2.3.5 Current
Limit
– Allows adjustment of the current limit from 50% to 110% of rated output.
1.
Select LIMIT CURRENT from configuration menu
o
Select current limit as a percentage of the rated output current of the rectifier.
2.3.6 Temperature
Compensation – Allows enable or disable of the temperature compensation feature.
1.
Select TEMP. COMP. from configuration menu
o
Select DISABLE or ENABLE
NOTE: JP4 must be removed when temperature compensation is enabled.
2.3.7 Alarm
Settings – Allows setting the alarm thresholds for the provided alarms and the alarm time delay
1.
Select ALARM SETTING from the configuration menu.
o
In the ALARM SETTING menu select ALARM DELAY
Select the alarm delay in seconds. Delay can be set from 1 second to 30 seconds
1.
In the ALARM SETTING menu select DC LOW VOLTAGE
o
Select the desired low voltage alarm point in V/C (volts per cell)
1.
In the ALARM SETTING menu select DC HIGH VOLTAGE
o
Select the desired high voltage alarm point in V/C (volts per cell)
1.
In the ALARM SETTING menu select DC LOW CURRENT
o
Select the desired low current alarm point
1.
In the ALARM SETTING menu select AC FAIL VOLTAGE
o
Select the AC voltage operating range for the rectifier. Alarm will activate when the AC voltage
is below the selected value
2.3.8 Factory
Settings
– Allows the user to reset all settings to how they were programmed from the
factory. To reset the ESCR settings to the original factory settings, scroll to FACTORY SETTING in the
configuration menu. Select FACTORY SETTING. This will not change the BASIC OUTPUT settings.