Installation
2.1
Mounting the CUPS
NOTE:
Before installation, please inspect the unit. Assure nothing inside the package is damaged. Please keep
the original package in a safe place for future use.
Interchangeable mounting brackets are provided for 19/23” rack mounting
(Refer to visual in Section 2.1). Foot
stands are provided. Use the foot stand provided for tower mounting (Refer to visual in Section 2.2). When
mounting the CUPS in any configuration, consider the size and weight of the UPS. The rack must be able to
support the weight of the UPS, as well as an additional safety factor. Refer to Table 2 to verify the weight of the
UPS. The following considerations should be taken:
•
The location chosen for the UPS
should be within an ambient temperature range of 32˚F to 1
04
˚F (0˚C
to 4
0˚C) with a non
-condensing relative humidity no higher than 20 - 95%.
•
The UPS should be mounted in an area free of explosive materials and away from any liquids.
•
Avoid using equipment in location with corrosive gases and dust.
•
A clearance of at least 6 inches of free air must be maintained in front and on top for proper cooling.
•
Maintain 12 inches (300 mm) or more of clearance at the rear of the UPS when rack mounting in order
to allow for operation and maintenance.
•
All hardware should be corrosion resistant.
2.1.1 Rack-Mount Installation
Step 1:
Install the rack-mounting brackets to the CUPS.
Step 2:
Mount the CUPS to the rack using the necessary hardware.
Step 1
Step 2
2.1.2 Tower Installation (Optional)
Step 1:
Assemble the foot stand as shown below using the necessary hardware.
Step 2:
Remove the front panel of the CUPS, gently pull the display out, rotate it counterclockwise 90
º
, and align
the display to the CUPS display slot to reposition the display vertically.
Step 3:
Mount the CUPS to the foot stand.
Step 1
Step 2
Step 3