Mighty Max Volume Water Heater
Page 15
Term
Description
Pipe
Single-wall galvanized steel pipe,
24 gauge minimum.
Joint Sealing
Permanent duct tape or aluminum
tape
Insulation
Not required, but recommend R5
insulation for cold installations
(consult American Society of
Heating, Refrigerating, and
Air Conditioning Engineers
(ASHRAE) handbook
Table 9. Required Combustion Air Piping Material.
2.12 Electrical Wiring
WARNING
Electrically ground the heater in accordance with
the latest edition of ANSI/NFPA 70. In Canada, use
CSA C22.1. Do not rely on the gas or water piping
to ground the metal parts of the heater. Often,
plastic pipe or dielectric unions isolate the heater
electrically. Service and maintenance personnel
who work on or around the heater may be standing
on wet floors and could be electrocuted by an un-
grounded heater. Electrocution can cause serious
injury or death.
AVERTISSEMENT
La chaudière doit être mise à la terre selon les
exigences officielles locales ou, en l’absence de
toute instruction officielle, l’installation doit être
conforme avec la dernière édition du Code
électrique canadien CSA C22.1, Partie 1, au
Canada. N’utilisez pas la tuyauterie de gaz ou
d’eau pour mettre à la terre les parties métalliques
de la chaudière. Les unions diélectriques ou avec
tuyau en plastique peuvent isoler la chaudière
électriquement. Les membres du personnel de
service et d’entretien qui travaillent sur et autour de
la chaudiére peuvent marcher sur des planchers
mouillés et pourraient se faire électrocuter par une
chaudière non mise à la terre.
1.
Check heater wiring and pump for correct
voltage, frequency, and phase.
2.
Wire the heater and pump exactly as shown in
the wiring diagram supplied with the heater (see
Figure 11).
3.
Electrically interlock the pump and heater so the
heater cannot come on unless the pump is
running.
4.
Connect all field-installed devices (relays,
timers, temperature devices, etc.) to the heater
wiring at points labeled “Field Interlock” (see
Figure 11).
OUT OF
PRODUCTION
Содержание Mighty Max VW
Страница 25: ...Mighty Max Volume Water Heater Page 25 Figure 19 Troubleshooting Chart OUT OF PRODUCTION ...
Страница 29: ...Mighty Max Volume Water Heater Page 29 Front View Right Side View OUT OF PRODUCTION ...
Страница 30: ...Page 30 LAARS Heating Systems Front View Rear View Right Side View Left Side View OUT OF PRODUCTION ...
Страница 31: ...Mighty Max Volume Water Heater Page 31 OUT OF PRODUCTION ...