Appendix A: A31 Specifications
ELECTRICAL
DC Input Voltages
24VDC: 21
–
30VDC
48VDC: 42
–
60VDC
120VDC: 105
–
150VDC
Voltage Range: ± 10% from nominal
AC Output
AC Output Voltage: 1 Phase
–
120VAC (Standard), 208VAC, 220VAC, 240VAC
AC Output Power: 1000VA
–
15000VA (0.8 lagging factor)
Regulation
Line Regulation: ±3% over DC battery range
Load Regulation: ±4% from no load to full load
Frequency Regulation: ±0.5% (Quartz Clock)
Approximate
Efficiency
24VDC: 70
–
75%
48VDC: 85
–
90%
120VDC: 85
–
90%
Total Harmonic
Distortion
Approximately 5% at nominal DC input & full load. Less than 3% for any single
harmonic
Meters
Options 06C/06D
–
Analog DC Ammeter & DC Voltmeter ± 2% Accuracy
Option 22D
–
Digital DC Ammeter & DC Voltmeter ± 1% Accuracy
PROTECTION
Current Limit
Approximately 150%, protected by AC Output Breaker
Input/ Output
Input: DC Breaker, Reverse Polarity Protection Indicator, Filter Pre-Charge Circuit
Output: AC Breaker, AC Bypass Line Fuse
ENVIRONMENTAL
Audible Noise
Less than 65dBA at any point 5 feet from any vertical surface
Operating
Temperature
32 to 122˚F (0 to 50˚C)
Storage
Temperature
-40 to 140°F (-40 to 60°C)
Relative Humidity
0 to 95% (non-condensing)
Cooling
Convection Cooled (4000VA and larger inverters are fan-assisted)
Shock
The inverter in its shipping container withstands shock developed when one edge
of the container is dropped six inches while the opposite edge is resting on the
ground, or it is dropped two inches without any physical damage or degradation of
the electrical performance.
Vibration
The inverter in its shipping container, withstands vibration encountered in shipping
without physical damage or degradation of the electrical performance.
Altitude
This inverter is capable of operation at altitudes up to 3,300 feet at an ambient
temperature of up to +50°C (122°F) and 10,000 feet at an ambient temperature of
up to +40°C (104°F).
Ventilation
The inverter should be mounted so that ventilating openings are not blocked and
air entering the cabinet does not exceed 50° C (122°F).