LAARS Heating Systems
Page 10
If the system temperatures are unknown at the
time of installation, class IIC or higher venting
material is recommended.
The MagnaTherm is a Category IV appliance and
may be installed with the standards listed on Table 6.
The unit’s vent can terminate through the roof, or
through an outside wall.
All installations must be done following the vent
supplier’s recommended installation techniques.
If these are not available, refer to the LAARS
recommendations for the material used.
NOTE: For Category IV boilers, have horizontal
runs sloping upwards not less than 1/4 inch
per foot (21 mm/m) from the boiler to the
vent terminal; be installed so as to prevent
accumulation of condensate; and, where necessary,
have means provided for drainage of condensate.
ATTENTION: Pour la catégorie IV, les chaudières
ont horizontal en pente vers le haut au moins
1/4 de pouce par pied (21 mm/m) à partir de la
chaudière pour l’évent borne; être installé de façon
à éviter l’accumulation de condensats; et, le cas
échéant, ont des moyens prévus pour l’évacuation
des condensats.
This will allow the condensate to run back to the
MagnaTherm to drain. Route the vent pipe to the
heater as directly as possible. Seal all joints. Provide
adequate hangers as required in the venting system
manufacturer’s Installation Instructions, or at least
every 4 feet.
The unit must not support the weight of the vent
pipe. The maximum equivalent pipe length allowed
is 100 feet (30m). Each elbow is considered to be 5
feet (1.5m). LAARS offers accessories to use with
horizontal and vertical exhaust vent systems, as
shown in Table 5
3.2.1
Common Venting
The MagnaTherm can be common vented, however,
the common venting must be a professionally
designed and approved system. MagnaTherm
units are never permitted to share a vent with any
Catagory 1 appliances.
3.2.3
Venting Requirements Unique to
Canada
MagnaTherm boilers and water heaters are Vent
Category IV appliances. Per the requirements of
Table 5. Vent Accessories
(Place in section 3.1)
Model 1600
Model 2000
Model 2500
Model 3000
Model 3500
Model 4000
Screen for horizontal galvanized air pipe
D2012104
D2012101
D2012101
D2012102
D2012103
D2012103
Screen for horizontal PVC air pipe
CA012004
CA012001
CA012001
CA012002
CA012003
CA012003
Screen for horizontal polypropylene air pipe
CA012204
CA012201
CA012201
CA012202
CA012203
CA012203
Screen for vertical galvanized air pipe
D2012204
D2012201
D2012201
D2012202
D2012203
D2012203
Screen for vertical PVC air pipe
CA012404
CA012401
CA012401
CA012402
CA012403
CA012403
Screen for vertical polypropylene air pipe
CA012604
CA012601
CA012601
CA012602
CA012603
CA012603
Table 3a - Ducted Air Accessories
(Place in section 3.2)
Model 1600
Model 2000
Model 2500
Model 3000
Model 3500
Model 4000
Horizontal vent terminal for stainless steel
D2012004
D2012001
D2012001
D2012002
D2012003
D2012003
Screen for horizontal CPVC vent
CA012104
CA012101
CA012101
CA012102
CA012103
CA012103
Screen for vertical stainless steel vent
D2012304
D2012301
D2012301
D2012302
D2012303
D2012303
Screen for vertical CPVC vent
CA012504
CA012501
CA012501
CA012502
CA012503
CA012503
Table 3* - Vent Accessories
(Place in section 3.5)
Model 1600
Model 2000
Model 2500
Model 3000
Model 3500
Model 4000
Air intake screen for unit placed outdoors
CA0011904
CA011901
CA011901
CA011902
CA0011903
CA0011903
Vent terminal for unit placed outdoors
CA011803
CA011801
CA011801
CA011802
CA011803
CA011803
Table 3** - Air & Vent Accessories for Units Placed Outdoors
Installation Standards
Material
United States
Canada
Stainless steel
UL 1738
Venting must be ULC S636 certified for use as
venting material. The venting material class must
be chosen based upon the intended application
of the boiler, and must be installed according to
the maximum flue gas temperature and the vent
manufacturer’s instructions.
CPVC, sch 40
ANSI/ASTM F441
Polypropylene
Pending APPROVAL
ULC S636 Class 2C
Table 6. Required Exhaust Vent Material
Содержание MagnaTherm MGH1600
Страница 4: ...LAARS Heating Systems...
Страница 35: ...MagnaTherm Boilers and Water Heaters Page 31...
Страница 98: ...LAARS Heating Systems Page 94 1 13 12 4 3 5 13 2 15 Final Assembly DETAIL A 9 10 8 Final Assembly...
Страница 110: ...LAARS Heating Systems Page 106 6 2 7 11 1 5 4 12 10 3 3 8 9 6 Control Panel Assembly...