  -

 

)  in  the  control  unit.  Unnum-

bered wire is connected to the cable shield. Always 
check  the  connections  from  the  installation  and 
operation manual of the control unit as well.

 

In  figure  3  the  connection  example  1;  a  LJB2-78-
83  junction  box  has  been  used  to  connect  the  ca-
bling to the equipotential bonding. 

In  figure  3  connection  examples  2  and  3;  equipo-
tential  bonding  is  not  available.  The  shield  is  con-
nected  to  the  appropriate  connector  in  the  supply 
device. 

In  these  kinds  of  arrangements,  it  must  be 
ensured  that the electrostatic charges  do  not 

cause  a  hazard.  Make  sure  in  the  installation  that 
the device and cabling are not close to any strong 
current or other installations, and that they are not 
exposed  to  any  strong  stream  flows,  mechanical 
abrasions, or impacts. 

The  cable  may  be  shortened  or  extended  with  a 
junction  box,  if  necessary.  The  sensor  may  be 
installed  by  hanging  it  from  its  cable  (upper  limit 
alarm)  or  immersed  in  the  liquid  to  be  measured 
(lower limit or interface alarms).

 

The  example  in  figure  3  shows  an  oil  separator 
application  in  which  the  switch  data  is  received 
when the upper electrode is covered in oil i.e. is no 
longer immersed in the conductive liquid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.  OPERATION

 

This  chapter  provides  a  general  description  of  the 
operation of the oil alarm in different situations. For 
a  more  detailed  description,  please  refer  to  the 
manual of the control unit in use. 

Normal 
mode 

The SET/DM3AL oil level sensor is entire-
ly immersed in water. 

 

The indicator lights are off. 

 

The relays are energized. 

 

 

Oil 
cham-
ber full 

 

The  SET/DM3AL  sensor  is  immersed  in 
oil.  (The  sensor  does  not  issue  an  alarm 
before  the  upper  electrode  is  covered  in 
oil. The alarm is issued at the latest when 
the entire sensor is immersed in oil.) 

 

The Oil chamber is full indicator lights up. 

 

The buzzer sounds  

 

The relays are de-energized.  

 

(Please note. A similar alarm is issued 
when the SET/ DM3AL sensor is in the 
air.) 

 

 

 

Once  the  alarm  is  off,  the  indicator  lights 
switch off, the buzzer stops, and the relays 
are energized. 

 

Fault 
alarm 

The  sensor  is  broken,  there  is  a  sensor 
cable  break  or  a  short  circuit,  or  the  sen-
sor  signal  is  not  recognized  (digital  sys-
tem). 

 

 

 

The sensor circuit’s Fault indicator is on.  

 

The buzzer sounds.  

 

The relays are de-energized.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3. Installation example in an oil separator.

 

 