AUXILIARY DRIVES

 signal is present. If no auxiliary drives are required (for start release), terminal 8 from X2, 

START RELEASE

 should be switched with L-. If the genset has not started at the end of the starting program, 

the 

FAILED START 

/

 MOTOR FAULT

 alarm is issued and the automatic system inhibited. Following the removal of 

the start command, the unit is switched off. 
In addition to the remote start, the genset can also be started via the Sprinkler command (see further in this 
document). 

8.3. 

Test operating mode 

After button selection to the T

EST 

position, the start program is triggered. The 

START CONTROL

 indication 

flashes as long as there is no start release and the 

SWITCH ON AUXILIARY DRIVES

 signal is present. If no auxil-

iary drives are required (for start release), terminal 8 from X2, 

START RELEASE

 should be switched with L-.  

In order to switch off the genset, the O

FF 

or (if the start command is not present) A

UTOMATIC 

operating mode 

must be selected. 

8.4. 

Sprinkler operation 

The following functions are intended for the operation of an electrical sprinkler pump: 
Switching of all switching-off alarms (overspeed alarm remains switched off for electronic speed sensor, de-
mand VDS 2100-22) to warning 
Start program to 6 (parameterisable) start attempts 
Upon sprinkler request being withdrawn: Cessation of the sprinkler operation after the 

SPRINKLER RUN

-

ON 

TIME

, or only manual switching off

 

 

Sprinkler operation is automatically cancelled after the sprinkler requirement is removed after a stipulated 
run-on time or can only be ended manually (demand VDS 2100-22).

 

If the automatic system is parameter-

ised for manual shutdown, the LED of the O

FF 

operating mode flashes as soon as the sprinkler input is free. 

Stopping can then be carried out via the O

FF 

operating mode (or always via Emergency Stop). 

9. 

Error messages / Programmable operation indicators 

Any of the 10 LEDs can either display an error message or be parameterised as an operation indicators. 

9.1. 

Use as an operational indicator 

These displays are independent of the selected operating mode. Thus, they can be used as displays of operational con-
ditions via contact inputs as normal signal lamps. The parameterisation is described in the service instructions. 

9.2. 

Use as an error message 

The arrival of an error message is displayed by the LED flashing. At the same time, the acoustic signal (for 
the entered duration) is controlled. The acoustic signal is switched off with a pulse from the  A

LARM 

O

FF 

key 

(or automatically after the entered time). However, the LED continues to flash. If the value 0 sec. is entered 
for the duration of the horn switch-on, no automatic switch-off is carried out: The horn remains switched on 
until manually deleted. 
Due to a second button actuation of A

LARM 

O

FF

, the message switches from flashing to continuously illumi-

nated. Due to the necessary second acknowledgement, e.g. the switching off of the acoustic signal genera-
tor after an automatic switch-off, it can be distinguished which error message has newly occurred. 
The display is cleared after the error is eliminated after renewed actuation of the A

LARM 

O

FF 

key. 

With messages that lead to the switching-off of the genset, further operation is inhibited and this is indicated 
by 

AUTOMATIC SYSTEM LOCKED

. In order to unlock, the O

FF 

operating mode (any actuated external Emergency 

OFF buttons must also be unlocked) must be

 

selected. 

The parameterisation is described in the service instructions. 

9.3. 

Alarms 9 and 10 

Both these alarms can be delayed from 0 to 240 sec. by the signal transmission, i.e. for the alarm contact to 
issue an error, the signal must be pending for a parameterised time. Furthermore, both these alarms are also 
effective in the Off operating mode (Off), but without switching on the horn. Thus, criteria (e.g. tank overfill-
ing, leakage warning) that always have to be reported can be monitored.  

Содержание KEA 293 PST

Страница 1: ...All functions allocated to the genset are included for sprinkler operation Ten displays can be selected as alarms or operational indicators Provision has been made for remote acknowledgement of alarms...

Страница 2: ...5 8 3 Test operating mode 6 8 4 Sprinkler operation 6 9 Error messages Programmable operation indicators 6 9 1 Use as an operational indicator 6 9 2 Use as an error message 6 9 3 Alarms 9 and 10 6 9 4...

Страница 3: ...unit The connection regulations must be observed 3 The installation and commissioning must only be carried out by sufficiently qualified personnel 4 Applicable regulations especially those of the VDE...

Страница 4: ...can be selected using the keys 6 2 Start key The motor can be started in MANUALoperating mode by actuating this button If the motor needs to be pre heated the pre heating device must be externally co...

Страница 5: ...m is controlled by three criteria That s why this message has expired needs to be interpreted The message is controlled if the genset has not started at the end of the starting program This message FA...

Страница 6: ...t is free Stopping can then be carried out via the OFF operating mode or always via Emergency Stop 9 Error messages Programmable operation indicators Any of the 10 LEDs can either display an error mes...

Страница 7: ...et is immediately ready for operation in the event of a start request sprinkler request 10 Remote acknowledgement Existing alarms can be remotely acknowledged with a signal L on terminal 32 A constant...

Страница 8: ...kler operation run on time 0 sec Stop time 30 sec 13 2 Start process gas engine Starter on If the starter speed is exceeded the switching on of the ignition is delayed e g after 2 sec Then another 2 s...

Страница 9: ...70 C Operation 10 C 50 C Standards regulations DIN VDE 0160 14 2 Auxiliary voltage Switchable 9 12 15V or 14 24 35V DC 14 3 Analogue input Battery voltage monitor 14 4 Digital inputs and outputs Input...

Страница 10: ...293 PST_EN_Ver 2016 07 01 doc 10 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 1...

Страница 11: ...ST_EN_Ver 2016 07 01 doc 11 Alfred Kuhse GmbH Telephone 49 0 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 15 2...

Страница 12: ...Operating instructions KEA 293 PST 12 12 File BA_KEA 293 PST_EN_Ver 2016 07 01 doc 16 Drilling template Scale 1 1 print without scaling...

Отзывы: