C.

Turn On Your KwiKool System - 

Pressing the ON/OFF button once on your control 

panel will put your unit in the ON position and “ON” will be displayed on the right 
side of your display as well as the previously chosen mode.

COOL - 

If the unit was previously set to the cooling mode (cool) then “cool” will be 

displayed. If the compressor is running, the ”cool” on the display will be flashing.  If 
your unit has been sitting for over 2 minutes, this should happen immediately upon 
turning the unit on, unless your set point is lower than the current room tempera-
ture. In this case your unit is ready to automatically turn on once the temperature 
rises above the set point. If the unit was recently turned off or the unit turned itself 
off because it reached the set point, the compressor will not turn on until the 
system waits for approximately 2 minutes. This prevents the compressor from 
being damaged do to a condition called short cycling. The indicator that the unit is in 
the “time out” condition is that the F (or C) in the display will be flashing. When the 
compressor starts, the F will stop flashing and the “COOL” will begin flashing. 
Note that the condenser fan will not start immediately with the compressor. And 
once the condenser fan kicks in and if the ambient temperature entering the make 
up air for the condenser return is below 75 degrees F you may notice the fan 
cycling on and off, this is normal. If the display flashes 99, this indicates ambient 
temperature of 99 degrees F or more. This is normal and will stop flashing when the 
ambient temperature falls below 99 degrees F.

HEAT - 

If the unit was previously set to the Heat Mode then “Heat” will be 

displayed. If the compressor is running, “Heat” on the display will be flashing. If 
your unit has been sitting for over 2 minutes, this should happen immediately upon 

System Operation - 

1.

Page 8

a.

b.

Lowering or raising the set point will not change the temperature of the supply 
air. For best results always adjust the set point to a temperature your KwiKool 
can cycle on and off at to avoid operational issues such as freezing or rapid fan 
cycling, KwiKool systems are designed to maintain the set point when sized 
properly and constant operation without achieving the set point may shorten 
the expected operational life of your system.

In Cool Mode the lowest set point temperature available for your KwiKool is 
60 degrees F, and the highest setting is 95 degrees F. The control will not 
allow adjustments beyond these ranges.

NOTES:

5.

NOTE:

 Operations of KPHP systems will not have control of the supply air fan 

when in Heat Mode, the supply air is controlled by a pressure switch to optimize 
the systems operation and this switch overrides the microprocessor selection. It is 
normal for the supply air fan to delay in starting and to cycle on and off in the Heat 
Mode.

Up (+) and Down (-) Arrow Buttons -

 

Raises or lowers the desired set tempera-

ture. When changing the set point, pressing the + or – key, the word SET will 
appear on the display and the current set point flashes ON and OFF. The value of 
the set point is changed 1 degree each time the + or – is pressed. The adjusted set 
point flashes on and off 12 times after the last change and then returns to display 
the room temperature.

2.

3.

Содержание KPHP Series

Страница 1: ...Portable Heat Pumps Operation Manual P P H P P H PORTABLE HEAT PUMPS...

Страница 2: ......

Страница 3: ...ained for future reference Section I Unit Components Page 3 Section II Assembly and Installation Page 4 6 Section III Operational Safeguards Page 6 Section IV System Operation Page 6 9 Section V Built...

Страница 4: ......

Страница 5: ...Unit Components Legend 1 Cold Air Return 2 Control Pad 3 Cold Air Supply 4 Condenser Air Inlet 5 Condenser Air Outlet 6 Cord Storage 7 Condensate Nipple 8 Condensate Alarm Jack 9 Access Door 10 Vent...

Страница 6: ...h a float switch that shuts your KwiKool down and alerts operators with an alarm and display CF Condensate Full when the condensate tank is full This prevents accidental water overflow on the floor Th...

Страница 7: ...rected normally above a drop ceiling must be well ventilated and large enough for the discharge air to be absorbed Discharge air is prevented from entering the make up air inlet by way of a factory in...

Страница 8: ...C D F E G H I J Power Connection Verify that the source power phase and breaker size is compatible with your KwiKool serial plate information and that the electrical circuit is dedicated only for the...

Страница 9: ...is timing out Heat Cool mode when conditioning is required in applications with changing load requirements The system automatically selects the mode based on the set point and flashes the current ope...

Страница 10: ...op flashing when the ambient temperature falls below 99 degrees F HEAT If the unit was previously set to the Heat Mode then Heat will be displayed If the compressor is running Heat on the display will...

Страница 11: ...by mode stays solid FAN If the unit was previously set to the fan mode then FAN will be displayed and the supply air fan will start to run Time Delay Protects your KwiKool from potential damage by del...

Страница 12: ...of the unit If the unit is operated in an environment above 110 F the high pressure switch may trip stopping the unit s compressor You also may notice diminished performance The High Pressure Switch...

Страница 13: ...enance Your KwiKool unit comes from the factory with air filters installed on the evaporator inlet to prevent dust and debris from entering the system and circulating in the conditioned space factory...

Страница 14: ...ondensate pump Inspect condensate pump for over flow and proper operation check condensate line for a clog or crimping Resets automatically upon fault correction or call 1 800 KwiKool if the problem p...

Страница 15: ...d has detected low pressure This alarm might cycle on and off Check air filter and replace if dirty Make sure nothing is blocking the filter inlet Check for icing on coil Resets automatically when fau...

Страница 16: ...s installed to specification remove or add duct as needed check air filter for blockage Fault Possible Cause Possible Solution Display shows 32 and unit will not turn on cooling No connection of tempe...

Страница 17: ...ed power cable and check incoming power Call 1 800 KwiKool Fault Possible Cause Possible Solution 99 Flashes on display Ambient room temperature over 99 degrees F Unit is working properly Lowering of...