X / KPHP Troubleshooting Guide

Fault

Possible Cause

Possible Solution

Unit displays 

CF

, Audio 

alarm fails to clear on start 
up or while operating

External Condensate Tank is 
full. Condensate bypass jack 
or condensate float switch 
jack is not installed or not 
positioned correctly. Water 
level switch is engaged

Empty External Tank (if 
using). Make sure thank is 
upright and level. Unplug 
bypass plug or tank plug and 
reinstall to assure good 
connections. System 
automatically resets when 
fault condition is corrected.

Unit Displays 

CP

 and Audio 

alarm is sounding during 
start up or while operating. 

Microprocessor board has 
detected high water level in 
the condensate pump. 

Inspect condensate pump for 
over flow and proper 
operation, check condensate 
line for a clog or crimping. 
Resets automatically upon 
fault correction, or call 
1-800-KwiKool if the problem 
persist.

Unit Displays 

HP

, Audio 

alarm is sounding during 
start up or while operating.

Microprocessor board has 
detected high pressure. The 
High Pressure switch is 
tripped.

High pressure is normally 
caused by reduced 
condenser air flow. In Cool 
Mode check for restriction in 
ducting. Check condenser 
motors and/or blowers for 
proper operation. In Heat 
Mode be sure the service 
door is closed, check the air 
filter for blockage and be 
sure that the return air flow 
is unrestricted and the 
supply air fan is operating. 
High pressure is a manual 
reset type. To reset, open 
filter door. The button is 
located above the filter. 
Press button to reset (you 
should feel a click).

Содержание KPHP Series

Страница 1: ...Portable Heat Pumps Operation Manual P P H P P H PORTABLE HEAT PUMPS...

Страница 2: ......

Страница 3: ...ained for future reference Section I Unit Components Page 3 Section II Assembly and Installation Page 4 6 Section III Operational Safeguards Page 6 Section IV System Operation Page 6 9 Section V Built...

Страница 4: ......

Страница 5: ...Unit Components Legend 1 Cold Air Return 2 Control Pad 3 Cold Air Supply 4 Condenser Air Inlet 5 Condenser Air Outlet 6 Cord Storage 7 Condensate Nipple 8 Condensate Alarm Jack 9 Access Door 10 Vent...

Страница 6: ...h a float switch that shuts your KwiKool down and alerts operators with an alarm and display CF Condensate Full when the condensate tank is full This prevents accidental water overflow on the floor Th...

Страница 7: ...rected normally above a drop ceiling must be well ventilated and large enough for the discharge air to be absorbed Discharge air is prevented from entering the make up air inlet by way of a factory in...

Страница 8: ...C D F E G H I J Power Connection Verify that the source power phase and breaker size is compatible with your KwiKool serial plate information and that the electrical circuit is dedicated only for the...

Страница 9: ...is timing out Heat Cool mode when conditioning is required in applications with changing load requirements The system automatically selects the mode based on the set point and flashes the current ope...

Страница 10: ...op flashing when the ambient temperature falls below 99 degrees F HEAT If the unit was previously set to the Heat Mode then Heat will be displayed If the compressor is running Heat on the display will...

Страница 11: ...by mode stays solid FAN If the unit was previously set to the fan mode then FAN will be displayed and the supply air fan will start to run Time Delay Protects your KwiKool from potential damage by del...

Страница 12: ...of the unit If the unit is operated in an environment above 110 F the high pressure switch may trip stopping the unit s compressor You also may notice diminished performance The High Pressure Switch...

Страница 13: ...enance Your KwiKool unit comes from the factory with air filters installed on the evaporator inlet to prevent dust and debris from entering the system and circulating in the conditioned space factory...

Страница 14: ...ondensate pump Inspect condensate pump for over flow and proper operation check condensate line for a clog or crimping Resets automatically upon fault correction or call 1 800 KwiKool if the problem p...

Страница 15: ...d has detected low pressure This alarm might cycle on and off Check air filter and replace if dirty Make sure nothing is blocking the filter inlet Check for icing on coil Resets automatically when fau...

Страница 16: ...s installed to specification remove or add duct as needed check air filter for blockage Fault Possible Cause Possible Solution Display shows 32 and unit will not turn on cooling No connection of tempe...

Страница 17: ...ed power cable and check incoming power Call 1 800 KwiKool Fault Possible Cause Possible Solution 99 Flashes on display Ambient room temperature over 99 degrees F Unit is working properly Lowering of...

Страница 18: ...Revision 1017016...

Отзывы: