10
2 Operation
2.1
Starting the ESCR
All equipment is shipped from the factory fully checked and adjusted based on the factory settings
listed below. Before connecting the battery check with the battery manufacturer for the correct voltage
settings and adjust the configuration accordingly (refer to section 2.3 for configuration). Failure to
match the charger settings with the connected battery may damage or shorten the life of the battery.
Configurations
The ESCR rectifier is available in the following configurations:
ESCR-20/10-12/24V-AV1
This model can be configured for 12V-10AMP or12V-20AMP or 24V-10AMP
ESCR-40/20-12/24V-AV1
This model can be configured for 12V-40AMP or 24V-20AMP
ESCR-6-12/24V-AV1
This model can be configured for 12V-6AMP or 24V-6AMP
ESCR-10-24V-AV1
This model is configured for 24V-10AMP
ESCR-20-24V-AV1
This model is configured for 24V-20AMP
DC output configuration is field selectable and must be configured by user.
AC input is 120V/208V/240VAC and is selected automatically when power is applied.
FLOAT VOLTAGE
EQUALIZE VOLTAGE
2.17 volts/cell (LEAD)
2.33 volts/cell (LEAD)
2.25 volts cell (VRLA)
2.27 volts/cell (VRLA)
1.40 volts/cell (NiCad)
1.55 volts/cell (NiCad)
Table 6 – DC Voltage Output Ratings
FLOAT EQUALIZE
2.12-2.3 volts/cell + 0.1 volt (LEAD) (VRLA)
2.25-2.4 volts/cell +0.1volt (LEAD) (VRLA)
1.39-1.45 volts/cell + 0.1 volts (NICAD)
1.5-1.60 volts/cell + 0.1volts(NICAD)
Table 7 – Voltage Range Output Ratings
ESCR-20/10-12/24V-AV1: 20A@12V setting; 10A@24V setting
ESCR-40/20-12/24V-AV1: 40A@12V setting; 20A@24V setting
ESCR-6-12/24V-AV1: 6A@12V setting; 6A@24V setting
ESCR-4-24V-A1: 4A@24V setting
ESCR-10-24V-AV1: 10A@24V setting
ESCR-20-24V-AV1: 20A@24V setting
Table 8 – Output Current
Содержание ESCR
Страница 6: ...v Quick Start Guide...
Страница 7: ...1 Quick Start Guide...
Страница 9: ...3 Figure 2 ESCR Mounting Dimensions for D99 Figure 3 ESCR Mounting Dimensions for D100...