INSTALLATION, OPERATING AND TROUBLESHOOTING INSTRUCTIONS FOR MODEL A75D / A75DE –

THREE PHASE

 

Page 6 of 20 

 
 

GENERAL 

The  LaMarche  models  A75D  and  A75DE  are  SCR  battery  chargers.    These  models  are  designed  with  a 
LCD Digital Display. The A75DE is designed as a battery eliminator and can be operated with or without 
batteries connected. 
 
The LaMarche model A75D/A75DE series battery charger is a solid state unit utilizing SCR technology.  It 
has +/- 0.5% regulation from no load to full load over the specified input voltage, frequency and ambient 
temperature range. 
 
The  A75D/A75DE  series  is  offered  with  DC  output  voltages  of  24,  48  or  130VDC  with  output  currents 
from 25 to 500 Amps.  These chargers may be powered with 208, 240, or 480VAC.  The current limit is 
factory set at 105% and is adjustable from 50 to 110%. 
 

OUTPUT RATINGS 

DC VOLTAGE 

The A75D/A75DE series battery chargers provide separate voltage adjustments for floating or equalizing 
lead or nickel cadmium cells.  The float or equalize mode of operation is selected by pressing the equalize 
button on the display which is located on the front of the battery charger. 
 
The factory settings are as follows: 

Float Voltage 

Equalize Voltage 

2.17 volts/cell (lead) 

2.25 volts/cell (VRLA) 

2.33 volts/cell (Lead) 

2.27 volts/cell (VRLA) 

1.40 volts/cell (NC) 

1.55 volts/cell (NC) 

 

 

VOLTAGE RANGE 

 

Float 

Equalize 

Lead Acid 

NiCad 

24V 

23 – 29.5 

24 - 31 

11 – 13L 

17 – 20N 

48V 

46 - 57 

48 - 61 

22 – 26L 

33 – 39N 

130V 

115 - 140 

123 - 145 

53 – 62L 

83 – 93N 

 
 
Note: 

Typical cell ranges are based on the following: 

Lead Acid 2.17 V/C Float, 2.33V/C Equalize 
NiCad 1.44 V/C Float, 1.55V/C Equalize 

 
 

OUTPUT CURRENT 

See Input Current Chart 
 

REGULATION  

Steady State output voltage remains /- 0.5% of rated voltage for any load current from no load 
to full load and for input voltages 10% / -12%. 
 

FILTERING 

A75D – NO FILTERING 
A75DE - 100 mv RMS, with or without a battery connected 
 
 

 

Содержание A75D

Страница 1: ...Digital METERS THREE PHASE ECN DATE CPN124997 20535 8 14 20098 8 13 20084 8 13 19784 12 12 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 3061 ISSUE DATE ECN 19609 7 12 INSTRUCT...

Страница 2: ...UTMOST IMPORTANCE THAT EACH TIME BEFORE USING THIS UNIT YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by t...

Страница 3: ...Gases from the battery will corrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on t...

Страница 4: ...provide a copy of the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or...

Страница 5: ...f the battery cables charger output and relay rack terminals Connect the proper battery cable to the ground bar or battery charger output terminal Energize the power supply by turning on the units AC...

Страница 6: ...75D A75DE series battery chargers provide separate voltage adjustments for floating or equalizing lead or nickel cadmium cells The float or equalize mode of operation is selected by pressing the equal...

Страница 7: ...E PHASE VOLTAGE MODEL NUMBER D B C A75D A75DE 208 240 480 50 24V 30 26 13 75 24V 44 38 19 100 24V 59 51 26 125 24V 74 64 32 150 24V 89 77 38 200 24V 118 102 51 50 48V 15 13 6 75 48V 22 19 10 100 48V 3...

Страница 8: ...E terminals of all chargers can be connected together to ensure all chargers automatically switch into and out of equalize mode together PROTECTION Current Walk In The output current gradually increas...

Страница 9: ...terminals together If the charger is equipped with a Remote Equalize Terminal connect the RE terminals together CURRENT WALK IN Output current will gradually increase after the battery charger is tur...

Страница 10: ...INFORMATION MINIMUM WIRE SIZES See Wire Size Chart lists the ac input and dc output minimum wire size requirements At distances exceeding 10 feet the dc wire size should be chosen to keep the voltage...

Страница 11: ...500000 3 52620 400 400000 1750 1750000 2 66360 500 500000 2000 2000000 DENOTES ALL SIZES LARGER THAN 0000 ARE EXPRESSED IN MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ult...

Страница 12: ...le lists the AC input and the DC output minimum wire size requirements At distances exceeding 10 feet the DC wire size should be chosen to keep the voltage difference between the units DC output termi...

Страница 13: ...done in the following order single power supply 1 Connect AC input line to the terminal block provided Be sure the AC circuit breaker is off 2 Observe the polarity of the battery cables and the rectif...

Страница 14: ...changing the rectifier current limit between 50 110 of rated output Turning the adjustment which is located on the unit front panel clockwise lowers the current limit turning counterclockwise raises...

Страница 15: ...lashing LED Solid LED High DC voltage 2 45 Vpc Lead Acid High DC voltage shutdown HVSD 2 5 Vpc Lead Acid Low DC current 5 A Timer mode Mode 0 Equalize Time 8 Hours OPT 46R RELAY PACKAGE 2 SETS OF FORM...

Страница 16: ...indicate The timer will automatically return the charger to the float mode when the equalize cycle is complete MODE 1 DISPLAY indicates P01 This mode of operation automatically starts an equalize cycl...

Страница 17: ...can be caused by defective batteries and customer loads make sure batteries and loads are free from defects NOTE If the problem is found to be located in the printed circuit boards the board should be...

Страница 18: ...output Meter should not indicate If the meter reads full scale deflection this indicates an ac dc short During shipping an AC wire may rub against the DC lugs terminals etc and cause a short These pro...

Страница 19: ...nal components 4 Check front panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REP...

Страница 20: ...r installation installation adjustments and service arrangements Should minor adjustments be required the local La Marche sales representative should be contacted to provide this service only All sale...

Отзывы: