9.4. 

Internal error messages 

All possible error messages monitored by the software are described in the following. They can be released or locked. 
The parameterisation (release) is described in the service instructions.  

9.4.1. 

Overspeed 

For the overspeed monitoring, either the generator frequency or the frequency of a pick-up is used (according to the pa-
rameterisation).  

9.4.2. 

Speed measurement failed 

This message is always effective. If all parameterised criteria for the R

UNNING 

message are withdrawn during 

operation, the monitoring is switched off. For this reason, the genset is shut down and the automatic system 
is locked and the 

FAILED START 

/

 MOTOR ERROR

 message is displayed. 

9.4.3. 

Engine does not switch off 

This message is always effective. If the motor still runs after the stop process has expired (parameterised 
though the switch-on duration of the stop solenoid), the stop process is repeated and the 

FAILED START 

/

 

MOTOR ERROR

 message is displayed. The automatic system is not locked, so that the genset is immediately 

ready for operation in the event of a start request (sprinkler request). 

10. 

Remote acknowledgement 

Existing alarms can be remotely acknowledged with a signal (L-) on terminal 32. A constant signal provides 
the command to unlock only once. The automatic system is also unlocked if all of the deactivating fault mes-
sages can be cleared.  
The  parameterisation  defines  which  alarms  are  to  be  cleared.  If  the  alarm  contact  is  still  active,  remote 
acknowledgement of the message is not possible. If the automatic system has been inhibited by the  Q

UICK 

S

TOP

 input, it cannot be unlocked by the remote acknowledgement, but only locally by changing the operat-

ing mode to O

FF

11. 

Speed regulation 

The automatic system provides adjusting pulses for the speed controller (if the function is enabled) when in 
A

UTO 

and T

EST 

operating modes, if the speed is not within the parameterised window. A pause is made be-

tween two pulses so that the motor has time to execute the command 

12. 

Emergency Stop / Emergency Off (external) 

A pulse on the Q

UICK 

S

TOP 

(E

MERGENCY 

S

TOP

) input is sufficient to trigger the Emergency Stop function. 

Thus, independent of the operating mode: 

  the genset is shut down 

  the automatic system is locked for further start processes (display: 

AUTOMATIC SYSTEM LOCKED

). 

 
In order to unlock, the system must be changed to O

FF 

operating mode. If the Q

UICK 

S

TOP 

signal is still pend-

ing, it cannot be unlocked. The A

UTOMATIC SYSTEM LOCKED

 display remains switched on. 

Содержание KEA 293 PST

Страница 1: ...All functions allocated to the genset are included for sprinkler operation Ten displays can be selected as alarms or operational indicators Provision has been made for remote acknowledgement of alarms...

Страница 2: ...5 8 3 Test operating mode 6 8 4 Sprinkler operation 6 9 Error messages Programmable operation indicators 6 9 1 Use as an operational indicator 6 9 2 Use as an error message 6 9 3 Alarms 9 and 10 6 9 4...

Страница 3: ...unit The connection regulations must be observed 3 The installation and commissioning must only be carried out by sufficiently qualified personnel 4 Applicable regulations especially those of the VDE...

Страница 4: ...can be selected using the keys 6 2 Start key The motor can be started in MANUALoperating mode by actuating this button If the motor needs to be pre heated the pre heating device must be externally co...

Страница 5: ...m is controlled by three criteria That s why this message has expired needs to be interpreted The message is controlled if the genset has not started at the end of the starting program This message FA...

Страница 6: ...t is free Stopping can then be carried out via the OFF operating mode or always via Emergency Stop 9 Error messages Programmable operation indicators Any of the 10 LEDs can either display an error mes...

Страница 7: ...et is immediately ready for operation in the event of a start request sprinkler request 10 Remote acknowledgement Existing alarms can be remotely acknowledged with a signal L on terminal 32 A constant...

Страница 8: ...kler operation run on time 0 sec Stop time 30 sec 13 2 Start process gas engine Starter on If the starter speed is exceeded the switching on of the ignition is delayed e g after 2 sec Then another 2 s...

Страница 9: ...70 C Operation 10 C 50 C Standards regulations DIN VDE 0160 14 2 Auxiliary voltage Switchable 9 12 15V or 14 24 35V DC 14 3 Analogue input Battery voltage monitor 14 4 Digital inputs and outputs Input...

Страница 10: ...293 PST_EN_Ver 2016 07 01 doc 10 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 1...

Страница 11: ...ST_EN_Ver 2016 07 01 doc 11 Alfred Kuhse GmbH Telephone 49 0 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 15 2...

Страница 12: ...Operating instructions KEA 293 PST 12 12 File BA_KEA 293 PST_EN_Ver 2016 07 01 doc 16 Drilling template Scale 1 1 print without scaling...

Отзывы: