MODEL A36D SERIES - INSTRUCTIONS AND TROUBLESHOOTING
Page 6 of 33
Current limiting
A circuit adjustable from 90% to 115% of rated load, limits the DC output current. The current limit is
factory set at 115% of rated output.
Refer to Section 9.6 for details.
4.3
HIGH-VOLTAGE SHUTDOWN
A circuit provided for load protection which causes the rectifier to shut down should its output voltage
exceed a preset value.
Refer to Section 9.3 for details.
4.4
REMOTE SENSING
The point of output DC voltage sensing may be moved to battery or power board terminals to compensate
for voltage drops in cables (See Section 7.3)