System trips breaker on 
start up

Incoming power is incorrect, 
breaker is undersized or 
faulty, and/or  extension 
power cable is too long and 
or undersized.

Verify the circuit and power 
cable is within the systems 
specifications, consult with 
your electrician or call 
1-800-KwiKool for 
guidance.

System starts up and 
operates in the chosen 
mode but the condenser 
discharge air exhaust fan 
stops and starts in cool 
mode or in heat mode the 
supply air fan starts and 
stops.

Normal operating condition 
especially in low tempera-
tures.

No action required, see 
sections IV C. 2 & 3

Note:

 To avoid excessive 

fan cycling, return air must 
not be below the specifica-
tions of your KwiKool 
system.

Supply air flow is limited, and 
or water is dripping from the 
front of the system

Supply or return air is 
blocked or restricted, and or 
the evaporator coil is 
freezing. 

Verify that supply and 
return air are not blocked 
and duct work is installed 
to specification, remove or 
add duct as needed, check 
air filter for blockage.

Fault

Possible Cause

Possible Solution

Display shows 

32

 and unit 

will not turn on cooling.

No connection of tempera-
ture sensor to Micropro-
cessor. Temperature 
Sensor malfunction.

Call 1-800-KwiKool for 
instructions.

Condensate is not pumping.

Water is below pumping  
level, external line 
restricted, line installed with 
too high of lift.

Reservoir fills, and then 
pumps. Check for line 
crimping or restrictions and 
proper line run height. Refer 
to the user guide Section 5: 
Built in Safeguards.

Evaporator coil is freezing

Low or restricted air flow. 
Undersized capacity, unit 
constantly on, unable to 
achieve set point. Low 
return air temperature out 
of factory specifications. 
Evaporator door open, 
mechanical system 
malfunction.

Direct supply return air to 
area of highest heat load, 
check for blocked air flow 
from the supply air, replace 
air filters, adjust set point to 
allow the unit to cycle, add 
another KwiKool system or 
larger capacity model, close 
evaporator compartment 
door. Install service gauges 
to view pressures.
Call 1-800-KwiKool

Содержание KPHP Series

Страница 1: ...Portable Heat Pumps Operation Manual P P H P P H PORTABLE HEAT PUMPS...

Страница 2: ......

Страница 3: ...ained for future reference Section I Unit Components Page 3 Section II Assembly and Installation Page 4 6 Section III Operational Safeguards Page 6 Section IV System Operation Page 6 9 Section V Built...

Страница 4: ......

Страница 5: ...Unit Components Legend 1 Cold Air Return 2 Control Pad 3 Cold Air Supply 4 Condenser Air Inlet 5 Condenser Air Outlet 6 Cord Storage 7 Condensate Nipple 8 Condensate Alarm Jack 9 Access Door 10 Vent...

Страница 6: ...h a float switch that shuts your KwiKool down and alerts operators with an alarm and display CF Condensate Full when the condensate tank is full This prevents accidental water overflow on the floor Th...

Страница 7: ...rected normally above a drop ceiling must be well ventilated and large enough for the discharge air to be absorbed Discharge air is prevented from entering the make up air inlet by way of a factory in...

Страница 8: ...C D F E G H I J Power Connection Verify that the source power phase and breaker size is compatible with your KwiKool serial plate information and that the electrical circuit is dedicated only for the...

Страница 9: ...is timing out Heat Cool mode when conditioning is required in applications with changing load requirements The system automatically selects the mode based on the set point and flashes the current ope...

Страница 10: ...op flashing when the ambient temperature falls below 99 degrees F HEAT If the unit was previously set to the Heat Mode then Heat will be displayed If the compressor is running Heat on the display will...

Страница 11: ...by mode stays solid FAN If the unit was previously set to the fan mode then FAN will be displayed and the supply air fan will start to run Time Delay Protects your KwiKool from potential damage by del...

Страница 12: ...of the unit If the unit is operated in an environment above 110 F the high pressure switch may trip stopping the unit s compressor You also may notice diminished performance The High Pressure Switch...

Страница 13: ...enance Your KwiKool unit comes from the factory with air filters installed on the evaporator inlet to prevent dust and debris from entering the system and circulating in the conditioned space factory...

Страница 14: ...ondensate pump Inspect condensate pump for over flow and proper operation check condensate line for a clog or crimping Resets automatically upon fault correction or call 1 800 KwiKool if the problem p...

Страница 15: ...d has detected low pressure This alarm might cycle on and off Check air filter and replace if dirty Make sure nothing is blocking the filter inlet Check for icing on coil Resets automatically when fau...

Страница 16: ...s installed to specification remove or add duct as needed check air filter for blockage Fault Possible Cause Possible Solution Display shows 32 and unit will not turn on cooling No connection of tempe...

Страница 17: ...ed power cable and check incoming power Call 1 800 KwiKool Fault Possible Cause Possible Solution 99 Flashes on display Ambient room temperature over 99 degrees F Unit is working properly Lowering of...