Page 7

Drain Hose Connection 

- The KCA/KCW is equipped with a high lift internal conden-

sate pump. Maximum lift is 20’. Use the provided 3/8” flexible hose and connect it to 
the 3/8” male connection on the unit for the evaporator coil condensate drain. The 
drain line must be located so it will not be exposed to freezing temperatures. The 
drain should be the full size of the drain connection. (Connect the drain hose to the 
condensate drain or the janitor closet.) A 1/2” ID (5/8” OD), PVC tubing or 3/8” 
copper tubing is required for the drain. Insulate the drain hose; condensation may 
occur during humid conditions. (Field supplied material). Plug in the 3/8” drain hose 
onto the unit and install the hose clamp. Then connect the 3/8”flexible line to the field 
supplied condensate line. Make sure the hose does not leak.

NOTE: do not use more than 15’ of drain hose vertically. This is maximum head 

(lift) of the condensate pump.

When securing the drain hose to the highest vertical position (no more than 15’ high) 
and running the hose to the drain, run the drain hose on a downward slope at a 
minimum rate of 1/4” per foot for proper drainage.
Check the following items: No kinks or bends in the drain hose; No traps in the drain 
hose; The end of the drain hose should be higher than the water level at the drain;
No dripping from the drain hose at the clamping area

G.

Wall Thermostat Connection

 - Preparation for thermostat connection:

H.

Use with a single stage wall thermostat. (Type: standard 24 volt input system)

Set the wall thermostat to cooling system mode, since most wall thermostats are 
designed for both heating and cooling.

Prepare the wire harness for connection from the unit to the thermostat. The 
recommended wire size is: Wire Type: Thermostat cable / Solid Wire 16-26 AWG.

Identify the thermostat connectors labeled G, C, Y or Y1, and R

1.

2.

3.

4.

Connecting a Thermostat to Your KCA/KCW Unit

Wall Thermostat

Connector Name

R
C
Y or Y1
W
G

KCA/KCW Wiring

Label Name

R - 24V
C - Common
Y1
Not Used
G

Color

Red
White
Yellow
Not Used
Green

Function

24 VAC Power
Common
Cool ON / OFF
Heat
Fan ON / OFF

Install the wall thermostat to the proper location inside the room where it can be 
conveniently accessed. Do no install the wall thermostat where unusual heating 
conditions might be present ( i.e. hot pipes, direct sunlight, etc.). Install the 
thermostat somewhere close to the area of the return filter grill.
Most standard thermostat devices will provide these basic functions: 
Fan mode: ON / AUTO (Select the desired fan mode)
System mode: Cool / Heat

5.

WARNING: All electrical work should only be performed by qualified personnel. Installa-

tion or repair to any electrical components by non-certified personnel may result in 

personal injury and/or damage to the unit.

Содержание CeilingMaster KCA Series

Страница 1: ...KCA KCW Operation Manual CEILING MASTER...

Страница 2: ......

Страница 3: ...roper usage and all safeguards This manual should be retained for future reference Section I Unit Components Page 3 Section II KCA KCW Standard Features Page 3 Section III Introduction Page 4 Section...

Страница 4: ......

Страница 5: ...PO emergency power off N O connection Automatic shut off with alarm signal output and audible alarm for C D E Condensate Pump High Pressure Switch Activation Low Pressure Switch Activation 1 2 3 Legen...

Страница 6: ...for use or misuse of unit improper installation or failure to follow local building codes V Installation Things you will need for installation B Before you begin installation it is important to verify...

Страница 7: ...maximum flexibility is installation methods Vibration isolation is required but can be installed on the unit or on the attachment to the building structure One common installation method and one that...

Страница 8: ...ctor and run the wire into the electri cal box Strip the ends of the wires and install the appropriate connectors to the 3 wires for single phase units and 4 wires on the 3 phase models Attach to the...

Страница 9: ...water level at the drain No dripping from the drain hose at the clamping area G Wall Thermostat Connection Preparation for thermostat connection H Use with a single stage wall thermostat Type standar...

Страница 10: ...re Alarm Control Panel or EPO Emergency Power Off to KCA KCW First remove the jumper from the S1 and S2 terminals of the external terminal block Connect the fire alarm signal wires or EPO wires to you...

Страница 11: ...he 3rd party thermostat is connected properly to unit and secured to the wall D Test Operation E Check operation with wall thermostat Set wall thermostat to FAN ON or FAN ONLY mode Fan should engage w...

Страница 12: ...al factory jumper and retest Condenser Blocked Make sure that the condenser inlets and outlets are not blocked Verify that the condenser intake air is not overheated due to lack of ventilation or cond...

Страница 13: ...Switch Actuated Potentially low on refrigerant Call a qualified technician since this is not user serviceable Condensate Pump Overflow Check to make sure condensate line is not kinked or obstructed I...

Страница 14: ...Revision 071916...

Отзывы: