Digital Integrated Protection Relay
K-PAM 5500 Series
21
③ LOG Check
- Event Record Check
- Fault Record & Waveform Record
LCD Display
Display Description
- Save up to 1024 EVENT occurrence information
- Displays power ON/OFF, protection element operation status,
digital input/output status, CB control, set value change,
event / fault /waveform record delete, MIN&MAX CLEAR,
CB counter, etc.
LCD Display
Display Description
- Save up to 300 FAULT occurrence information
- Displays the PICK-UP, OPERATE, RELEASE, operation time,
fundamental wave (voltage, current, sequence voltage, current etc.) value,
phase, frequency, etc.
- Save up to 16 Fault Waveform
- 32Sample, 2Sec (120Cycle, 60Hz)
- Check it by uploading it on-site or from a remote location through
KBIED_MNE.
- Displays voltage/current value, phase, waveform, digital input/output
status, protection relay element status, harmonic (fundamental and
2nd to 15th harmonics), THD, etc.