background image

12 

 

3.2.2  Controls  

Button 

Function 

ON/Mute/Up 

Button  

 

 

1-Second Press: 

Change Selection (while in Setting Menu) 

Mute Alarm (while in Battery Mode or Bypass Mode) 

3-Second Press: 

Power ON UPS (Online Mode) 

Self-Test (while in AC Mode, ECO Mode, or Converter Mode)  

Select/Down 

Button 

 

 

1-Second Press: 

View Parameters (Refer to Section 3.2)

 

Change Selection (while in Setting Menu) 

3-Second Press: 

Enter Settings Menu (while in Standby Mode or Bypass Mode)

 

OFF/Enter 

Button 

 

 

1-Second Press: 

Confirm Selection (while in Setting Menu) 

  

3-Second Press: 

Power OFF UPS (while in Battery Mode) 

Transfer to Bypass Mode (if Bypass Mode is enabled in Settings Menu)  

ON/Mute/Up + 

Select/Down 

Button 

 

 

1-Second Press: 

Exit Settings Menu / Return to Upper Settings Menu (while in Setting Menu) 

 

  

3-Second Press: 

Transfer to Bypass Mode (if Bypass Mode is enabled in Settings Menu)

 

Table 6 

 Button Operation  

 

3.2.3  Audible Alarms 

Battery Mode 

Beeps every 5 seconds 

Low Battery 

Beeps every 2 seconds 

UPS Overload 

Beeps every second 

Fault 

Continuous Beep 

Bypass Mode 

Beeps every 10 seconds 

 

Table 7 

 Audible Alarms 

  

 

 

Содержание CUPS

Страница 1: ...nd Operation Manual This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com 106 Bradrock Dr Des Plaines IL 60018 1967 CPN 144266 Instruct...

Страница 2: ...ids nor any wet material comes in contact with any internal components Do not operate this UPS outside the input and output ratings listed on the UPS nameplate Do not use this UPS for any purpose not...

Страница 3: ...ion number to have the UPS sent back for evaluation and repair CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for a...

Страница 4: ...3 2 2 Understanding the Rear Panel View 4 2 3 Battery Connections 6 2 3 1 Internal Battery Connections 6 2 3 2 External Battery Connections 6 2 4 AC Input Connections 7 2 5 AC Output Connections 7 2 6...

Страница 5: ...t 15 18 4 16 EPO Logic Set 16 18 4 17 Site Fault Detection Enable Disable Set 17 18 4 18 Battery Mode Backup Timer Display Setting Set 18 19 4 19 AC Mains Voltage Range Set 19 19 4 20 Escape Set 00 19...

Страница 6: ...pability to connect multiple battery packs provide the user the flexibility to accommodate different type loads size and backup requirements This UPS system offer an ECO mode operation which improves...

Страница 7: ...Assure to deliver the spent battery to a recycling facility or ship it to La Marche Mfg in the replacement battery packing material 1 2 Moving the CUPS Follow the steps below 1 Inspect and verify that...

Страница 8: ...nsing relative humidity no higher than 20 95 The UPS should be mounted in an area free of explosive materials and away from any liquids Avoid using equipment in location with corrosive gases and dust...

Страница 9: ...o Non Critical Loads 2 Output Receptacles Connect to Critical loads 3 AC Input 20A for 1 KVA 30A for 3KVA system 4 Network Fax Modem Surge Protection 5 USB Communication Port 6 RS 232 Port 7 SNMP Inte...

Страница 10: ...y inductive loads C Inverter Inverter converts DC power to regulated sine wave AC power by using high frequency switches Transformer connected to inverter helps to get pure sine wave D Batteries Seale...

Страница 11: ...Reconnecting Internal Battery 2 3 2 External Battery Connections NOTE Skip this step if external batteries are not required External battery packs can be used with the CUPS to allow for bigger battery...

Страница 12: ...it provided with a maximum branch circuit overcurrent protection in accordance with the National Electrical Code Input Plugs required per UPS model UPS Model Input Plug Overcurrent Protection CUPS 1kV...

Страница 13: ...UPS it will provide advanced communication and monitoring options USB Port RS 232 Port Intelligent Slot Figure 7 Communication Ports 2 7 Emergency Power OFF Function The CUPS is equipped with EPO Emer...

Страница 14: ...9 Standby Mode Figure 10 Online Mode 230VAC Example Power Up Batteries 1 Press the ON Mute button on the front panel for two seconds to power on the CUPS display Refer to Figure 11 2 Within 5 seconds...

Страница 15: ...y BAT 0 0A Battery Current OUT 0 1A AC Output Current IN 0 2A AC Input Current BAT 83 Battery Capacity OUT 0 Output Load Capacity 31 5 C UPS System Temperature The diagram on the bottom section of the...

Страница 16: ...ad Indicates that programmable management outlets are enabled Mode Operation Information Icon Function Indicates the mains supply is connected to the CUPS Indicates the battery is working Indicates ba...

Страница 17: ...ss Mode OFF Enter Button 1 Second Press Confirm Selection while in Setting Menu 3 Second Press Power OFF UPS while in Battery Mode Transfer to Bypass Mode if Bypass Mode is enabled in Settings Menu ON...

Страница 18: ...Battery Mode Backup Time RAT Running Battery Mode Backup Time SD Shutdown OK OK ON ON BL Battery Low OL Overload OI Over Input Current NC Battery Not Connected OC Over Charge SF Site Wiring Fault EP...

Страница 19: ...the UPS can be set at a constant output frequency 50 Hz or 60 Hz The CUPS will still charge the battery at Frequency Converter Mode Battery Mode The CUPS will supply power to the load using the batte...

Страница 20: ...et 01 The 01 Setting allows the user to configure the CUPS output voltage Below are the available output voltage selections per CUPS model 100 127VAC Models 100 110 115 120 125VAC Default 200 240VAC M...

Страница 21: ...ass Voltage Range Set 07 The 07 Setting allows the user to adjust the HLS High Loss Setting and the LLS Low Loss Setting for Bypass Mode The HLS is the maximum allowable bypass voltage threshold The L...

Страница 22: ...power for the critical loads during Battery Mode The backup time can be set at the range of 0 999 minutes By default the backup time is set to 999 minutes 4 11 Battery Mode Backup Timer Set 11 The 11...

Страница 23: ...e user to adjust the CUPS charger output voltage when in float Float charging is used for all normal battery charging needs The charger float voltage can be set at the range of 2 20 2 33 volts per cel...

Страница 24: ...ll not utilize the AC mains supply Online Mode Bypass Mode and will enter Battery Mode if applicable Use the Up Down buttons to select HLS or LLS and confirm selection using the OFF ENTER button Below...

Страница 25: ...e Wiring Fault Sounding every 2 seconds EPO Enable Sounding every 2 seconds Over Temperature Sounding every 2 seconds Charger Failure Sounding every 2 seconds Battery Fault Sounding every 2 seconds At...

Страница 26: ...l inspection on all internal components 4 Check front panel meters for accuracy and LED operation 4 2 Troubleshooting Procedure Troubleshooting should be performed only by trained service personnel or...

Страница 27: ...nal batteries This is normal and should cause no harm to personnel Connect the cables quickly and firmly 3 The CUPS is equipped with internal batteries and only a qualified service person can replace...

Страница 28: ...s from UPS output After repetitive overloads the UPS is locked in Bypass Mode Connected devices are fed directly by the mains Remove excess loads from UPS output first then shut down the UPS and resta...

Страница 29: ...88 90 BATTERY Battery Type 12V 9AH 12V 9AH 12V 9AH Numbers 2 4 6 Recharge Time 3 hours recover to 95 capacity for internal battery 2A charging current Charging Current Default 2A Max 8A adjustable Ch...

Страница 30: ...00VA 1640W 18 2A 110Vac input 1800VA 1500W 18A 100Vac input CUPS 3kVA 100 125Vac 50 60Hz 24A 1 3000VA 3000W 24A 125Vac input 3000VA 3000W 25A 120Vac input 3000VA 3000W 26 1A 115Vac input 3000VA 3000W...

Страница 31: ...n installation adjustments and service arrangements Should minor adjustments be required the local La Marche sales representative should be contacted to provide this service only All sales are final O...

Страница 32: ...31 Appendix E Document Control and Revision History Part Number 144266 Instruction Number P25 LACUPS 2 Issue ECN 22796 01 21 23019 09 21 22796 01 21...