Page 12
LAARS Heating Systems
Figure 8. Top-To-Rear Vent Collar.
Adapter Plate
Top Panel
Vent
Collar/Stack
Blank Plate
(Heater
Jacket)
Blank Plate On
Flue Collector
Blank Plate On
Heater Jacket
Top Panel
1. Removal of Blank Plate and Adapter
Plate From Heater
3. Blank Plate Placement
Over Stack Top Opening
Blank Plate
(Flue
Collector)
Vent
Collar/Stack
2. Removal of Blank Plate From
Rear of Flue Collector
4. Connecting Vent Collar/Stack
to Flue Collector
Table 7. Vent Piping Specifications (Combustion Air Exhaust).
Heater
Pipe Diameter
Max Pipe Length
Max No.
Side Wall
Side Wall
Size
of Elbows
Vent Terminal
Combustion Air
in.
mm
ft.
m
Part Number
Terminal Part Number
320M
6
152
50
15
5
D2004500
20260701
400M
7
178
50
15
5
D2004600
20260702
IMPORTANT:
Maximum pipe length allowed is 50 feet (15m), regardless of the number of elbows. Maximum number of elbows allowed is 5.
Vent pipe minimum clearance from combusible surfaces is 6 inches (152mm).
OUT OF