background image

Trianco Newport

Page 3

SECTION 1.
General Information

These boilers have been designed and

constructed according to ASME codes using heavy

gauge steel tubes and boiler plate.

The reliable heat exchanger incorporates special

flue baffles to assure quiet and efficient operation and

a purpose designed ceraform combustion chamber

minimizes base loss and also provides a tight

enclosure with the heat exchanger.

The domestic hot water coil is located at the top

of the boiler in the hottest zone for an ample supply of

hot water and a unique feature of its attachment is the

raised coil flange which allows the use of clamping

bolts rather than studs, thereby eliminating water leaks

caused by broken studs.

The complete unit comes pre-assembled for easy

installation and is encased by a fully insulated baked

enamel jacket.

1A. Boiler Installation

For recommended installation practice reference

should be made to the National Fire Protection

Standard for Oil Burning Equipment (NFPA 31 -

Latest Edition).

1B. Freight Claims

Inspection should be made of boiler and its

components for damage upon arrival. Any claims for

damage should immediately be filed against the

carrier by the consignee.

1C. Boiler Location

The boiler should be positioned as near to the

chimney as possible and have a minimum smoke pipe

connector length of 18"(457mm).

Caution

Newport boilers must not be directly connected to a
heating system using oxygen permeable tubing (see
warranty). Use a water to water heat exchanger
between boiler and system to prevent corrosion.

1D. Boiler Clearances (to combustibles)

Top - 6" (152mm)

Front - 24" (610mm)

Rear - 6" (152mm) Sides - 6" (152mm)

1E. Floor

The boiler must be mounted on a

noncombustible masonry or cement floor with no

combustibles underneath.

1F. Combustion and Ventilation Air

To insure an adequate supply of fresh air for

combustion and ventilation an inlet and outlet opening

should be provided at floor and ceiling level. Each

opening must have a minimum of one square inch

(16.5 sq. cm) of free area for every 1,000 BTU/h

(293kW) of input or 140 square inches (903 sq. cm)

per one gallon (3.785L) of oil burned per hour. The

openings must not be in a position liable to blockage.

1G. Chimney and Draft Requirements

To assure the safe and proper operation of the oil

burner the boiler must be connected to a chimney

having sufficient draft at all times to evacuate the flue

gases to atmosphere. A draft regulator must be

installed in the smoke-pipe as near to the flue as

possible and adjusted to achieve an overfire draft of

0.01 ins. W.C.

1H. Jacket (normally fitted)

If not fitted, assemble panels in accordance with

instructions in Figure 4.

1I. Oil Burner (normally fitted)

If not fitted, insert burner tube into boiler so that

it is approximately ¼" (6mm) from inside wall of

ceraform chamber, then clamp mounting flange and

bolt up to front-plate (see Figure 3).

The burner should be wired and connected to the

oil line in accordance with the manufacturer’s

instructions.

1J. Boiler Controls (normally fitted)

If controls are supplied separately, fit them to the

boiler in the positions shown in Figure 3, with jacket

in place.

Circulator - 1¼" return tapping at front of boiler.

Tridicator - temp/press. gauge.

Relief Valve - Provide ¾" tee and auto vent as

shown on front page for air elimination.

Aquastat Relay - L8124A - ¾" tapping in coil

plate.

Fit a drain valve (not supplied) in a tee at

hydronic return connection and check all connections

are made water tight.

1K. Oil

USE ONLY No. 2 HEATING OIL. Do not use

gasoline, crankcase draining or any oil containing

gasoline.

1L. Oil Storage and Pipe Layout

Storage Tank: 

Consult local fire and building

codes for acceptable fuel storage methods in your area.

Fuel Line:

 A single pipe system of not less than

3/8" OD copper tubing is recommended when fuel

Содержание newport NP 100

Страница 1: ...gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exa...

Страница 2: ...n Air 3 1G Chimney and Draft Requirements 3 1H Jacket normally fitted 3 1I Oil Burner normally fitted 3 1J Boiler Controls normally fitted 3 1K Oil 3 1L Oil Storage and Pipe Layout 3 1M Electrical Wir...

Страница 3: ...insure an adequate supply of fresh air for combustion and ventilation an inlet and outlet opening should be provided at floor and ceiling level Each opening must have a minimum of one square inch 16 5...

Страница 4: ...water inlet 3 Connect pressure relief valve 11 if required by codes maximum 150 PSI as close to the unit as possible No other valves or restrictions may be installed between the DHW coil and the reli...

Страница 5: ...ping NPT Tankless Coil Tridicator Hydronic Return 1 Hydronic Supply 1 Aquastat Well Relief Valve Fitting Figure 2 Components Location PRESSURE RELIEF VALVE DRAIN PIPE IN ACCORDANCE WITH EXISTING REGUL...

Страница 6: ...ons may be removed by an acid treatment but your servicing company can advise on the most satisfactory method of cleaning or whether a replacement coil is necessary 1T Coil Removal 1 Switch off electr...

Страница 7: ...NPT 1 1 1 1 1 1 1 Specifications Firing Rate GPH 0 75 0 85 1 00 1 10 1 25 1 35 1 50 Input MBTU hr kW 85 25 103 30 120 35 133 39 150 44 160 47 177 52 Output MBTU hr kW 74 21 90 26 105 30 116 34 130 38...

Страница 8: ...ide 2 to front panel 3 with screws 2 Slide assembled jacket over boiler and secure side panels to base tray 3 Fix rear panel 4 to sides 4 Adjust corner brackets 5 on heat exchanger so they touch insid...

Страница 9: ...information PIPE LENGTHS H One Pipe Gravity System 3 8 O D 1 2 O D ft m ft m ft m 0 0 0 0 0 0 1 0 5 33 10 1 65 19 8 3 0 9 65 19 8 130 39 6 5 1 5 130 39 6 260 79 2 6 2 195 59 4 325 99 PIPE LENGTHS H Tw...

Страница 10: ...t means overload protection as required 24V Room Thermostat 1K L1 Hot Power Supply 120V L2 Circulator Switch Low Limit Circulator Hi Limit 1K2 Oil Burner Relay Heating Circulator AQUASTAT RELAY L8124A...

Страница 11: ...3 058 panel 2500 020 Burner Panel Assembly 125 155 before 1990 53 058 Burner Panel Assembly 125 155 after 1990 use with p n 53 0560 Part Number Description Size 53 090 Flue Cover Assembly 125 155 53 1...

Отзывы: