Page 33
1
2
3
4
Condensate
drain pipe
4.15
Disposal of Condensate
High efficiency gas condensing Water Heaters create
condensation when operating. Condensation has
acidic (pH) of approximately 4-5.
Condensate must be drained in accordance with all
local regulations. Follow your local code with regards
to the disposal of condensation.
One of 4 disposal methods must be followed
1. to floor drain
2. to neutralizer drain (optional kit * )
3. to laundry tub
4. to condensate pump (field supplied)
If a neutralizer is installed, periodic replacement of the
lime stone (or neutralizing agent) will be required. The
rate of depletion of the lime stone varies upon usage
of the Water Heater.
During the first year of operation, please check the
neutralizer every few months for depletion.
Apply only corrosion-resistant materials for the
condensate drain lines such as 1/2˝ PVC, CPVC,
Polypropylene pipe or included plastic hose.
NOTICE
Category II & IV water heaters must be installed with a
means provided for the drainage of condensate.
AVIS
Catégorie II & ; IV chauffe-eau doit être installé avec
une moyens prévus pour l’évacuation des condensats.
CAUTION
Condensate is mildly acidic (pH=5), and may harm
some floor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe,
and anything that will come in contact with the
condensate can withstand the acidity, or neutralize
the condensate before disposal.
Damage caused by
failure to install a neutralizer kit or to adequately
treat condensate will not be the manufacturer’s
responsibility.
*
Contact Laars to order Kit# A2123601
_________________________________________
Содержание MSTWW199
Страница 36: ...LAARS Heating Systems Page 36 4 19 Wiring Diagram...
Страница 37: ...Mascot ST Tankless Water Heater Page 37 4 20 Ladder Diagram...
Страница 50: ...LAARS Heating Systems Page 50 6 2 Fault Tree Analysis 6 2 1 Flame Detection 6 2 2 Gas Detection...
Страница 61: ...Mascot ST Tankless Water Heater Page 61 Cover Assembly 21...