background image

16

17

KDH4756

dehumidifier

EN

4. Storage of equipment / appliances

The storage of equipment should be done in accordance with the 

manufacturer’s instructions.

5. Storage of packed (unsold) equipment

Storage package protection should be constructed in such a way that 

mechanical damage to the equipment inside the package will not 

cause it to leak refrigerant.
The maximum number of pieces of equipment permitted to be stored 

together will be determined by local regulations.

6. Information Servicing
1) Area checks

Prior to beginning work on systems containing flammable refrigerants, 

safety checks are necessary to ensure that the risk of ignition is minimised. 

For repair to the refrigerating system, the following precautions shall be 

complied with prior to conducting work on the system.

2) Work procedure

Works shall be undertaken under a controlled procedure so as to 

minimise the risk of a flammable gas or vapour being present while 

the work is being performed.

3) General work area

All maintenance staff and others working in the local area shall be 

instructed on the nature of work being carried out. Work in confined 

spaces shall be avoided. The area around the work space shall be 

sectioned off. Ensure that the conditions within the area have been 

made safe by control of flammable material.

4) Checking for presence of refrigerant

The area shall be checked with an appropriate refrigerant detector 

prior to and during work, to ensure the technician is aware of 

potentially flammable atmospheres. Ensure that the leak detection 

equipment being used is suitable for use with flammable refrigerants, 

i.e. no sparking, adequately sealed or intrinsically safe.

5) Presence of fire extinguisher

If any hot work is to be conducted on the refrigeration equipment or 

any associated parts, appropriate fire extinguishing equipment shall 

be available on hand. Have a dry power or CO2 fire extinguisher next 

to the charging area.

6) No ignition sources

No person carrying out work with a refrigeration system which involves 

exposing any pipe work that contains or has contained flammable 

refrigerant shall use any sources of ignition in such a manner that 

it may lead to risk of fire or explosion. All possible ignition sources, 

including cigarette smoking, should be kept sufficiently far away from 

the site of installation, repairing, removing and disposal, during which 

flammable refrigerant can possibly be released to the surrounding 

space. Prior to work taking place, the area around the equipment is 

to be surveyed to make sure that there are no flammable hazards or 

ignition risks. “NO SMOKING” signs shall be displayed.

7) Ventilated area

Ensure the work area is in the open or that it is adequately ventilated 

before breaking into the system or conducting any hot work. A degree 

of ventilation shall continue during the period that the work is carried 

out. The ventilation should safely disperse any released refrigerant 

and preferably expel it externally into the atmosphere.

8) Checks to the refrigeration equipment

Where electrical components are being changed, they shall be 

fit for the purpose and to the correct specification. At all times the 

manufacturer’s maintenance and service guidelines shall be followed.
If in doubt, consult the manufacturer’s technical department for 

assistance. The following checks shall be applied to installations using 

flammable refrigerants:
•  the charge size is in accordance with the room size within which the 

refrigerant containing parts are installed;

•  the ventilation machinery and outlets are operating adequately and 

are not obstructed;

•  if  an  indirect  refrigerating  circuit  is  being  used,  the  secondary 

circuits shall be checked for the presence of refrigerant; marking to 

the equipment continues to be visible and legible.

• marking and signs that are illegible shall be corrected;
•  refrigeration pipe or components are installed in a position where 

they are unlikely to be exposed to any substance which may 

corrode refrigerant containing components, unless the components 

are constructed of materials which are inherently resistant to being 

corroded or are suitably protected against being so corroded.

9) Checks to electrical devices

Repair and maintenance to electrical components shall include 

initial safety checks and component inspection procedures. If a fault 

exists that could compromise safety, then no electrical supply shall 

be connected to the circuit until it is satisfactorily dealt with. If the 

fault cannot be corrected immediately but it is necessary to continue 

operation, and adequate temporary solution shall be used. This shall 

be reported to the owner of the equipment, so all parties are advised.
Initial safety checks shall include:
•  that capacitors are discharged: this shall be done in a safe manner 

to avoid possibility of sparking

•  that  there  no  live  electrical  components  and  wiring  are  exposed 

while charging, recovering or purging the system;

• that there is continuity of earth bonding.

Содержание KDH4756

Страница 1: ...instructions manual manual de instrucciones manual de instru es dehumidifier KDH4756...

Страница 2: ...ntee a safe use Please read carefully the instructions and safety measures described in this manual We sincerely hope you will be satisfied when using your new appliance INDEX 1 SAFETY INSTRUCTIONS 4...

Страница 3: ...d not be used for other purposes than the ones intended and sole ly for household use Any damage resulting from using the appliance outside this scope any incorrect use as well as any manual modificat...

Страница 4: ...or future reference Read all instructions before using the pro duct Maintenance and service operations are only to be carried out by authorized pro fessionals Any damage caused by manual modifica tion...

Страница 5: ...small spaces Do not place the dehumidifier in places where water may splash onto it Place the dehumidifier on a levelled and sturdy surface Lack of ventilation can cause overheating and fire Water may...

Страница 6: ...er If the dehumidifier is knocked over during use turn it off and unplug it from the main power supply immediately Visually inspect the unit to ensure there is no damage If you suspect the unit has be...

Страница 7: ...nit behind the water collector Note on the fuse The unit s circuit board PCB is designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board s...

Страница 8: ...lled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Caution Risk of fire flammable materials for R32 R290 units only IMPORTANT NOTE r...

Страница 9: ...rant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks NO...

Страница 10: ...s Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration detection equipment shall be calibrated in a refrigerant f...

Страница 11: ...to another refrigeration system unless it has been cleaned and checked 15 Labelling Equipment shall be labelled stating that it has been de commissioned and emptied of refrigerant The label shall be d...

Страница 12: ...t 40 humidity level set mode operation on indicator light 50 humidity level set mode operation on indicator light 60 humidity level set mode operation on indicator light Control buttons Mode Press to...

Страница 13: ...h is also being used for other electrical appliances Select a suitable location making sure you have easy access to an electrical outlet Plug the unit into an electrical socket outlet with earth conne...

Страница 14: ...e an electrical shock cause the insulation to deteriorate or cause the unit to rust The air intake and outlet grilles get soiled easily so use a vacuum attachment or brush to clean 2 Clean the collect...

Страница 15: ...r service review the chart below first yourself Problem What to check The unit does not start Make sure the dehumidifier s plug is pushed completely into the outlet Check the house fuse circuit breake...

Страница 16: ...iliar with these instructions Knowing what could go wrong can help prevent problems from occurring 4 ENVIRONMENTAL PROTECTION In order to protect the environment we strive to reduce the volume of pack...

Страница 17: ...lementos que puedan ser reparados por el usuario Acuda al Servicio de Atenci n al Cliente Avisos Importantes Antes de usar el aparato lea atentamente este manual de instrucciones y gu rdelo en un luga...

Страница 18: ...e el aparato se en fr e antes de efectuar cualquier operaci n de limpieza Para limpiar el exterior del producto utilice nicamente un pa o suave y seco Cualquier da o derivado del uso del aparato fuera...

Страница 19: ...e calor Puede causar una descarga el ctrica o un incendio debido a la generaci n de calor Puede causar descargas el ctricas o un incendio 1 5 Advertencias de seguridad Siga las instrucciones de este m...

Страница 20: ...tenga precauci n de no comprimirlo No pase por encima del deshumidificador ni se siente sobre l ya que podr a causar una descarga el ctrica o una aver a en el deshumidificador Existe peligro de incen...

Страница 21: ...personas igualmente cualificadas para evitar riesgos La instalaci n del deshumificador deber realizarse de acuerdo con las normativas nacionales sobre cableado El aparato con calentador el ctrico deb...

Страница 22: ...e pared que va a utilizar no est conectado a tierra ni protegido ade cuadamente por un fusible de retardo o un disyuntor el fusible o el disyuntor que ne cesita est n determinados por la corriente m x...

Страница 23: ...or el c trico en funcionamiento No perfore ni queme la unidad Tenga en cuenta que es posible que los refrigerantes no contengan olor Instale opere y almacene el aparato en una habitaci n con una super...

Страница 24: ...as de equipos que se pueden almacenar juntas estar determinado por las regulaciones locales 6 Servicios de informaci n 1 Controles de rea Antes de comenzar a trabajar en sistemas que contienen refrige...

Страница 25: ...les y procedimientos de inspecci n de componentes Si se produce un fallo que pueda poner en peligro la seguridad ning n suministro el ctrico deber estar conectado al circuito hasta que se corrija sati...

Страница 26: ...el circuito con gas inerte evacuar purgar nuevamente con gas inerte abrir el circuito cort ndolo o sold ndolo La carga de refrigerante debe recuperarse en los cilindros de recuperaci n adecuados El si...

Страница 27: ...icen cilindros de recuperaci n de refrigerante apropiados Aseg rese de que est n disponibles los n meros correctos de cilindros para mantener la carga total del sistema Todos los cilindros que vaya a...

Страница 28: ...lame al servicio t cnico Luz indicadora de funcionamiento continuo Luz indicadora del modo de funcionamiento de ajuste del nivel de humedad al 40 Luz indicadora del modo de funcionamiento de ajuste de...

Страница 29: ...unidad Cuando use el deshumidificador por primera vez ponga la unidad en funcionamiento de forma continua durante 24 horas Esta unidad est dise ada para funcionar en un ambiente de trabajo de entre 5...

Страница 30: ...a manguera de drenaje de la salida y vuelva a instalar el tap n de goma 2 3 Mantenimiento Apague el deshumidificador y quite el tap n de la toma de pared antes de limpiarlo 1 Limpieza de la rejilla y...

Страница 31: ...da Cable de alimentaci n 2 4 Resoluci n de problemas Antes de llamar al servicio t cnico revise usted mismo la siguiente tabla Problema Qu debe verificar La unidad no arranca Aseg rese de que el enchu...

Страница 32: ...arizadosconestasinstrucciones El hecho de conocer los posibles problemas puede servirle de ayuda para evitar que se produzcan 4 PROTECCI N MEDIOAMBIENTAL A fin de proteger el medio ambiente intentamos...

Страница 33: ...r reparadas pelo utilizador Contacte o Servi o de Apoio ao Cliente Avisos Importantes Antes de utilizar o aparelho leia atentamen te este manual de instru es e guarde o num local seguro pois poder pre...

Страница 34: ...re que a m quina arrefe a antes de efetuar qualquer opera o de limpeza Para limpar a parte exterior do aparelho uti lize apenas um pano seco e macio fora deste mbito qualquer utiliza o in correta bem...

Страница 35: ...obre como utilizar e manter corretamente o seu desumidificador Um pouco de cuidado preventivo da sua parte poder poupar lhe muito tempo e dinheiro ao longo da vida til do seu desumidificador Encontrar...

Страница 36: ...funcionamento Poder provocar explos es ou inc ndios Cont m contaminantes e poder deix lo doente Poder provocar choques el tricos CUIDADO N o utilize a unidade em espa os pequenos N o coloque o desumi...

Страница 37: ...nico ou t cnicos de qualifica o semelhante para evitar si tua es de perigo O desumidificador deve ser instalado de acordo com os regu lamentos de instala o el trica nacionais O aparelho com resist nci...

Страница 38: ...m fus vel retardador ou disjuntor o fus vel ou disjuntor neces s rio determinado pela corrente m xima da unidade A corrente m xima indica da na placa de caracter sticas localizada na unidade pe a a el...

Страница 39: ...mento em funcionamento N o furar nem queimar Esteja ciente de que os refrigerantes po dem ser inodoros O aparelho deve ser instalado operado e guardado numa divis o com uma superf cie superior a 4 m2...

Страница 40: ...es do equipamento ser determinada por regulamentos locais 6 Informa es de assist ncia t cnica 1 Inspe es da rea Antes de come ar a trabalhar em sistemas que contenham gases refrigerantes inflam veis n...

Страница 41: ...ligar nenhuma fonte de alimenta o ao circuito at que a falha seja satisfatoriamente resolvida Se a falha n o puder ser corrigida imediatamente mas necess rio que o aparelho continue a funcionar dever...

Страница 42: ...e novamente com g s inerte abra o circuito cortando o ou soldando o O carregamento de refrigerante dever se efetuar nos cilindros de recupera o adequados O sistema deve ser lavado com azoto sem oxig n...

Страница 43: ...e que se utilizam apenas os devidos cilindros de recupera o Certifique se de que as quantidades corretas de cilindros para suportar o carregamento total do sistema est o dispon veis Todos os cilindros...

Страница 44: ...ada e volte a lig la Se o erro persistir contacte a Assist ncia T cnica Luz indicadora de funcionamento cont nuo ligada luz indicadora de modo de ajuste do n vel de humidade a 40 luz indicadora de mod...

Страница 45: ...exterior na divis o Ao utilizar a unidade Quando utilizar o desumidificador pela primeira vez opere o continuamente durante 24 horas Esta unidade foi concebida para funcionar num ambiente de funciona...

Страница 46: ...m cont nua n o estiver a ser utilizada retire a mangueira de escoamento da sa da e volte a instalar o tamp o de borracha 2 3 Manuten o Desligue o desumidificador e retire o cabo de alimenta o da tomad...

Страница 47: ...emas Antes de ligar para o apoio t cnico verifique a tabela abaixo Problema O que verificar A unidade n o arranca Certifique se de que o ficha de alimenta o do desumidificador est completamente introd...

Страница 48: ...de compra do aparelho AVISO qualquer tentativa de arranjar o aparelho sem contactar o fabricante ou revendedor ir invalidar a garantia Todos os utilizadores devem familiarizar se com estas instru es...

Страница 49: ...uced and distributed by Importado producido y distribuido por Importado produzido e distribu do por Worten equipamentos para o lar S A Rua Jo o Mendon a n 505 4464 503 Senhora da Hora Portugal dehumid...

Отзывы: