La Cornue 75LCI18 Скачать руководство пользователя страница 14

 

Revised 3/27/20                                               Copyright ©  2020  La Cornue                                                                    Page 14 

 

c.

 

Duct runs for 600 – 1200 CFM ventilator models should not exceed 35 linear feet with two 90-degree 
elbows and two 45-degree elbows, a damper and a roof or wall cap.  Longer runs or additional elbows 
will result in decreased ventilation performance.  Each 90-degree elbow is the equivalent of 6 linear 
feet of duct pipe; each 45-degree elbow is equivalent to 3 linear feet of duct pipe. 
 

d.

 

Always run ventilator ducts to the outdoors.  DO NOT terminate a duct into an attic, basement, 
garage, crawl space under a house, a chimney, other ducting or an enclosed room. 
 

4.

 

Dampers 

 

 
IMPORTANT:

  DO NOT USE SCREWS TO ATTACH ANY TYPE OF DAMPER AS THE SCREWS MAY BLOCK THE 

DAMPER BLADES. 
 

IMPORTANT:

  DO NOT USE MORE THAN ONE DAMPER IN THE VENTILATION SYSTEM.  

NOTE

:  Many styles of 

roof caps and wall caps have built-in dampers.  See 

Roof Caps and Wall Caps

 section for more detail. 

Always use carefully crafted, tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically 
view and test the damper blades to make certain they are opening and closing correctly.  Make sure that the 
damper blades do not touch the duct walls and that there is no debris blocking the free movement of the 
damper mechanism.  Common things to look for include screws protruding into the blade’s path, overspray of 
paint, plaster and insulation.  If using rectangular duct, be sure that all four sides of the duct are on the 
outside of the damper’s start collar or frame. On ventilator installations designed to recirculate the exhaust 
air back into the kitchen, be sure to remove the aluminum damper blade before attaching the duct to the 
damper frame.

 

 

600 – 1200 CFM Ventilator Models

 

600-1200 CFM models have either an 8" or 10" round start collar that requires use of a damper with 
the corresponding dimension. 
 

 

Damper in Roof Cap or Wall Cap 

In ventilation systems utilizing a roof cap or wall cap 

with

 a built-in damper, do not install an 

additional in-line damper. Two dampers are unnecessary and will cause increased static pressure (air 
resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate 
ventilation. 
 

In-line Damper

 (for ventilation systems utilizing a roof cap or wall cap 

without

 a built-in damper)

 

In cold weather areas, installing an “in-line” damper may be the preferred type of installation.  This is 
because in-line dampers installed just above the perimeter of the heated space (the ceiling) will 
reduce the amount of cold air traveling down the duct into the heated space and into the kitchen 
through the ventilator. In-line dampers must be installed so that the exhaust air flow will open the 
butterfly blades.   
 
For 

horizontal duct runs

, the in-line damper must be installed so that the hinge between the two 

butterfly blades is 

vertical

—the hinge pin must point up and down.  Otherwise, because of gravity, 

the damper’s blades will not close and the damper will not prevent backdrafts.   
 
For 

vertical duct runs

, the in-line damper’s hinge will be 

horizontal

 (sideways), which is correct for 

vertical duct runs.  Gravity will help close the damper blades after each use.  
 
For 

upward slanted duct runs

, the in-line damper’s hinge must point to the top and bottom sides of 

the duct.  In his position, gravity will help close the damper blades after each use.  Otherwise, because 
of gravity, the damper’s blades will not close and the damper will not prevent backdrafts.   
 

Содержание 75LCI18

Страница 1: ...Revised 3 27 20 Copyright 2020 La Cornue Page 1 ATTENTION PLEASE REMOVE THE RIGHT SIDE BAFFLE FILTER TO LOCATE YOUR NEW REMOTE CONTROL ...

Страница 2: ...Revised 3 27 20 Copyright 2020 La Cornue Page 2 ...

Страница 3: ...200 10 165LCI22 64 3 8 22 1200 10 180LCI18 70 3 8 18 1200 10 180LCI22 70 3 8 22 1200 10 Before beginning installation please thoroughly read and become familiar with these instructions Installation and service must be completed by a qualified installer Failure to properly install this product may void the warranty Installer Please leave Installation Instructions with the range hood Insert Owner Pl...

Страница 4: ...d Use proper pan size Always use cookware appropriate for the size of the surface element WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close fitting lid cookie sheet or metal tray then turn off the burner BE CAREFUL TO PREVENT BURNS If the flames do not go out immediately EVACUATE AND CALL THE FIRE DEPARTMENT ...

Страница 5: ...al Connection Give copy of these 2 pages to electrician PART 1 Planning the Installation La Cornue Insert Series for Wood Hoods are designed for installation inside custom hood canopies Proper installation of the Insert is directly related to the material from which the custom canopy is constructed A qualified person must complete the installation of this unit Because of the large size and weight ...

Страница 6: ...CI18 165LCI18 180LCI18 8 5 3 Speed Two Internal Motors D 1200 120LCI22 135LCI22 150LCI22 165LCI22 180LCI22 8 5 3 Speed Two Internal Motors Notes 1 Center of electrical access is 7 from front 2 1 2 from side of liner Connection access is behind filters 2 Damper not included 3 Length width cutouts should be 1 8 larger than above dimensions 1 Center of electrical access is 7 from front 2 1 2 from sid...

Страница 7: ... Damper not included 3 Length width cutouts should be 1 8 larger than above dimensions 1 Center of electrical access is 7 from front 2 1 2 from side of liner Connection access is behind filters 2 Damper not included No Vent Transition Needed 3 Length width cutouts should be 1 8 larger than above dimensions Notes C Front View D Front View d Side View c Side View ...

Страница 8: ...y setting the Insert on its face on cardboard and drilling from the back side Secure the Insert by driving screws by others tightly into the wood frame Use washers where necessary When removing the filters be careful not to scratch the Insert by placing the filters screws drill bits or drill on the Insert s face CONNECTING TO THE VENT PIPE The La Cornue Insert Series for Wood Hoods comes with a me...

Страница 9: ...ne is a corrosive substance DO NOT USE Follow polish manufacturer s instructions LED LIGHT BULBS La Cornue Insert Series for Wood Hoods are designed for MR16 GU10 LED flood light bulbs They can be purchased at most home or grocery stores The bulbs provided with the unit are 3 5 watt 350 lumens and 3000K warm white color temperature Explaining the Remote The diagram to the left shows all functions ...

Страница 10: ... It is the owner s responsibility to ensure that a qualified person performs the electrical connection of this appliance The electrical installation including minimum supply wire size must comply with the National Electric Code ANSI NFPA 70 1990 or latest revision and local codes and ordinances A copy of this standard may be obtained from National Fire Protection Association 1 Batterymarch Park Qu...

Страница 11: ...control to the blower motor Wiring Diagrams IMPORTANT Copy this page and previous page to your electrical installer All Models IMPORTANT La Cornue does not pay warranty claims for damage to Inserts or components connected to other brand blowers inconsistent with these Installation Instructions Always consult the switch manufacturer s installation instructions when substituting control switches The...

Страница 12: ...r use and care of the product change fuses or to reset the circuit breakers Service calls to correct faulty installation such as performance issues relating to improperly sized ducting or restrictive roof caps is not covered and will by default be charged back to the Homeowner Light bulbs are not covered under warranty La Cornue disclaims and excludes any liability for implied warranties or for in...

Страница 13: ...be directly connected to one another Where possible always include at least 15 inches of straight pipe between fittings 3 Duct Pipe and Fitting Sizes See Duct Sizing Chart and Area Calculations Section for more detail IMPORTANT DO NOT use either of the following duct pipe sizes or fitting sizes for any kitchen hood ventilator installations 6 round duct pipe 3 25 x 10 rectangular x 6 round transiti...

Страница 14: ... damper blade before attaching the duct to the damper frame 600 1200 CFM Ventilator Models 600 1200 CFM models have either an 8 or 10 round start collar that requires use of a damper with the corresponding dimension Damper in Roof Cap or Wall Cap In ventilation systems utilizing a roof cap or wall cap with a built in damper do not install an additional in line damper Two dampers are unnecessary an...

Страница 15: ... rattling vibration and air buffeting noises as well as inadequate ventilation Roof caps and wall caps must have an integral bird screen 6 Attaching Duct to House Framework The ventilation system should be attached to the framework in such a manner that the weight of the duct and fittings is supported with no stress on the duct joints fittings or on the ventilator All ducting should be attached so...

Отзывы: