![Kuma Stoves K-180 Alpine LE Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/kuma-stoves/k-180-alpine-le/k-180-alpine-le_installation-and-operating-instructions-manual_2009739007.webp)
K-180
| Rev. 190829
SECTION 3 –
( I N )
INSTALLATION INSTRUCTIONS
FLOOR PROTECTION REQUIREMENTS
If the bottom of the insert is raised at least 5” from the combustible floor, then a hearth that provides ember
protection only (no R-value) is sufficient. If the bottom of the insert is less than 5” from the combustible floor,
then Type 2 thermal protection (with an R-value of 1.4) is required.
It is highly recommended that this insert is installed by a qualified professional certified by the
National Fireplace Institute.
The structural integrity of the floor, walls and ceiling/roof must be maintained.
NEVER INSTALL AN INSERT IN A SLEEPING ROOM
This insert is heavy: Get help from another person and use proper lifting techniques
Minimum
Hearth Size
G
6”
H
16”
TYPE 1 - Ember protection
RAISED HEARTH
Min. 5”
non-combustible
TYPE 1 - Ember protection
CANTILEVERED INSERT
Min. 5”
air space
TYPE 2 – 1.4 R-Value
INSERT AT FLOOR LEVEL
At floor level or less
than 5” above