![Kuka KR C2 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/kuka/kr-c2/kr-c2_operating-handbook_2009633021.webp)
2
The file $MACHINE.DAT (continued)
21 of 91
Maschinendaten 12.0400 en
2.1.19 $SLAVE_LOOP_FOL_ALARM[ ]
Deviation limit between master and slave
Data type
real
min
Value
----
Unit
degrees, mm
Value
max ----
Assignment
----
Shut--off threshold
If the following error exceeds the threshold value, PATH--MAINTAINING BRAKING is
triggered.
2.1.20 $SLAVE_LOOP_SPEED_ALARM[ ]
Max. speed deviation for torque--controlled slave drives
Data type
real
min
Value
----
Unit
rpm
Value
max ----
Assignment
----
Shut--off threshold
If the actual speed exceeds the threshold value, PATH--MAINTAINING BRAKING is
triggered. The value is specified in rpm.
2.1.21 $SLAVE_LOOP_PMCHANNEL[Ln]
Definition of the KPS module for slave control loops
Data type
int
min
Value
--
Unit
[ ]
Value
max ----
Assignment
----
$SLAVE_LOOP_PMCHANNEL[Ln]=y defines the KPS module connected to a slave control
loop. In the case of master loops, the value 0 must be entered as the assignment for these
control loops is already defined using $PMCHANNEL[An] (see above) and must not be taken
into consideration here.
2.1.22 $LOOP_TYPE[Ln]
Selection of the control loop type
Data type
int
min
Value
1
Unit
[ ]
Value
max 4
Assignment
----
$LOOP_TYPE[Ln]=y