background image

LAARS Heating Systems

Page 10

2.3.2 Side Wall Combustion Air Terminal

Never obtain combustion air from the pool area.

Corrosion of and/or damage to the pool heater may
result. The Laars side wall combustion air terminal
(listed in Table 1) must be used when the unit takes its
combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1.

Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning fluid,
chlorinated compounds, etc.)

2.

Locate the terminal so that it will not be subject
to damage by accident or vandalism.

3.

Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches
(30 cm) above grade, but the installer may
determine it should be higher, depending upon
local conditions.

4.

If the Pennant is side-wall vented to the same
wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).

2.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the

vent must extend at least 3 feet (0.9m) above the point
at which it penetrates the roof. It must extend at least 2
feet (0.6m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0m), and
high enough above the roof line to prevent blockage
from snow. When the combustion air is taken from the
roof, the combustion air must terminate at least 12"
(30cm) below the vent terminal (see Figure 2).

2.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2).
The opening on the end of the terminal must be at
least 12" (30cm) above the point at which it penetrates
the roof, and high enough above the roof line to
prevent blockage from snow. When the vent
terminates on the roof, the combustion air must
terminate at least 12" (30cm) below the vent terminal.

2.4 Vent Terminals for Outdoor Units

For outdoor applications, the vent and

combustion air openings must be covered with proper
terminals to prevent rain, snow and other objects from
falling into the Pennant.

Part numbers for the terminals to cover the vent

and combustion air openings are shown in Table 6.
Vent opening must be on top of the unit, and the
combustion air opening must be on the back of the
unit. The terminals are connected directly to the unit.
No vent piping is used.

Outdoor Vent

Outdoor

Model (Size)

Terminal

Combustion

Air Terminal

500

20254701

D2007900

750

20254703

D2007900

1000

20254705

D2008000

1250

D2007700

D2008000

1500

D2007700

D2008000

1750

D2007800

D2008000

2000

D2007800

D2008200

Table 6. Vent Terminals for Outdoor Units

Alternately, the installer may use a short piece of

galvanized single wall or B-vent and an approved rain
cap for the vent termination. A minimum 12" of vent
height is acceptable. In addition, a properly sized
single wall galvanized 90° ell can be used for the
intake air terminal, with the open end of the ell facing
down to prevent rain infiltration. The combustion air
inlet opening must still be high enough to prevent
blockage by snow (see Section 2.3.2).

SECTION 3.
Gas Supply and Piping

3.1 Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not by the appliance.

The Pennant’s gas train allows the user to pipe

the gas from either the right side or the left side of the
unit. As shipped, the right side of the gas train is
capped off, and there is a manual valve on the left
side. If desired, the manual valve on the left side of the
gas train may be moved to the right side, and the cap
on the right side may be moved to the left.

Review the following instructions before

proceeding with the installation.
1.

Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Laars
Heating Systems appliances are normally
equipped to operate at elevations up to 2000
feet (610m). Pennant appliances may be adjusted
to operate properly at higher elevations;
however, input will be reduced if the heating
value of the gas supply is below sea level values.

2.

The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas
pressure is 5" W.C. (1.2kPa).

3.

Refer to Table 7, size supply.

Содержание Pennant PNCP

Страница 1: ...alified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death...

Страница 2: ...amming Control Parameters 13 5 3 3 Setpoint LSP 14 5 3 4 Differential dLS 14 5 3 5 Pump Operation 14 5 3 6 Heater Purge Pump Delay PD 14 5 4 Limit Controls 14 SECTION 6 Operating Instructions 6 1 Sequ...

Страница 3: ...oper installation The Pennant appliance is protected against over pressurization A pressure relief valve is fitted to all appliances It is installed on the outlet header at the water outlet of the app...

Страница 4: ...age to the area adjacent to the appliance or to lower floors of the structure When such a location is not available it is recommended that a suitable drain pan adequately drained be installed under th...

Страница 5: ...86 101 8 26 30 78 29 75 8 22 8 22 80 203 8 20 12 30 8 20 1500 78 199 39 101 101 8 26 30 78 29 75 8 22 8 22 91 231 8 20 12 30 8 20 1750 89 226 44 113 101 8 26 30 78 29 75 8 22 8 22 101 256 8 20 14 36...

Страница 6: ...er may result SECTION 2 Venting and Combustion Air 2 1 Combustion Air Pennant pool heaters must have provisions for combustion and ventilation air in accordance with section 5 3 Air for Combustion and...

Страница 7: ...ke to the heater as directly as possible Seal all joints with tape Provide adequate hangers The unit must not support the weight of the combustion air intake pipe Maximum linear pipe length allowed is...

Страница 8: ...dition to following proper vent sizing construction and safety requirements from the National Fuel Gas Code ANSI Z223 1 or in Canada from CSA B149 1 as well as all applicable local codes it is require...

Страница 9: ...possible locations under windows or near doors should be avoided 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas Code requires that it be at least 12 inches 30 c...

Страница 10: ...door Units For outdoor applications the vent and combustion air openings must be covered with proper terminals to prevent rain snow and other objects from falling into the Pennant Part numbers for the...

Страница 11: ...line must be firing at maximum capacity to properly measure the inlet supply pressure The pressure can be measured at the supply pressure port on the gas valve Low gas pressure could be an indication...

Страница 12: ...er outlet This sensor is a capillary and bulb It shall be used with the immersion well that is provided Figure 5 Pool Heater Piping The Pennant Pool Heater is shipped with a field installed mixing sys...

Страница 13: ...wer connection Connect a fused 15 ampere 120 volt supply to the black wire Neutral leg is connected directly to the white wire Ground wire is connected to the green wire Wiring diagrams are shown in S...

Страница 14: ...6 Operating Instructions 6 1 Sequence of Operation The amber Ready light on the front panel indicates that the control system is energized Upon a call for heat from the pool temperature control the gr...

Страница 15: ...0 to 2500 Feet Altitude The setup must be checked before the unit is put in operation Problems such as failure to start rough ignition strong exhaust odors etc can be due to improper setup Damage to...

Страница 16: ...ignition control label c Open gas shutoff valve Restart the appliance The ignition sequence will start again and the burner will start The appliance will return to its previous mode of operation NOTE...

Страница 17: ...ated temperatures in spas and hot tubs can be hazardous Follow these Safety Rules for Hot Tubs Spa or hot tub water temperatures should never exceed 104 F 40 C A temperature of 100 F 38 C is considere...

Страница 18: ...e the retainer clip and the control Replace in reverse order 7 2 7 Ignition Controls The ignition controls ensure the proved interrupted type ignition system They control the hot surface ignitor s and...

Страница 19: ...nt rear and bottom of the integral metal sections and remove the heat controls the blower s pre purge and post purge Pennant models 500 750 and 1000 have one ignition control Models 1250 1500 1750 and...

Страница 20: ...y adjusting the air shutter s at the bottom of the fan s Check the CO2 and adjust the air shutters if further adjustment to the CO2 is needed Models 1250 1500 1750 and 2000 have two blowers and two ai...

Страница 21: ...and not at the light blue wire on that connector replace the control 8 6 Troubleshooting Pennant Controls The Pennant series consists of three models with one ignition module 500 750 1000 and four mod...

Страница 22: ...placement Parts Only genuine Laars replacement parts should be used 9 1 General Information To order or purchase parts for the Laars Pennant contact your nearest Laars dealer or distributor If they ca...

Страница 23: ...op 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002 24 Exhaust Plenum 5C2007 10C2007 10C2007 20C2007 20C2007 20C2007 20C2007 25 Bracket Chamber Front 5C2009 7C2009 10C2009 25 Bracket Chamber Front Lef...

Страница 24: ...401 20255401 20255401 20255401 20255401 20255401 20255401 49 Relief Valve 75 PSI A0063300 A0063300 A0063600 A0063600 A0063600 A0063600 A0002700 50 Tee Adapter Outlet Bronze 20150301 20150301 20150301...

Страница 25: ...700 E2310700 E2310700 74 Transformer E2108700 E2108700 E2108700 E2310400 E2310400 E2310400 E2310400 75 Switch Rocker E2106600 E2106600 E2106600 E2106600 E2106600 E2106600 E2106600 Sensor E2314300 E231...

Страница 26: ...0 1 1 2 1 1 81 Burner Tray Manifold 3 Burners Left L2012800 L2012800 L2012800 L2012800 L2012800 1 1 3 1 2 81 Burner Tray Manifold 4 Burners Right L2012700 L2012700 L2012700 L2012700 1 1 1 2 81 Burner...

Страница 27: ...Pennant Pool Heater Page 27 Figure 9 Sheet Metal Components...

Страница 28: ...LAARS Heating Systems Page 28 Figure 10 Internal Components NOTE Model 2000 shown for reference...

Страница 29: ...Pennant Pool Heater Page 29 Figure 11 Heat Exchanger Components A See pump chart below for pump numbers...

Страница 30: ...LAARS Heating Systems Page 30 Figure 12 Pennant 500 1000 Ladder Diagram SECTION 10 Wiring Diagrams...

Страница 31: ...Pennant Pool Heater Page 31 Figure 13 Pennant 1250 2000 Ladder Diagram...

Страница 32: ...LAARS Heating Systems Page 32 Figure 14 Pennant 500 1000 Wiring Schematic...

Страница 33: ...Pennant Pool Heater Page 33 Figure 15 Pennant 1250 2000 Wiring Schematic...

Страница 34: ...LAARS Heating Systems Page 34 Figure 16 Field Wiring PNCP 500 1000...

Страница 35: ...Pennant Pool Heater Page 35...

Страница 36: ...93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars...

Отзывы: