11 Technical Data
11.1 General
Data
Display:
6-digit, 14 segment LED
Digit height:
14 mm
Data retention:
> 10 years, EEPROM
Operation:
5 keys
11.2 Measuring signal inputs
Sampling rate:
10 readings/sec
SELV circuits, reinforced / double insulation
Voltage input
Progr. ranges:
0 … 10 V, 2 … 10 V, ± 10 V
Meas. range:
-10.5 ... +10.5 V
Resolution:
< 0.4 mV (
±
15Bit)
Meas. accuracy typ. 0.02 % of range
@ 23°C:
max.
0.05 % of range
Temperature drift: < 100 ppm/K
Input resistance: 1 M
Max. voltage:
± 30 V
Current input
Progr. ranges:
0 ... 20 mA, 4 … 20 mA
Measuring range: -0.5 ... 21 mA
Resolution:
1 µA (> 14 Bit)
Measuring accuracy typ. 0.02 % of range
@ 23°C:
max.
0.05 % of range
Temperature drift: < 100 ppm/K
Input resistance: 22
+ PTC 25
Voltage drop:
ca. 1,8 V @ 20 mA
Max. current:
60 mA
11.3 Control Inputs MPI 1 / MPI 2
SELV circuits, reinforced / double insulation
Quantity:
2, optocouplers
Function:
programmable
Switching levels: Low: < 2 V
High: > 4 V (max. 30 V)
Pulse length:
>100 ms
11.4 Alarm
outputs
Relays:
changeover contacts
Prescribed fuse: 5A
Switching voltage: max. 250 V AC / 125 V DC
min. 5 V AC / V DC
Switching current: max. 5 A AC / A DC
min.
10
mA
Switching capacity: max. 1250 VA / 150 W
The maximum values shall in no case
be exceeded!
Mechanical service life (switching cycles) 1x10
7
N° of switching cycles at 5 A / 250 V AC 5x10
4
N° of switching cycles at 5 A /30 V DC
5x10
4
11.5 Supply voltage
AC supply:
100 ... 240 V AC / max. 9 VA
50 / 60 Hz, Tolerance
±
10%
ext. fuse protection: T 0.1 A
DC supply:
10 ... 30 VDC / max. 3.5 W
with galvanic isolation and,
reverse polarity protection
SELV, CLASS II (Limited
Power Source)
ext. fuse protection: T 0.4 A
Mains hum
50 Hz or 60 Hz,
suppression :
programmable
11.6 Sensor Supply voltage
(Voltage output for external sensors)
SELV circuits, reinforced / double insulation
at AC supply:
24 VDC
r
15 %, 30 mA
15 VDC
r
1 %, 25 mA
at DC supply:
15 VDC
r
1 %, 25 mA
11.7 Climatic Conditions
Operating temperature: -20°C ... +65°C
Storage temperature: -25°C ... +75°C
Relative humidity: R.H. 93 % at +40°C,
non-condensing
Altitude:
up to 2000 m
11.8 EMC
Noise immunity: EN61000-6-2
with shielded signal and
control cables
Noise emission: EN55011 Class B
11.9 Device Safety
Design to:
EN 61010 Part 1
Protection Class: Protection Class 2 (front side)
Only the front side is classified as
accessible for the operator.
Application area: Pollution level 2
over-voltage Category II
Insulation:
Front: double insulation,
Rear side: basic insulation,
Signal inputs and und sensor power supply: SELV
11.10 Mechanical Data
Housing:
Panel mount housing
to DIN 43 700, RAL 7021
Dimensions:
96 x 48 x 102 mm
Panel cut-out:
92
+0.8
x 45
+0.6
mm
Installation depth: approx. 92 mm incl. terminals
Weight::
approx.
180
g
Protection:
IP65 (front, device only)
Housing material: Polycarbonate UL94 V-2
Vibration resistance: 10 - 55 Hz / 1 mm / XYZ
EN60068-2-6
30 min in each direction
en
gl
is
h
Page 19
Содержание CODIX 565
Страница 6: ...5 Blockschaltbild 6 Anschlussbelegung Seite 6 ...
Страница 7: ...7 Bedienkonzept Betriebsmode deutsch Seite 7 ...
Страница 17: ...Ansteuerung bei steigendem Mess Signal Ansteuerung bei fallendem Mess Signal deutsch Seite 17 ...
Страница 28: ...5 Block diagram 6 Connections Page 6 ...
Страница 29: ...7 Operating concept Operating mode english Page 7 ...
Страница 31: ...Selecting Function Setting Parameters Accepting Parameters Function Groups Function Parameter english Page 9 ...
Страница 39: ...Control with incrementing measuring signal Control with decrementing measuring signal english Page 17 ...
Страница 66: ...Page 22 ...
Страница 72: ...5 Schema a blocchi 6 Collegamento Pagina 6 ...
Страница 94: ...5 Diagrama funcional 6 Conexiones Página 6 ...
Страница 109: ...español Página 21 ...
Страница 111: ......