LAARS Heating Systems
Page 10
2.3.2 Side Wall Combustion Air Terminal
Never obtain combustion air from the pool area.
Corrosion of and/or damage to the pool heater may
result. The Laars side wall combustion air terminal
(listed in Table 1) must be used when the unit takes its
combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1.
Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning fluid,
chlorinated compounds, etc.)
2.
Locate the terminal so that it will not be subject
to damage by accident or vandalism.
3.
Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches
(30 cm) above grade, but the installer may
determine it should be higher, depending upon
local conditions.
4.
If the Pennant is side-wall vented to the same
wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point
at which it penetrates the roof. It must extend at least 2
feet (0.6m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0m), and
high enough above the roof line to prevent blockage
from snow. When the combustion air is taken from the
roof, the combustion air must terminate at least 12"
(30cm) below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
field-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2).
The opening on the end of the terminal must be at
least 12" (30cm) above the point at which it penetrates
the roof, and high enough above the roof line to
prevent blockage from snow. When the vent
terminates on the roof, the combustion air must
terminate at least 12" (30cm) below the vent terminal.
2.4 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper
terminals to prevent rain, snow and other objects from
falling into the Pennant.
Part numbers for the terminals to cover the vent
and combustion air openings are shown in Table 6.
Vent opening must be on top of the unit, and the
combustion air opening must be on the back of the
unit. The terminals are connected directly to the unit.
No vent piping is used.
Outdoor Vent
Outdoor
Model (Size)
Terminal
Combustion
Air Terminal
500
20254701
D2007900
750
20254703
D2007900
1000
20254705
D2008000
1250
D2007700
D2008000
1500
D2007700
D2008000
1750
D2007800
D2008000
2000
D2007800
D2008200
Table 6. Vent Terminals for Outdoor Units
Alternately, the installer may use a short piece of
galvanized single wall or B-vent and an approved rain
cap for the vent termination. A minimum 12" of vent
height is acceptable. In addition, a properly sized
single wall galvanized 90° ell can be used for the
intake air terminal, with the open end of the ell facing
down to prevent rain infiltration. The combustion air
inlet opening must still be high enough to prevent
blockage by snow (see Section 2.3.2).
SECTION 3.
Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not by the appliance.
The Pennant’s gas train allows the user to pipe
the gas from either the right side or the left side of the
unit. As shipped, the right side of the gas train is
capped off, and there is a manual valve on the left
side. If desired, the manual valve on the left side of the
gas train may be moved to the right side, and the cap
on the right side may be moved to the left.
Review the following instructions before
proceeding with the installation.
1.
Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Laars
Heating Systems appliances are normally
equipped to operate at elevations up to 2000
feet (610m). Pennant appliances may be adjusted
to operate properly at higher elevations;
however, input will be reduced if the heating
value of the gas supply is below sea level values.
2.
The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas
pressure is 5" W.C. (1.2kPa).
3.
Refer to Table 7, size supply.
Содержание Pennant PNCP
Страница 27: ...Pennant Pool Heater Page 27 Figure 9 Sheet Metal Components...
Страница 28: ...LAARS Heating Systems Page 28 Figure 10 Internal Components NOTE Model 2000 shown for reference...
Страница 29: ...Pennant Pool Heater Page 29 Figure 11 Heat Exchanger Components A See pump chart below for pump numbers...
Страница 30: ...LAARS Heating Systems Page 30 Figure 12 Pennant 500 1000 Ladder Diagram SECTION 10 Wiring Diagrams...
Страница 31: ...Pennant Pool Heater Page 31 Figure 13 Pennant 1250 2000 Ladder Diagram...
Страница 32: ...LAARS Heating Systems Page 32 Figure 14 Pennant 500 1000 Wiring Schematic...
Страница 33: ...Pennant Pool Heater Page 33 Figure 15 Pennant 1250 2000 Wiring Schematic...
Страница 34: ...LAARS Heating Systems Page 34 Figure 16 Field Wiring PNCP 500 1000...
Страница 35: ...Pennant Pool Heater Page 35...