SET/DM3AL 

 

D26052AE-2 

Operation and Installation Manual 

 

 

All rights reserved. 

 

Copyright © 2019, Labkotec Oy 

 

 

4(5) 

5.  OPERATION TEST 

Always  check  the  correct  operation  of  the  alarm 
after  the  installation  and  after  making  the  connec-
tions.  You  should  also  check  the  operation  every 
time  the  separator  is  emptied  or  at  least  once  a 
year.

 

Testing 
the ope-
ration 

1.  Immerse the sensor entirely in 

water. The device should be in 
normal mode (see chapter 4). 

 

2. Lift the sensor in the air or im-

merse it 

in oil. The “Oil chamber 

full” alarm should be issued (see 
Chapter 4). 

 

3. Put the sensor back into water. 

The alarm should stop after a 
while. Clean the sensor before   
installing it into the separator. 
 

If the sensor does not function as described, check 
the device settings from the control unit manual or 
contact the representative of the manufacturer 

6.  SERVICE AND REPAIR 

The  sensor  must  be  cleaned  and  tested  when 
emptying  the  storage  chamber  and  in  connection 
with  the  annual  maintenance.  A  mild  detergent 
(e.g. washing-up liquid) and a scrubbing brush can 
be used for cleaning the sensor, if necessary.

 

During  maintenance  procedures  (such 
as  servicing  the  oil/fuel  separator  sys-

tems),  the  sensor  should  not  be  lifted  out  of 
the  separator  tank  or  installed  back  until 
there is water in the tank. 

The  instructions  concerning  the 
inspection  and  maintenance  of  Ex 

equipment contained in the standards IEC/EN 
60079-17  and  IEC/EN  60079-19  should  be  ob-
served when executing service, inspection, or 
repair procedures 

In fault situation check the cabling and connections 
of possible short-circuits or interruptions, then, if 
necessary, measure the sensor current and com-
pare it with current values below. 

Attention!  If  the  sensor  is  located  in  an  explosive 
atmosphere, the multimeter must be Exi-approved! 

Sensor in the water: 

– 4 mA 

Sensor in the air: 

– 11 mA 

Sensor in the oil or grease: 

– 11 mA 

 

 

 

Also  measure  the  output  voltage  of  control  unit.  It 
is  typically  between  10-

12  V  with  Labkotec  Oy’s 

SET-control  units.  See  details  from  the  manual  of 
the control unit. 

In  case  of  queries, 

please  contact  Labkotec  Oy’s 

service. 

7.  SET/DM3AL 

– and SET/DM3DL –SENSORS 

SET/DM3AL 

–sensor is designed to use with ana-

logical  SET-control  units,  such  as  e.g.  SET-1000, 
OilSET-1000, SET-2000, SET-2000 Hi Level/Oil. 

SET/DM3DL  -sensor  is  primarily  designed  to  use 
with  control  units  that  communicate  digitally,  such 
as e.g. LevelSET S. 

Visually  the  difference  of  SET/DM3AL-  and 
SET/DM3DL 

–sensors  is  that  SET/DM3AL  sensor 

body  is  black  and  SET/DM3DL  sensor  body  is 
grey. 

This operation and installation manual applies only 
to SET/DM3AL-sensor.

 