Revised 3/27/20 Copyright © 2020 La Cornue Page 13
Best Practices
Venting Installation Instructions
(All Models)
—Addendum to Installation Instructions—
IMPORTANT:
Problems caused by improper installations are not covered by the manufacturer’s warranty.
IMPORTANT:
Undersized and improperly installed duct pipe and/or other ventilation components will cause
excessive static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well
as inadequate ventilation.
1.
Building Codes
Kitchen Hood Ventilators should be installed by qualified technicians familiar with state and local building
codes.
2.
Duct Pipe and Fittings (Elbows, Transitions, Roof & Wall Caps)
a.
Use round or rectangular rigid metal duct only. Where possible, use round duct as it creates the least
amount of static pressure. DO NOT use flex duct.
b.
All duct sections and fittings (EXCEPT DAMPERS, per Section 4), should overlap and be connected with
at least 3 – 4 equally spaced screws and wrapped tightly with 2 – 3 layers of Aluminum Foil Metal Duct
Tape. This type of duct tape is more durable than traditional cloth duct tape. DO NOT use butt joints.
c.
For best air flow, elbows and pipe size transition fittings should not be directly connected to one
another. Where possible, always include at least 15 inches of straight pipe between fittings.
3.
Duct Pipe and Fitting Sizes.
(See
Duct Sizing Chart and Area Calculations
Section for more detail)
IMPORTANT:
DO NOT use either of the following duct pipe sizes or fitting sizes for any kitchen hood
ventilator installations:
- 6” round duct pipe
- 3.25” x 10” rectangular x 6” round transitions
- 6” x 7” linear transitions
IMPORTANT:
No portion of any length of duct pipe or fitting should be smaller than the discharge port of the
ventilator. This is very important because any type of restriction anywhere in the ventilation system will
cause increased static pressure (air resistance), that may result in rattling, vibration and air buffeting noises,
as well as inadequate ventilation.
Duct Runs – Length
a.
Configure the ventilation duct run to be as short and as direct to the outside as possible. Minimize
the number of elbows and transition fittings used. Complex or long runs should be reviewed by a
qualified installer.
b.
No portion of the ducting should be run so that the exhaust air flows downward. Since exhaust heat
rises, forcing the air to flow downward will cause increased static pressure. As previously mentioned,
improperly installed duct pipe will cause excessive static pressure (air resistance), that may result in
rattling, vibration and air buffeting noises, as well as inadequate ventilation.