Figure 15. Typical installation.

4.

Separate the union on the economizer pipe and

remove the lower half of the union from the

economizer outlet.

5.

Undo the four economizer retainer nuts. (see

Figure 14). Remove the boiler drain valve.

6.

Undo the four clamps that hold the outer shroud

to the upper head. (see Figure 14)

7.

Drop the economizer, inner shroud and outer

shroud together by separating the upper head and

outer shroud.

8.

Clean combustion coil with a wire brush.

9.

Reassembly is done in reverse order. Use

silicone sealer to seal joint between upped head

and outer shroud.

5.6 Combined Water (potable) Heating

and Space Heating

(see Figure 15)

Piping and components connected to this water

heater for the space heating application shall be

suitable for use with potable water.

Toxic chemicals, such as used for boiler

treatment, shall not be introduced into the potable

water used for space heating.

This water heater when used to supply potable

water shall not be connected to any heating system or

component(s) previously used with a nonpotable

water heating appliance.

When the system requires water for heating at

temperatures higher than required for other uses, an

anti-scald mixing or tempering valve shall be installed

to temper the water for those uses in order to reduce

scald hazard potential.

SECTION 6.
Quick Reference Trouble Shooter

6.1 Short Cycling

1.

Tank aquastat set too high

2.

Units shut down before reaching limit.

Continuously restarts without resetting

a.) Limit out of calibration

b.) Wrong air/gas orifices for input or fuel (refer

to 9600 gas orifice chart ONLY)

Figure 14. Cutaway view.

Содержание 9600 HWG

Страница 1: ...service technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury pro...

Страница 2: ...ide Wall 5 2 4 Locating Unit for Proper Vent Height 5 2 5 Locating Unit with Respect to Ventilation 5 2 6 Locating Unit with Respect to Storage Tanks 5 SECTION 3 Installation 3 1 Installing Vent Pipin...

Страница 3: ...rements take precedence over the general instructions contained herein All electrical wiring is to be done in accordance with local codes or in the absence of local codes with 1 the National Electrica...

Страница 4: ...y AGA CGA for installation on combustible flooring in basements in closets utility rooms or alcoves It must not be installed on carpeting The location for the unit should be chosen with regard to the...

Страница 5: ...vent locations you select must permit direct pipe runs to the terminal from the boiler Since the 9600 HWG Water Heater is designed to drain any water that collects in the vent it is important that yo...

Страница 6: ...Install a shut off valve in the piping between the thermometer fitting and the tank The following steps are recommended for vent installation 1 Obtain the necessary 3 or 4 diameter plastic piping and...

Страница 7: ...ntains a minimum of 10 psi static pressure If water hardness is greater than 10 grains a water soft ening or particle suspension device must be installed be fore the heater or warranty will be void Co...

Страница 8: ...Page 8 LAARS Heating Systems Figure 7 Two temperature system Figure 6 Single 9600 HWG Storage Tank...

Страница 9: ...9600 HWG Water Heater Page 9 Figure 8 Multiple 9600 HWG s storage tanks...

Страница 10: ...t attempt because of air contained in gas lines In this case blower will stop after 5 minutes Should this happen turn off main switch Wait five minutes and turn on switch again If burner fails three t...

Страница 11: ...s or hose see Figure 9 3 The pressure relief valve should be operated manually at least once a year To do this place a suitable container under the relief valve drain pipe The discharge from this valv...

Страница 12: ...tall new O ring valve top and replace valve top on valve and install and tighten screws 6 Restore pressure to water heater bleed air from the petcock on the valve and restart water heater 7 Replace ac...

Страница 13: ...heater for the space heating application shall be suitable for use with potable water Toxic chemicals such as used for boiler treatment shall not be introduced into the potable water used for space h...

Страница 14: ...Defective low limit operating control safety limit or system differential pressure switch 2 Jump control wires one control at a time to identify open circuit in control no continuity FOR DIAGNOSIS ONL...

Страница 15: ...ge 15 Figure 16 Wiring diagram Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify Proper Operation After Servicing F...

Страница 16: ...Page 16 LAARS Heating Systems Figure 18 Lighting and shutdown procedures...

Страница 17: ...nstallation manual Set regulator for maximum run pressure of 9 3 Remove blower and inspect flame holder burner for hole 4 Check that the blower flanges and gas piping are sealed 6 4 Occasional Lockout...

Страница 18: ...310 Blower Assembly HWG 250 2400 086 Combustion Coil Assembly 9 2400 082 Flame Holder 7 2400 308 Flame Holder HWG 250 2400 286 Ignitor 2400 088 Capacitor Motor Starter 2400 224 Control Board 2400 014...

Страница 19: ...9600 HWG Water Heater Page 19...

Страница 20: ...vice Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars co...

Отзывы: