25
Vertical Direct Vent Installations
The EVERHOT
®
IGI series water heater can also be installed to vent vertically through the roof using a
vertical discharge adaptor, optional vent extension tubes, a condensate collector, a roof terminal, and a
universal lead tile. In addition to the total equivalent feet limit of 41 feet (12.5 m), the maximum height of
the venting system is limited to 21 feet (6.4 m). A condensate collector is required on all vertical venting
heights over 5 feet (1.5 m). Determine the distance in height required from the water heater and order
the vent extension pipes required.
Vertical Vent Installations
Figure 10
The condensate collector will require a ¾” CPVC pipe connection with a trap to act as a seal against
discharging flue products into the room. Run the condensate line to a suitable drain. The condensate
collector must be located within 5 feet (1.52 m) of the water heater vent connection.
NOTICE
The Condensate Collector must be located within 5 feet (1.52 m) of the water heater vent connection.
CAUTION
A trap must be installed after the condensate connection to prevent flue products from leaking into the
room.
Содержание IGI-180C-5N
Страница 7: ...7 EVERHOT IGI Model Series Dimensions Figure 1...
Страница 14: ...14 Recommended Piping for a Basic Installation Figure 2...
Страница 15: ...15 Recommended Piping for a Circulation System Figure 3...
Страница 35: ...35 Horizontal Vent System Installation examples Figure 36...
Страница 38: ...38 Vertical Vent System Installation examples Figure 40...
Страница 39: ...39 Cut Line Template Figure 41...
Страница 44: ...44 Wiring Diagram Schematic Figure 43...
Страница 59: ...59 Schematic Diagram of Internal Parts Figure 53...
Страница 61: ...61 Internal Components...
Страница 62: ...62 Internal Components...
Страница 63: ...63 Electrical Components...
Страница 67: ...67 NOTES...