Laars Sequencing Controls

OUTDOOR RESET SETTINGS

CALCULATED (

CAL

)

•  This is the water temperature the SC will stage units to hold.  It is based on Outdoor temperature, the Reset Ratio, the Offset, the 

Setback/Shutdown values (see pg. 24 and the DHW input (see pg. 25).  

•  The Calculated water temperature can not be less than the minimum water temperature setting (see pg. 8).

•  If either the System or Outdoor sensor is reading a fault condition, all stages will immediately turn off.  The Calculated water 

temperature display will show 

OFF

 to indicate this condition.

OFF

OFF

•  If the outdoor temperature is above the Outdoor Cutoff, the SC will not activate stages.  The Calculated display will show 

OFF

to indicate this condition.

•  A DHW call (see pg. 25) will override the Outdoor Cutoff.  During a DHW call, the Calculated temperature will be 200°F.

• 

Calculated temperature.

•  The Calculated temperature is the average temperature the SC will maintain.  The system can be expected to fl uctuate above and 

below the Calculated temperature.  The size of the fl uctuation depends on the number of stages, the size of each stage, the system 

load, and the Sequencing options.

•  The Calculated temperature is based on all the parameters described above.  The Calculated value can not be changed by 

pressing the 

UP

 or 

UP

UP

DOWN

 button while it is displayed.

DOWN

DOWN

OUTDOOR TEMPERATURE (

OUt

 

 

No Adjustment - Display Only

•  The Outdoor Sensor must be installed for the Outdoor Reset function to work. If the sensor shows 

OPn

 for open or 

SHt

 for 

short, no stages will be activated.

OUTDOOR CUTOFF (

COF

 

 

Default: 60

°

F

•  The Outdoor Cutoff sets at what outdoor temperature the SC will begin heating. This setting will only be available if the SC does 

not register a fault from the Outdoor sensor (

OPn

 Open or 

SHt

 short). 

•  For heating, when the Outdoor temperature drops below the Outdoor Cutoff temperature, the SC will begin to Sequence stages 

for heat. It will continue to Sequence until the Outdoor temperature rises to 2°F above the Outdoor Cutoff temperature.

•  The Outdoor Cutoff temperature can be set from 40 to 100°F. In addition, an ON setting is provided to override the Outdoor 

Cutoff for continuous Sequencing, and an OFF setting can be used to temporarily prevent any Sequencing.

•  The Outdoor Cutoff has a built in 2°F differential. 

•  If the Outdoor temperature rises 2°F above the Outdoor Cutoff, the SC will not activate stages and the Set Point will read 

OFF

,  

unless there is a DHW call.

•  If the building is too cold before the system starts, raise the Outdoor Cutoff 

temperature.

RESET RATIO (

RSt

 

 

 

Default: 7

•  The Reset Ratio controls how much heat will be added based on outdoor 

temperature.  The Reset Ratios are shown as Outdoor Temperature:Water 

Temperature.

•  A 1:1 Reset Ratio signifi es for each degree it gets colder outside, the Calculated 

water temperature will raise 1 degree.

•  The other Reset Ratios available are shown on the right.  

•  The Reset Ratio curves start at 70°F.  At 70°F the SC will require 100°F water.  

Note that this is not the point where the SC will begin giving heat.  That point 

is determined by the Outdoor Cutoff.  Also note that this starting point can be 

changed by adjusting the Offset as shown below.

•  For new installations with standard baseboard heating, begin with a Reset Ratio 

curve of  7.

•  For new installations with radiant heat, begin with a Reset Ratio curve of  4 or 5.

•  Adjust the Reset Ratio value in cold weather.  If the ambient indoor temperatures 

are cold in the cold weather, pick the next higher Reset Ratio (that is, go from 7 to 

8).  If the ambient building temperatures are warm in the cold weather, pick the next 

lower Reset Ratio.

•  Wait at least 24 hours before making another Reset Ratio adjustment.

•  The Reset Ratio can be set from 1 to 12.

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

W

at

er

Te

m

pe

ra

tu

re

(in

°F

)

100

120

110

130

140

150

160

180

170

190

200

210

220

12 11

10

9

8

7

6

4

3

2

5

1

1:4 1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1

4:1

8:1

NOTICE

The SC will not compute a 

Calculated water temperature 

below the minimum water 

temperature setting.

Содержание SC6

Страница 1: ...20 ma OUTDOOR SC Non Modulating Model SC6 SC6P and SC 12 Output panel to Sequence up to 12 individual stages with lead lag and manual override capabilities Installation and Operation Instructions FOR...

Страница 2: ...WITCH 8 OFF 10 SET POINT CONTROL WITH OSS SEQUENCING 11 OUTDOOR RESET WITH NORMAL SEQUENCING 12 OUTDOOR RESET WITH OSS SEQUENCING 13 SC 6 AND SC 12 OUTPUT WIRING 14 WIRING THE STAGE OUTPUTS 14 SC 6P O...

Страница 3: ...ON Output 5 OFF AUTO ON Output 6 OFF AUTO ON System LEAD OUTPUT ON 4 20 ma OUTDOOR SC Digital display reads sensor value constantly Install a relay for each output stage which will be active Use these...

Страница 4: ...oint control for temperature 8 Outdoor Reset Hydronic heating control with outdoor reset ON ON 1 System Pump SYSTEM relay is on based on outside temp Shutdown and DHW priority 1 Combustion Air Damper...

Страница 5: ...r the enclosure through a different opening from any Class 2 voltage wiring Connect the hot line to terminal marked LINE Connect the neutral line to the terminal marked NEUT The green ground screw mus...

Страница 6: ...tact the Calculated water DHW input is enabled by closing a dry contact the Calculated water DHW temperature or the Set Point will change to 200 F and the decimal point on the left most digit on the d...

Страница 7: ...active The System relay will remain energized even if all Output Stages are off If an outdoor sensor is not connected or registers a fault condition The System relay will be energized when any stage i...

Страница 8: ...rease the value DOWN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequenc...

Страница 9: ...WN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequencing Mode Default N...

Страница 10: ...e System Delay is adjustable from 0 to 30 minutes Default is 0 5 or 6 Times Purge Time The Purge Time should be set to the length of the unit s purge cycle The Purge Time will apply when any ON OFF un...

Страница 11: ...t With a known 4mA input the offset can be set to make the External Set Point 110 F The Program Offset is adjustable between 10 F to 10 F Default is 0 F 4 or more Times Throttling Range The throttling...

Страница 12: ...ill remain energized after the last Output has been turned off or the outdoor temperature rises above the Starter The System Delay is adjustable from 0 to 30 minutes 8 Times Purge Time The Purge Time...

Страница 13: ...egardless of outdoor temperature or the reset curve selected The Offset is adjustable from 40 F to 40 F Default is 0 F 6 Times System Delay The System Delay controls how long the System relay will rem...

Страница 14: ...lly Open N O relay contact The N O contacts are dry contacts only They do not source any voltage Each N O contact is capable of switching 6A resistive Total output of all stages including the SYSTEM m...

Страница 15: ...o the Hi control circuit 3 Stage Lo Mid Hi Units Each unit has one pump relay and three stage relays associated with it Check the chart for the Pump Lo Mid and Hi OUTPUT positions OUTPUT positions OUT...

Страница 16: ...nputs Pump 3 Pump 2 Pump 1 Pump 3 Pump 2 Pump 1 Connect to 120VAC see page 5 Plumbing Class 1 Wiring Class 2 Sensor Wiring The laars SC Sequencing control DOES NOT source power for boiler stages or pu...

Страница 17: ...e HiFire HiFire LoMid LoMid Output 7 Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit HiMid HiMid Output 8 Limit Limit Limit Limit Limit HiFire HiFire HiFire MidFire MidFire HiFire Hi...

Страница 18: ...not register a fault from the Outdoor sensor OPn Open or SHt short For heating when the Outdoor temperature drops below the Outdoor Cutoff temperature the SC will begin to Sequence stages for heat It...

Страница 19: ...heat It will continue to Sequence until the Outdoor temperature rises to 2 F above the Outdoor Cutoff temperature The Outdoor Cutoff temperature can be set from 40 to 100 F In addition an ON setting...

Страница 20: ...ature display ashing the new value NORMAL SEQUENCING SETTINGS REACTION TIME Rt Default 2 minutes The Reaction Time controls how Output Stages are Sequenced on and off based on PID type logic Shorter R...

Страница 21: ...Calculated water temperature to allow the Output Stage to run longer and therefore also be off longer before restarting The Last Stage Hold provides an adjustable temperature value which is added to...

Страница 22: ...Stage The Output with the green light on is currently the Lead Stage Only one Stage Output can be the Lead Stage at any given time The Lead Stage is always the rst stage brought on when there is a cal...

Страница 23: ...sition OFF position OFF OUTPUT LIGHTS The row of red lights marked OUTPUT ON indicate which outputs are energized If the red light next to a Stage Output is on then its output relay should be energize...

Страница 24: ...ust be continuous for any Stage Output to be active If the PROVE PROVE inputs are opened when Stage PROVE inputs are opened when Stage PROVE Outputs are active then they will immediately de energize a...

Страница 25: ...will close the DHW input terminals DHW input terminals DHW If the System Output is con gured for Combustion Air Damper operation the System relay output will be closed when any Stage Output is activa...

Страница 26: ...Temperature Display Outdoor Temperature Display shows SHt The SC sees a short across the input terminals Remove the wires from the OUTDOOR 11 and 12 and 12 and inputs The display should change to rea...

Страница 27: ...t being energized to determine why it is not operating Red stage light is lit but the unit is not on The SC is calling for this unit to be on Follow the procedure above Red stage light is not lit but...

Страница 28: ...rvice Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A...

Отзывы: