Page 39
HTD
0
S16
Read
Inlet Sensor
AI
0
Read
1
S16
Read
Outlet Sensor
AI
1
Read
2
S16
Read
Flue Sensor
AI
2
Read
3
S16
Read
DHW Sensor
AI
3
Read
4
S16
Read
System Inlet Sensor
AI
4
Read
5
S16
Read
System Outlet Sensor
AI
5
Read
6
S16
Read
Outdoor Sensor
AI
6
Read
12
S16
Read
Flame Signal 1
AI
12
Read
14
S16
Read
0-10VDC (4-20mA) Input for BMS
AI
14
Read
17
S16
Read
0-10VDC (4-20mA) Input for Blower Speed
AI
17
Read
bit0 = Flow Switch
bit1 = LWCO
bit2 = MRHL
bit3 = Blocked Flue
bit4 = High Gas Pressure
bit5 = Low Gas Pressure
bit6 = Field Interlock
bit7 = ARHL
bit0 = Field Input 1
bit1 = Field Input 2
0=None
1=Anti-Short Cycle
2=Service
3=DHW
4=Cascade
5=External
6=CH1
7=CH2
10=Anti-Frost
11=Warm weather shutdown
bit0 = Run contact
bit1 = Alarm Contact
bit2 = DHW Pump
bit3 = System Pump
bit4 = Louver contact
bit5 = Aux dry contact 1
bit6 = Aux dry contact 2
bit7 = Boiler pump
bit8 = Aux powered contact
bit 0 = Burner 1 Pilot Gas valve
bit 1 = Burner 1 Gas valve 1
23
S16
Read
0-10VDC (4-20mA) Output for Pump Speed
AI
23
Read
24
S16
Read
0-10VDC (4-20mA) Output for Fan Speed
AI
24
Read
27
S16
Read
Modulating Fan 1 - Speed
AI
27
Read
33
S16
Read
Modulating Burner1 Firing rate
AI
33
Read
FLOW SWITCH = 0
LOW WATER CUT OFF ERROR = 1
MANUAL RESET HIGH LIMIT = 2
PRESSURE SWITCH = 3
HIGH GAS PRESSURE SWITCH = 4
LOW GAS PRESSURE SWITCH = 5
FIELD INTERLOCK = 6
SPARE SAFETY CHAIN = 7
OUTLET PROBE LOCKOUT = 8
OUTLET PROBE DRIFT = 9
OUTLET PROBE HIGH LIMIT = 10
FLUE PROBE LOCKOUT = 11
FLUE PROBE DRIFT = 13
FLUE PROBE HIGH LIMIT = 14
INLET PROBE LOCKOUT = 15
DELTA-T = 16
GENERIC LOCKOUT = 17
BURNER APS LOCKOUT = 18
BURNER PARASITIC FLAME = 20
BURNER MAX IGNITION ATTEMPTS = 22
BURNER MAX FLAME LOSS = 24
NO LOCKOUT = 255
24 VDC ERROR = 30
24 VAC ERROR = 31
DHW PROBE ERROR = 32
SYSTEM SUPPLY PROBE ERROR = 33
SYSTEM RETURN PROBE ERROR = 34
OUTDOOR PROBE ERROR = 35
HIGH LIMIT AUTO ERROR = 41
HIGH DELTA-T ERROR = 42
FAN SPEED ERROR = 43
38
U16
Read
History - DHW Demand Cycles
AI
38
Read
39
U16
Read
History - CH1 Demand Cycles
AI
39
Read
40
U16
Read
History - CH2 Demand Cycles
AI
40
Read
43
U16
Read
History - Cascade Demand Cycles
AI
43
Read
44
U16
Read
History - Burner Stage 1 Cycles
AI
44
Read
48
U16
Read
History - Boiler Pump Cycles
AI
48
Read
Notes
Map Descriptor Name
BACnet
Data Type
BACnet
Object ID Read/Write
Read
AI
19
Read
AI
18
Read
Read
Digital Output Status
AI
21
Read
Read
Error Code
AI
36
Read
Safety Chain Status
Non-safety Chain Status
Demand Source
Gas and Pilot Valve Status
AI
22
AI
20
Modbus
Address Type
R/W
18
S16
Read
19
S16
Read
20
S16
Read
Read
S16
21
Read
S16
22
36
S16
Read
35
S16
Read
Lockout code
AI
35
7.E Modbus to BACnet Memory Map