___________________________________________________________________________________________ 

2

 

EA440

 

SECTION 1 : SPECIFICATION 

Sensing Input 

Quadrature Droop Input

 

  Voltage 

190 

– 264 Vac, 1 phase 2 wire 

  Burden 

10 ohms 

  Frequency 

50 / 60 Hz, selectable 

  Max. input 

0.33 A 

 

  Max. sensitivity 

0.07 A for 5% droop (PF=0) 

Excitation Output

 

 

  Voltage 

Max. 90 Vdc @ power input 207 Vac 

Analogue Voltage Input 

  Current 

Continuous 4A 

  Input Resistance  1K ohm 

   

Intermittent 10A for 10 secs. 

  Max. Input 

+/- 5 Vdc 

  Resistance 

Min. 15 ohm 

  Sensitivity 

1V for 5% generator volts 

 

 

External Voltage Adjustment

 

Under Frequency Protection 

  Max. +/- 8%  @ 1K ohm 1 watt potentiometer 

  Set 

point 95% Hz 

 

  Slope 

170% down to 30 Hz 

Voltage Regulation

 

 

  Less than +/- 1% ( with 4% engine governing ) 

Voltage Thermal Drift 

 

  Less than 3% at temperature range -40 to +70 

˚C 

Build Up Voltage

 

 

  5 Vac residual volts at power input terminal 

Environment 

 

  Operating Temperature 

-40 to +70 

˚C 

Soft Start Ramp Time 

  Storage Temperature 

-40 to +85 

˚C 

  2 s/- 10% 

  Relative Humidity 

Max. 95% 

 

  Vibration 

3.3 Gs @ 100 

 2K Hz 

Static Power Dissipation

 

 

  Max.12 watts 

Dimensions 

 

  150.0 (L) x 135.0 (W) x 48.0 (H) mm

 

 

 

 

Weight 

 

  418 g +/- 2%

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

115.0

135.0

130.0

150.0

21.5

48.0

   5.5

STABILITY

DROOP

TRIM

VOLT

UFRO

LED

C B A

C-A < 90KW
C-B < 90-550KW
B-A < 550KW

Resistor

 

ATTENTION 

1. AVR  can  be  mounted  directly  on  the 

engine,  genset,  switchgear,  control 
panel, or any position that will not affect 
operation.  For  dimension  reference, 
please see Figure 1. 

2. All voltage readings are to be taken with 

an  average-reading  voltmeter  Meggers 
and high-potential test equipment must 
not  be  used.  Use  of  such  equipment 
could damage the AVR. 

3. Improper  setting  of  under-frequency 

protection  could  cause  the  output 
voltage  of  the  unit  to  drop  or  become 
unstable  under  with  changes  in  load. 
Avoid  making  any  changes  to  the  U/F 
setting unless necessary. 

 

Figure 1

 

Outline Drawing 

Содержание EA440

Страница 1: ...Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA440 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX440 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ...c residual volts at power input terminal Environment Operating Temperature 40 to 70 C Soft Start Ramp Time Storage Temperature 40 to 85 C 2 seconds 10 Relative Humidity Max 95 Vibration 3 3 Gs 100 2K Hz Static Power Dissipation Max 12 watts Dimensions 150 0 L x 135 0 W x 48 0 H mm Weight 418 g 2 115 0 135 0 130 0 150 0 21 5 48 0 5 5 STABILITY DROOP TRIM VOLT UFRO LED C B A C A 90KW C B 90 550KW B ...

Страница 3: ...rn the external trimmer to midway position 3 Turn the stability trimmer on the AVR board to midway position 4 Connect a voltmeter to generator output voltage terminals 5 Start generator set and run on no load at nominal frequency 50 53 Hz or 60 63 Hz 6 If the red Led is illuminated refer to the under frequency roll off adjustment 7 Carefully turn volt trimmer clockwise until rated voltage is reach...

Страница 4: ...commended see Figure 4 Field SW R V F F BATT G T S R WARNING Overly field flashing may damage the AVR or generator excitation winding Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments SECTION 5 PARALLEL FUNCTION 5 1 Parallel Compensation 5 1 1 W...

Страница 5: ...e Generator Manual Low output voltage External VR broken Check wiring and testing VR Terminal 1 2 not linked Please linked terminal 1 2 Terminal 3 2 no sensing input Please refer to Figure 2 Under frequency Please refer to the Generator Manual Defective Generator Please refer to the Generator Manual Over output voltage AVR adjustment not well Please refer to voltage adjustment page Defective Gener...

Отзывы: