■ UVR Setting Method
① After selecting ‘UVR (27)’ in Protection Relay Element Setting Method ④, press the RIGHT (
) Key.
② Select ‘UVR1’ or ‘UVR2’ by using UP (
) and DOWN (
) keys and press the RIGHT (
) key to enter the
setting screen.
③ Use the UP (
), DOWN (
) KEY to move the category you want to set, and then enter the ENTER ( )
KEY to pop up the password input screen. (initial password 0000)
④ Use the UP (
), DOWN (
) KEY to change the setting value and then press the ENTER ( ) KEY.
⑤ After completing the setting, press the LEFT (
) KEY to check whether the setting has been changed.
After selecting ‘Yes’ or ‘No’, the setting is completed when the ENTER key is pressed.
ENTER
ENTER
LCD Display
Category
Description
FUNCTION
Whether to use the function
- Setting Range : ENABLED, DISABLED
OP MODE
Operation Mode Setting
- Setting Range : EACH PHASE, 3PHASE
PICK-UP
Voltage Pick-up Setting
- Setting Range : 5 ~ 170V (1V STEP)
CURVE
DT/INVERSE Setting
- Setting Range : DT, INV
TIME DELAY
Operation Delay Time Setting
- Setting Range : 0.04 ~ 60.00s (0.01s STEP)
LEVER
Inverse Time Lever Setting
- Setting Range : 0.01 ~ 10.00 (0.01 STEP)
DEAD BLOCK
Set whether or not to use the minimum operating voltage
- Setting Range : ENABLED, DISABLED
DEAD VOLT
Minimum Operating Voltage Setting
- Setting Range : 5 ~ 170V (1V STEP)
BLOCK
Protection Blocking Condition Setting
- Setting Range : EASYLOGIC OPERAND
WAVEFORM
Whether to Record Waveforms
- Setting Range : ENABLED, DISABLED