External Set Point - Terminals 

4, 5, 

and

 6

•  The SC can accept a 4-20mA signal from an Energy Management System (EMS) or other signal 

source to change the Set Point remotely (see pg. 23).

•  Dip switch 6 and 8 must be 

OFF

 and dip switch 7 must be 

OFF

OFF

ON

.  These settings will allow the 

ON

ON

SC to read and monitor the system water temperature using the System temperature sensor and 

monitor the 4-20mA input to change the set point. (See wiring sensor on pg. 3) Also, see pg. 23 for 

EMS programming parameters.

Shutdown or Setback - Terminals 

7

 and 

77

8

•  When adjusting control 

SETBACK

Stb

 setting to 0 the 

SHUTDOWN

 feature is enabled by 

SHUTDOWN

SHUTDOWN

closing a dry contact and all active stages are turned off.  Any pumps controlled by the SC that 

were on will remain on until the System Delay is over, then they will also turn off.   

•  The 

SHUTDOWN

 feature can be used whenever it is desirable to turn off the SC from a remote 

SHUTDOWN

SHUTDOWN

location or another controller (for more details see pg. 24).   

•  When 

SETBACK 

Stb

 is enabled by adjusting control 

SETBACK

Stb

 setting to a value higher 

than 0 and closing a dry contact wired to terminals 7 and 8, the SC will immediately reduce the 

temperature of the circulating hot water by the 

SETBACK

Stb

 setting amount (see pg. 20 to 

adjust the amount of 

SETBACK)

.  All pumps controlled by the SC that were on will remain on until the 

System Delay is over, then they will turn off.  

•  The 

SHUTDOWN/SETBACK

 signal must be a dry contact only to terminals 7 and 8.  No voltage can be 

SHUTDOWN/SETBACK

SHUTDOWN/SETBACK

placed across the 

SHUTDOWN/SETBACK

 terminals.

SHUTDOWN/SETBACK

SHUTDOWN/SETBACK

Prove or Domestic Hot Water (DHW) Input - Terminals 

9

 and 

99

10

•  The Prove or Domestic Hot Water features are set by the External Input Mode in the Power Up 

Sequence. It can be switched between Prove (

Pr

) and Domestic Hot Water (

dh

).

•  The 

PROVE

 feature is used to check system components’ operation before activating any stages. See 

PROVE

PROVE

pg. 24 for typical applications. 

•  If the 

PROVE

 input terminals are open, the SC will enable only the System Output relay.  All Stage 

PROVE

PROVE

Outputs will be off when the 

PROVE

 input is open.

PROVE

PROVE

•  When the Domestic Hot Water (

DHW

•  When the Domestic Hot Water (

•  When the Domestic Hot Water (

) input is enabled by closing a dry contact, the Calculated water 

DHW

DHW

temperature or the Set Point will change to 200°F and the decimal point on the left-most digit on the 

display will fl ash.

•  The 

DHW

 input will take priority over the outdoor reset function or the Outdoor Cutoff temperature.  

DHW

DHW

Regardless of outdoor temperature, when the 

DHW

 input is closed, the SC will Sequence stages to 

DHW

DHW

hold 200°F.

•  If 

NO

 external conditions must be met before Stage Output is activated and terminals 

9

 and 

10

 are not used for Domestic Hot 

Water (see pg. 25), 

DO NOT

 remove the factory installed jumper across the 

PROVE/DHW

 terminals.

PROVE/DHW

PROVE/DHW

•  The 

PROVE/DHW

 signal must be a dry contact only to terminals 9 and 10.  No voltage can be placed across the 

PROVE/DHW

PROVE/DHW

PROVE/DHW

terminals.

IMPORTANT

FACTORY INSTALLED PROVE JUMPER: The 

PROVE

 input terminals must be 

PROVE

PROVE

shorted for Stage Outputs to be activated.  DO NOT remove the factory installed 

PROVE jumper unless replacing it with a Prove or Domestic Hot Water signal.

Outdoor Sensor- Terminals 

11

 and 

12

•  The Outdoor Sensor must be installed if the Outdoor Reset operational mode is required (dip switch 8 

ON

).

ON

ON

•  Installing the Outdoor Sensor is optional in the Set Point mode (dip switch 8 

OFF

). If it is installed, it will act as an Outdoor 

OFF

OFF

Cutoff (see pg. 18). No stages will be activated when the outdoor temperature is above the Outdoor Cutoff. 

•  Locate the Outdoor sensor in the shade on the north side of the building away from doors, 

windows, exhaust fans, vents, or other possible heat sources.

•  The sensor should be mounted at least 4 inches away from the building wall and 

approximately 10 feet above ground level.

•  Sensor wires can be extended up to 500’ by splicing with 18 gauge shielded wire.

•  Do not run sensor wire in conduit with line voltage.

•  Temperature sensors have no polarity.  Connect either wire to terminal 11 and 12.

•  Connect the shield to terminal 

3 SHIELD.

 Note that both sensor shields will be connected 

to terminal 3.

Dry Contact

Prove or Domestic

Hot Water Signal

INPUTS

5 6 7 8 9 10 11

Sensor Com

Dry Contact

Only

Dry Contact

Only

SHUTDOWN

/SETBACK

PROVE

/DHW

OUTD

4-20 ma

INPUTS

5 6 7 8 9 10 11 12

Sensor Com

Dry Contact

Only

Dry Contact

Only

SHUTDOWN

/SETBACK

PROVE

/DHW

4-20 ma

OUTDOOR

To Outdoor Sensor

In Shade

Shield

2 3 4

Com Shield

+

TEMP

4 5 6

+

Sensor Com

4-20 ma

SC Source Current

24VDC Excitation Voltage

(-) Input

(+) Signal

INPUTS

5 6 7 8 9

Sensor Com

Dry Contact

Only

Dry Contact

SHUTDOWN

/SETBACK

PROVE

4

+

4-20 ma

Dry Contact

Shutdown and

Setback Signal

4 5 6

+

Sensor Com

4-20 ma

EMS Sourcing Current

(-) Input

(+) Signal

Содержание SC6

Страница 1: ...20 ma OUTDOOR SC Non Modulating Model SC6 SC6P and SC 12 Output panel to Sequence up to 12 individual stages with lead lag and manual override capabilities Installation and Operation Instructions FOR...

Страница 2: ...WITCH 8 OFF 10 SET POINT CONTROL WITH OSS SEQUENCING 11 OUTDOOR RESET WITH NORMAL SEQUENCING 12 OUTDOOR RESET WITH OSS SEQUENCING 13 SC 6 AND SC 12 OUTPUT WIRING 14 WIRING THE STAGE OUTPUTS 14 SC 6P O...

Страница 3: ...ON Output 5 OFF AUTO ON Output 6 OFF AUTO ON System LEAD OUTPUT ON 4 20 ma OUTDOOR SC Digital display reads sensor value constantly Install a relay for each output stage which will be active Use these...

Страница 4: ...oint control for temperature 8 Outdoor Reset Hydronic heating control with outdoor reset ON ON 1 System Pump SYSTEM relay is on based on outside temp Shutdown and DHW priority 1 Combustion Air Damper...

Страница 5: ...r the enclosure through a different opening from any Class 2 voltage wiring Connect the hot line to terminal marked LINE Connect the neutral line to the terminal marked NEUT The green ground screw mus...

Страница 6: ...tact the Calculated water DHW input is enabled by closing a dry contact the Calculated water DHW temperature or the Set Point will change to 200 F and the decimal point on the left most digit on the d...

Страница 7: ...active The System relay will remain energized even if all Output Stages are off If an outdoor sensor is not connected or registers a fault condition The System relay will be energized when any stage i...

Страница 8: ...rease the value DOWN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequenc...

Страница 9: ...WN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequencing Mode Default N...

Страница 10: ...e System Delay is adjustable from 0 to 30 minutes Default is 0 5 or 6 Times Purge Time The Purge Time should be set to the length of the unit s purge cycle The Purge Time will apply when any ON OFF un...

Страница 11: ...t With a known 4mA input the offset can be set to make the External Set Point 110 F The Program Offset is adjustable between 10 F to 10 F Default is 0 F 4 or more Times Throttling Range The throttling...

Страница 12: ...ill remain energized after the last Output has been turned off or the outdoor temperature rises above the Starter The System Delay is adjustable from 0 to 30 minutes 8 Times Purge Time The Purge Time...

Страница 13: ...egardless of outdoor temperature or the reset curve selected The Offset is adjustable from 40 F to 40 F Default is 0 F 6 Times System Delay The System Delay controls how long the System relay will rem...

Страница 14: ...lly Open N O relay contact The N O contacts are dry contacts only They do not source any voltage Each N O contact is capable of switching 6A resistive Total output of all stages including the SYSTEM m...

Страница 15: ...o the Hi control circuit 3 Stage Lo Mid Hi Units Each unit has one pump relay and three stage relays associated with it Check the chart for the Pump Lo Mid and Hi OUTPUT positions OUTPUT positions OUT...

Страница 16: ...nputs Pump 3 Pump 2 Pump 1 Pump 3 Pump 2 Pump 1 Connect to 120VAC see page 5 Plumbing Class 1 Wiring Class 2 Sensor Wiring The laars SC Sequencing control DOES NOT source power for boiler stages or pu...

Страница 17: ...e HiFire HiFire LoMid LoMid Output 7 Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit HiMid HiMid Output 8 Limit Limit Limit Limit Limit HiFire HiFire HiFire MidFire MidFire HiFire Hi...

Страница 18: ...not register a fault from the Outdoor sensor OPn Open or SHt short For heating when the Outdoor temperature drops below the Outdoor Cutoff temperature the SC will begin to Sequence stages for heat It...

Страница 19: ...heat It will continue to Sequence until the Outdoor temperature rises to 2 F above the Outdoor Cutoff temperature The Outdoor Cutoff temperature can be set from 40 to 100 F In addition an ON setting...

Страница 20: ...ature display ashing the new value NORMAL SEQUENCING SETTINGS REACTION TIME Rt Default 2 minutes The Reaction Time controls how Output Stages are Sequenced on and off based on PID type logic Shorter R...

Страница 21: ...Calculated water temperature to allow the Output Stage to run longer and therefore also be off longer before restarting The Last Stage Hold provides an adjustable temperature value which is added to...

Страница 22: ...Stage The Output with the green light on is currently the Lead Stage Only one Stage Output can be the Lead Stage at any given time The Lead Stage is always the rst stage brought on when there is a cal...

Страница 23: ...sition OFF position OFF OUTPUT LIGHTS The row of red lights marked OUTPUT ON indicate which outputs are energized If the red light next to a Stage Output is on then its output relay should be energize...

Страница 24: ...ust be continuous for any Stage Output to be active If the PROVE PROVE inputs are opened when Stage PROVE inputs are opened when Stage PROVE Outputs are active then they will immediately de energize a...

Страница 25: ...will close the DHW input terminals DHW input terminals DHW If the System Output is con gured for Combustion Air Damper operation the System relay output will be closed when any Stage Output is activa...

Страница 26: ...Temperature Display Outdoor Temperature Display shows SHt The SC sees a short across the input terminals Remove the wires from the OUTDOOR 11 and 12 and 12 and inputs The display should change to rea...

Страница 27: ...t being energized to determine why it is not operating Red stage light is lit but the unit is not on The SC is calling for this unit to be on Follow the procedure above Red stage light is not lit but...

Страница 28: ...rvice Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A...

Отзывы: