background image

 

___________________________________________________________________________________________ 

4

 

EA440

 

Figure 4

 

Manual Field Flash 

 

3.4 

Trim Adjustment 

 
An auxiliary input is provided to connect to A1, A2. It is 
designed  to  accept  DC  +/-  5V.Turn  the  TRIM  trimmer 
fully  anticlockwise  has  no  effect,  Clockwise  it  has 
maximum effect. 

 

SECTION 4 : FIELD FLASHING 

When  the  regulator  is  installed  correctly  but  the 
generator is failed to generate power.  Besides carbon 
brushes  were  worn out, here are two  possible causes 
below. 
 

4.1 

The polarity of field is inverse 

 

Solution

Exchange the connection of F+ and F-. 

 

4.2 

The  residual  voltage  is  less  than  5  Vac, 

Solution 1

 

 

4.2.1  Shut  down  generator,  disconnect  the  wiring 

between AVR and generator then flash the field. 
Flashing  duration  =  3  seconds.  (See  wiring  in 
Figure 4) 

 

Resistor 3 

– 5 ohms for full wave AVR 

 

Resistor 5 

– 10 ohms for half wave AVR 

 

 

Warning

!!

    Over  field  flashing  may  damage 

the field winding of generator. 

 

4.2.2  Restart  generator  and  measure  the  residual 

voltage  by  AC  Voltmeter,  if  it  is  still  less  than  5 
Vac,  repeat  the  previous  process,  after  several 
times,  the  residual  voltage  still  cannot  be  built, 
Kutai  EB500  is  strongly  recommended,  see 
Figure 4. 

 

Field

SW

R

-

+

V

F+

F-

BATT.

~

G

~

T

S

R

 

 
 

 
 
 
 
 
 

WARNING 

Overly  field  flashing  may  damage  the  AVR  or 
generator excitation winding. 

Please  make  sure  you  have  read  and  understand 
the  contents  of  the  instruction  manual  prior  to 
installation.  Incorrect  wiring  connection  may 
result  in  irreversible  damage  to  the  product  and 
other equipments.

 

 

SECTION 5 : PARALLEL FUNCTION 

5.1 

Parallel Compensation 

 
5.1.1  When  it  is  required  to  operate  the  regulator  in 

parallel with an isolated or utility bus, in addition 
to  the  regulator  provisions,  a  10VA  current 
transformer (CT) is required ( See Figure 3 ). The 
CT  is  connected  in  a  generator  line  and  should 
deliver  from  1  amperes  secondary  current  at 
rated load. 

 

5.1.2  The  phase  relationship  of  CT  signal  to  the 

regulator sensing voltage  must be correct or the 
system will not parallel properly. The CT must be 
installed in the line of the three phase generator 
that does not supply sensing to the regulator. 

 
5.2 

Reactive Droop Compensation 

 

5.2.1  For  reactive  droop  compensation,  connect  the 

CT  to  it’s  respective  regulator  as  shown  on 
Figures 3. 

 

5.2.2  A  unit-parallel  switch  shorts  the  parallel  CT 

secondary  to  prevent  any  droop  signal  from 
being  injected  into  the  regulating  system  during 
single  unit  operation.  The  switch  may  not  be 
required 

on 

parallel 

droop 

compensation 

applications  where  a  voltage  drop  is  not 
objectionable. 

Содержание EA440

Страница 1: ...Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA440 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX440 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ...c residual volts at power input terminal Environment Operating Temperature 40 to 70 C Soft Start Ramp Time Storage Temperature 40 to 85 C 2 seconds 10 Relative Humidity Max 95 Vibration 3 3 Gs 100 2K Hz Static Power Dissipation Max 12 watts Dimensions 150 0 L x 135 0 W x 48 0 H mm Weight 418 g 2 115 0 135 0 130 0 150 0 21 5 48 0 5 5 STABILITY DROOP TRIM VOLT UFRO LED C B A C A 90KW C B 90 550KW B ...

Страница 3: ...rn the external trimmer to midway position 3 Turn the stability trimmer on the AVR board to midway position 4 Connect a voltmeter to generator output voltage terminals 5 Start generator set and run on no load at nominal frequency 50 53 Hz or 60 63 Hz 6 If the red Led is illuminated refer to the under frequency roll off adjustment 7 Carefully turn volt trimmer clockwise until rated voltage is reach...

Страница 4: ...commended see Figure 4 Field SW R V F F BATT G T S R WARNING Overly field flashing may damage the AVR or generator excitation winding Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments SECTION 5 PARALLEL FUNCTION 5 1 Parallel Compensation 5 1 1 W...

Страница 5: ...e Generator Manual Low output voltage External VR broken Check wiring and testing VR Terminal 1 2 not linked Please linked terminal 1 2 Terminal 3 2 no sensing input Please refer to Figure 2 Under frequency Please refer to the Generator Manual Defective Generator Please refer to the Generator Manual Over output voltage AVR adjustment not well Please refer to voltage adjustment page Defective Gener...

Отзывы: