Laars SC6 Скачать руководство пользователя страница 21

Page 21

Laars Sequencing Controls

PURGE TIME (

Pt

)  

 

 

 

 

Default: 0 minutes

•  Many units must go through a purge cycle before they are brought on line and can begin generating heating or cooling.

•  The Purge Time should be set to the length of time of the unit’s purge cycle.

•  The Purge Time applies to every Stage Output with ON/OFF units.

•  The Purge Time applies only to the Lo stages of multiple stage units (see charts on pg. 17).

•  When an ON/OFF stage, or a Lo stage, is turned on, the SC will begin counting down the Purge Time.  When the Purge Time 

has elapsed, then the SC will begin counting down the Reaction Time.  Therefore, if the Purge Time applies to a particular Stage 

Output, the minimum run time of that stage is the Purge Time plus half a Reaction Time.

•  The Purge Time can be set from 0 minutes (

0.0)

 to 10 minutes (

10.0

).

BOILER MINIMUM RUNTIME (

brt

 

 

Default: 0 minutes

•  This is the minimum time any Output Stage can run. This timer begins after any Purge Time 

Pt

.

•  The Boiler Minimum Runtime does NOT apply when only one stage holds the load or when all the stages but one have been 

turned off. In those cases, the Last Stage Hold 

LSH

 (see below) applies.

•  The Boiler Minimum Runtime setting prevents stages from being short cycled. 

•  The Boiler Minimum Runtime can be set from 0 minutes (

0.0

) to 6 minutes (

6.0

).

•  The System temperature may rise above Set Point during this time.

LAST STAGE HOLD (

LSH

 

 

 

Default: 10

°

F

•  This 

signifi cantly more output than is required to hold the load, the Output Stage will turn on, rapidly overshoot the Set Point, and 

then turn off as soon as the Purge Time 

Pt 

and Reaction Time are satisfi ed. 

•  In these conditions, it may be desirable to override the Set Point or Calculated water temperature to allow the Output Stage to run 

longer and therefore also be off longer before restarting.

•  The Last Stage Hold provides an adjustable temperature value which is added to the Set Point or Calculated water temperature.

•  When heating, the SC will keep the last Output Stage running until the System temperature exceeds the Set Point or Calculated 

water temperature plus the Last Stage Hold value.

OVERSIZE SYSTEM SEQUENCING SETTINGS

THROTTLING RANGE (

thr

 

 

 

Default: 5

°

F

•  The Throttling Range sets a temperature band around the Set Point or Calculated water temperature that controls when stages 

will be turned on or off. 

•  For example, in the Set Point heating mode, no stages will be activated until the temperature falls one full Throttling Range 

below the Set Point. A second stage will be activated when the temperature falls two full Throttling Ranges below the Set Point, 

and so on, with one extra stage being turned on as the temperature falls additional stages below the Set Point.

•  Stages will be turned off as the temperature rises toward the Set Point with one full throttling range as a differential. 

•  The last stage to be turned off will be allowed to exceed the Set Point by a full throttling range before it is turned off. This helps 

to prevent the last stage from short cycling when the load is low or when the stage is oversized.

Throttling Range Example

Heating Application Set Point = 180

°

F Throttling Range(

thr

) = 5

°

F 4 Boiler Stages, A, B, C, and D

Falling Temperature

Rising Temperature

Temperature

Calculation

Stage Turned On

Stages On

Stage Turned Off

Stages On

185

°

F

180 + (1)

THR

None

None

A

None

180

°

F

180 - (0)THR

None

None

None

A

175

°

F

180 - (1)THR

A

A

B

A

171 to 174

°

F

---

---

A

---

A,B

170

°

F

180 - (2)THR

B

A,B

C

A,B

166 to 169

°

F

---

---

A,B

---

A,B,C

165

°

F

180 - (3)THR

C

A,B,C

D

A,B,C

161 to 165

°

F

---

---

A,B,C

None

A,B,C,D

160

°

F

180 - (4)THR

D

A,B,C,D

None

A,B,C,D

Содержание SC6

Страница 1: ...20 ma OUTDOOR SC Non Modulating Model SC6 SC6P and SC 12 Output panel to Sequence up to 12 individual stages with lead lag and manual override capabilities Installation and Operation Instructions FOR...

Страница 2: ...WITCH 8 OFF 10 SET POINT CONTROL WITH OSS SEQUENCING 11 OUTDOOR RESET WITH NORMAL SEQUENCING 12 OUTDOOR RESET WITH OSS SEQUENCING 13 SC 6 AND SC 12 OUTPUT WIRING 14 WIRING THE STAGE OUTPUTS 14 SC 6P O...

Страница 3: ...ON Output 5 OFF AUTO ON Output 6 OFF AUTO ON System LEAD OUTPUT ON 4 20 ma OUTDOOR SC Digital display reads sensor value constantly Install a relay for each output stage which will be active Use these...

Страница 4: ...oint control for temperature 8 Outdoor Reset Hydronic heating control with outdoor reset ON ON 1 System Pump SYSTEM relay is on based on outside temp Shutdown and DHW priority 1 Combustion Air Damper...

Страница 5: ...r the enclosure through a different opening from any Class 2 voltage wiring Connect the hot line to terminal marked LINE Connect the neutral line to the terminal marked NEUT The green ground screw mus...

Страница 6: ...tact the Calculated water DHW input is enabled by closing a dry contact the Calculated water DHW temperature or the Set Point will change to 200 F and the decimal point on the left most digit on the d...

Страница 7: ...active The System relay will remain energized even if all Output Stages are off If an outdoor sensor is not connected or registers a fault condition The System relay will be energized when any stage i...

Страница 8: ...rease the value DOWN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequenc...

Страница 9: ...WN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequencing Mode Default N...

Страница 10: ...e System Delay is adjustable from 0 to 30 minutes Default is 0 5 or 6 Times Purge Time The Purge Time should be set to the length of the unit s purge cycle The Purge Time will apply when any ON OFF un...

Страница 11: ...t With a known 4mA input the offset can be set to make the External Set Point 110 F The Program Offset is adjustable between 10 F to 10 F Default is 0 F 4 or more Times Throttling Range The throttling...

Страница 12: ...ill remain energized after the last Output has been turned off or the outdoor temperature rises above the Starter The System Delay is adjustable from 0 to 30 minutes 8 Times Purge Time The Purge Time...

Страница 13: ...egardless of outdoor temperature or the reset curve selected The Offset is adjustable from 40 F to 40 F Default is 0 F 6 Times System Delay The System Delay controls how long the System relay will rem...

Страница 14: ...lly Open N O relay contact The N O contacts are dry contacts only They do not source any voltage Each N O contact is capable of switching 6A resistive Total output of all stages including the SYSTEM m...

Страница 15: ...o the Hi control circuit 3 Stage Lo Mid Hi Units Each unit has one pump relay and three stage relays associated with it Check the chart for the Pump Lo Mid and Hi OUTPUT positions OUTPUT positions OUT...

Страница 16: ...nputs Pump 3 Pump 2 Pump 1 Pump 3 Pump 2 Pump 1 Connect to 120VAC see page 5 Plumbing Class 1 Wiring Class 2 Sensor Wiring The laars SC Sequencing control DOES NOT source power for boiler stages or pu...

Страница 17: ...e HiFire HiFire LoMid LoMid Output 7 Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit HiMid HiMid Output 8 Limit Limit Limit Limit Limit HiFire HiFire HiFire MidFire MidFire HiFire Hi...

Страница 18: ...not register a fault from the Outdoor sensor OPn Open or SHt short For heating when the Outdoor temperature drops below the Outdoor Cutoff temperature the SC will begin to Sequence stages for heat It...

Страница 19: ...heat It will continue to Sequence until the Outdoor temperature rises to 2 F above the Outdoor Cutoff temperature The Outdoor Cutoff temperature can be set from 40 to 100 F In addition an ON setting...

Страница 20: ...ature display ashing the new value NORMAL SEQUENCING SETTINGS REACTION TIME Rt Default 2 minutes The Reaction Time controls how Output Stages are Sequenced on and off based on PID type logic Shorter R...

Страница 21: ...Calculated water temperature to allow the Output Stage to run longer and therefore also be off longer before restarting The Last Stage Hold provides an adjustable temperature value which is added to...

Страница 22: ...Stage The Output with the green light on is currently the Lead Stage Only one Stage Output can be the Lead Stage at any given time The Lead Stage is always the rst stage brought on when there is a cal...

Страница 23: ...sition OFF position OFF OUTPUT LIGHTS The row of red lights marked OUTPUT ON indicate which outputs are energized If the red light next to a Stage Output is on then its output relay should be energize...

Страница 24: ...ust be continuous for any Stage Output to be active If the PROVE PROVE inputs are opened when Stage PROVE inputs are opened when Stage PROVE Outputs are active then they will immediately de energize a...

Страница 25: ...will close the DHW input terminals DHW input terminals DHW If the System Output is con gured for Combustion Air Damper operation the System relay output will be closed when any Stage Output is activa...

Страница 26: ...Temperature Display Outdoor Temperature Display shows SHt The SC sees a short across the input terminals Remove the wires from the OUTDOOR 11 and 12 and 12 and inputs The display should change to rea...

Страница 27: ...t being energized to determine why it is not operating Red stage light is lit but the unit is not on The SC is calling for this unit to be on Follow the procedure above Red stage light is not lit but...

Страница 28: ...rvice Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A...

Отзывы: