R60726.0002 – Index 4 

 

EN - page 40 

Continuation „Analog Out Menu“: 

 

ANALOG GAIN (%)  

This parameter sets the maximum modulation. The ANALOG GAIN returns the max. Control of the analogue output 

in% related to (+/-) 10 V or 20 mA. 

 

e. g. 102.00 corresponds to a conversion of 10.2 V or 20.4 mA, when the ANALOG END value is reached. 

e. g. 95.00 corresponds to a conversion of 9.5 V or 18 mA, when the ANALOG END value is reached. 

 

0.00 

Smallest gain 

100.00 

Default value 

110.00 

Highest gain 

 

ANALOG OFFSET (%) 

This parameter defines the zero offset of the analog output. 

 

e. g. 0.20 result in an offset of 0.02 V or 0.04 mA at ANALOG START value 

 

-99.99 

Smallest offset 

Default value 

+99.99 

Highest offset 

 

Содержание 573T

Страница 1: ... 20 mA High accuracy reference output 10 V for potentiometers 1 kOhm Bright and high contrast display with event dependent color variations Emulation of a 7 segment display inclusively icons and units Intuitive and easy parameterization by plain text and touchscreen 24 V auxiliary output for encoder supply Totalization for each input Linearization with 24 control points for each input Numerous fea...

Страница 2: ... Extension with IO Link in preparation available on request 573T_5a June 18 Extension with Modbus Legal notices All contents included in this manual are protected by the terms of use and copyrights of Fritz Kübler GmbH Any reproduction modification usage or publication in other electronic and printed media as well as in the internet requires prior written authorization by Fritz Kübler GmbH German ...

Страница 3: ...10 Relay Output Option 14 3 11 IO Link Option 15 4 Display and touch screen 16 4 1 Screen structure for parametrization 16 4 2 Screen structure in operation 17 5 Parameter Overview Menu Structure 18 5 1 General Menu 20 5 2 IN 1 Properties 21 5 3 IN 1 Linearization 23 5 4 IN 1 Totalization 24 5 5 IN 2 Properties 25 5 6 IN 2 Linearization 26 5 7 IN 2 Totalization 26 5 8 Linkage Properties 27 5 9 IO ...

Страница 4: ...R60726 0002 Index 4 EN page 4 6 6 Technical specifications 59 ...

Страница 5: ...es the right to modify the hardware software or operation manual at any time and without prior notice Therefore there might be minor differences between the unit and the descriptions in operation manual The raiser respectively positioner is exclusively responsible for the safety of the system and equipment where the unit will be integrated During installation or maintenance all general and also al...

Страница 6: ...cross sections for wiring are described in the Technical Specifications Before first start up it must be ensured that all connections and wires are firmly seated and secured in the screw terminals All inclusively unused terminals must be fastened by turning the relevant screws clockwise up to the stop Overvoltages at the connections must be limited to values in accordance to the overvoltage catego...

Страница 7: ... in the parameter menu The device can be set to one of the following operation modes SINGLE single channel operation of input 1 DUAL two channel operation of input 1 and 2 IN 1 IN 2 two channel operation of input 1 and 2 in combination with sum IN1 IN 2 two channel operation of input 1 and 2 in combination with difference IN 1 x IN 2 two channel operation of input 1 and 2 in combination with multi...

Страница 8: ...R60726 0002 Index 4 EN page 8 2 2 Function diagram ...

Страница 9: ...at the auxiliary voltage output All GND terminals are internally interconnected 3 2 Auxiliary Voltage Output Terminal 3 and 4 provide an auxiliary output for supply of sensors and encoders The output voltage depends on the power supply DC version AC version The encoder voltage is approx 1 V lower than the power supply voltage at terminal 1 and 2 and should be loaded with max 250 mA The encoder vol...

Страница 10: ...t or current input can be set in the Menu IN 1 IN 2 PROPERTIES Important Before connecting the sensor the configuration voltage or current input must be set Wiring of the incremental inputs Voltage input Current input 3 4 Reference Output The unit provides a 10 V reference output at terminal 8 This output should be loaded with 10 mA maximum This reference output can be used for connecting a potent...

Страница 11: ...ng contacts When exceptionally mechanical contacts are used please connect an external capacitor between GND and the corresponding input A capacity of 10 µF will reduce the input frequency to 20 Hz and miscounting due to contact bouncing will be eliminated 3 6 Analog Output Option A 16 bit analog output is available at terminal 13 and 14 15 This output can be configured and scaled in the ANALOG ME...

Страница 12: ...he SERIAL MENU The serial interface RS232 or RS485 can be used for easy setup and commissioning of the units to modify settings and parameters during operation to read out internal states and actual measuring values by PC or PLC The following drawing shows the connection to a PC by using a standard Sub D 9 connector Connection of the RS232 interface Connection of the RS485 interface ...

Страница 13: ... must be applied to input terminal 19 COM In case of switching inductive loads it is advisable to use external filtering of the coils The switching states is displayed display with unit and status bar as C1 and C4 Wiring of the control outputs 3 9 AC Power supply Option The unit accepts AC supply from 115 to 230 V at the terminals 24 and 25 The power consumption depends on the level of the supply ...

Страница 14: ...re available at terminal 27 28 29 and 30 31 32 Switching conditions can be set in the PRESELECTION MENU The switching states are displayed display with unit and status bar as K1 and K2 AC switching capacity max 250 VAC max 3 A max 750 VA DC switching capacity max 150 VDC max 2 A max 50 W Wiring of the relay outputs ...

Страница 15: ... LINK PROPERTIES Display for analog sensors and data transmission of 6 input process data 32 Byte 6 input process data are sent to the IO link master cyclically The following values are submitted Value 1 Result of input 1 Value 2 Result of input 2 Value 3 Result of the link from input 1 to input 2 Value 4 Result of totalization of input 1 Value 5 Result of totalization of input 2 Value 6 Result of...

Страница 16: ...ect the parameter menu via arrow buttons and confirm with OK The menu selection can be terminated with C Parameter selection Select the parameter via arrow buttons and confirm with OK The parameter selection can be terminated with C Parameter editing Edit the parameter via arrow button up and down shift cursor via left and right and save with OK The parameter editing can be terminated with C Param...

Страница 17: ...d status bar To switch to the next display press the touch screen Control or Relay status are only shown with Option Analog Control Relay Output Two line display To switch to the next display press the top of the screen Display for quick start for enter preselection values PRESELECT VALUES To switch to the next display press the top of the screen or the skip button This is only possible with Optio...

Страница 18: ...TORY SETTINGS IN 1 PROPERTIES CONFIGURATION START VALUE END VALUE DECIMAL POINT SCALE UNITS SAMPLING TIME AVERAGE FILTER OFFSET LINEARIZATION TOTALIZATION IN 1 LINEARIZATION P1 X P1 Y P2 X P2 Y P23 X P23 Y P24 X P24 Y IN 1 TOTALIZATION TIME BASE DIVIDER DECIMAL POINT SCALE UNITS Menu Parameter IN 2 PROPERTIES CONFIGURATION START VALUE END VALUE DECIMAL POINT SCALE UNITS SAMPLING TIME AVERAGE FILTE...

Страница 19: ...LAY 2 EVENT COLOR 2 PRESELECTION 3 MENU SOURCE 3 MODE 3 HYSTERESIS 3 PULSE TIME 3 OUTPUT TARGET 3 OUTPUT POLARITY 3 OUTPUT LOCK 3 START UP DELAY 3 EVENT COLOR 3 Menu Parameter PRESELECTION 4 MENU SOURCE 4 MODE 4 HYSTERESIS 4 PULSE TIME 4 OUTPUT TARGET 4 OUTPUT POLARITY 4 OUTPUT LOCK 4 START UP DELAY 4 EVENT COLOR 4 SERIAL MENU UNIT NUMBER SERIAL BAUD RATE SERIAL FORMAT SERIAL INIT SERIAL PROTOCOL ...

Страница 20: ...fines the PIN code to lock the quick start of the menu PRESELECTION VALUE for entering the preselection values master PIN 6079 This Lock function is only useful in conjunction with active lock function in PIN PARAMETER 0000 No lock 9999 Access after entering PIN Code 9999 PIN PARAMETER This parameter defines the PIN code for lock function of all parameters master PIN 6079 0000 No lock 9999 Paramet...

Страница 21: ...t end value 10000 Default value 99999 Highest end value DECIMAL POINT This value defines the position of the decimal point 0 NO No decimal point 1 0000000 0 Decimal point at the specified position 2 000000 00 Decimal point at the specified position 3 00000 000 Decimal point at the specified position 4 0000 0000 Decimal point at the specified position 5 000 00000 Decimal point at the specified posi...

Страница 22: ...mbers of floating average cycles 4 16 numbers of floating average cycles OFFSET This parameter defines the zero offset tara of the input This parameter does not affect the TOTALIZATION function 99 999 Smallest offset 0 Default value 99 999 Highest offset LINEARIZATION This parameter defines the linearization function The linearization points are defined in Menu IN 1 IN 2 LINEARIZATION See appendix...

Страница 23: ... X X coordinate of the linearization point This value representing the display value which the unit show in the display without linearization 99999999 Smallest X coordinate 0 Default value 99999999 Largest X coordinate P1 Y P24 Y Y coordinate of the linearization point This is the display value which the unit should show in the display with linearization E g P2 X is replaced by P2 Y 99999999 Small...

Страница 24: ... 1 for the operation function at the control input see Command Menu DIVIDER This parameter defines the devisor for the totalization 0 1 No division 1 10 The result of the totalization is divided by 10 2 100 The result of the totalization is divided by 100 3 1000 The result of the totalization is divided by 1000 DECIMAL POINT This value defines the position of the decimal point 0 NO No decimal poin...

Страница 25: ...f input 2 at 10 V or 20 mA see IN 1 Properties DECIMAL POINT Position of the decimal point see IN 1 Properties SCALE UNITS The displayed units see IN 1 Properties SAMPLING TIME S Sampling interval of input 2 see IN 1 Properties AVERAGE FILTER Selectable averages filter function see IN 1 Properties OFFSET Zero offset tara see IN 1 Properties LINEARISATION Linearization function see IN 1 Properties ...

Страница 26: ... Y Y coordinate of the linearization point see IN 1Linearization 5 7 IN 2 Totalization The totalization of input 2 function is defined in this menu TIME BASE The time base of the totalization see IN 1 Totalization DIVIDER The devisor for the totalization see IN 1 Totalization DECIMAL POINT Position of the decimal point see IN 1 Totalization SCALE UNITS The displayed units see IN 1 P Totalization ...

Страница 27: ...ALUE This parameter defines the additive constant the result of the link will be charged 99999999 Smallest end value 0 Default value 99999999 Highest end value DECIMAL POINT This value defines the position of the decimal point 0 NO No decimal point 1 0000000 0 Decimal point at the specified position 2 000000 00 Decimal point at the specified position 3 00000 000 Decimal point at the specified posi...

Страница 28: ...es the position of the decimal point 0 NO No decimal point 1 0000000 0 Decimal point at the specified location 2 000000 00 Decimal point at the specified location 3 00000 000 Decimal point at the specified location 4 0000 0000 Decimal point at the specified location 5 000 00000 Decimal point at the specified location 6 00 000000 Decimal point at the specified location 7 0 0000000 Decimal point at ...

Страница 29: ...for devices with option Control Analog or Relay Output PRESELECTION 1 Preselection switching point 1 99999999 Smallest value 1000 Default value 99999999 Highest value PRESELECTION 2 Preselection switching point 2 99999999 Smallest value 2000 Default value 99999999 Highest value PRESELECTION 3 Preselection switching point 3 99999999 Smallest value 3000 Default value 99999999 Highest value PRESELECT...

Страница 30: ...t 1 with totalization 4 INPUT 2 TOTAL the reference source is input 2 with totalization 5 LINKAGE TOTAL the reference source is the result of the linking of input1 and input 2 with totalization 6 IO LINK VALUE 1 the reference source is the process data out value 1 sent by the IO Link master 7 IO LINK VALUE 2 the reference source is the process data out value 2 sent by the IO Link master 8 MINIMUM ...

Страница 31: ...ot equal 0 the following switching condition is applied Display value PRESELECTION 1 HYSTERESIS 1 OFF Display value PRESELECTION 1 HYSTERESIS 1 OFF 3 RESULT PRES Display value is greater or equal PRESELECTION 1 e g overspeed With HYSTERESIS 1 not equal 0 the following switching condition is applied Display value PRESELECTION 1 ON Display value PRESELECTION 1 HYSTERESIS 1 OFF 4 RESULT PRES Display ...

Страница 32: ...lay the output is set when at least one switching condition is true 0 NO No assignment 1 CTRL OUT 1 Switching condition assigned to Ctrl Out 1 2 CTRL OUT 2 Switching condition assigned to Ctrl Out 2 3 CTRL OUT 3 Switching condition assigned to Ctrl Out 3 4 CTRL OUT 4 Switching condition assigned to Ctrl Out 4 5 RELAY 1 Switching condition assigned to Rel 1 6 RELAY 2 Switching condition assigned to...

Страница 33: ...tart Up Delay 3 and 4 have an automatic start up suppression 0 000 No start up suppression 60 000 Start up suppression in seconds EVENT COLOR 1 Event depending change of the display color for the switching condition of preselection 1 EVENT COLOR 1 has the lowest priority EVENT COLOR 2 4 are allowed to overwrite this color change 0 NO CHANGE No color change 1 CHANGE TO RED Color change to red 2 CHA...

Страница 34: ...itching condition of preselection 2 See chapter PRESELECTION 1 MENU OUTPUT TARGET 2 Assignment of an output or relay for the switching condition of preselection 2 See chapter PRESELECTION 1 MENU expect default value see PRESELECTION 1 MENU 2 CTRL OUT 2 Assignment of switching conditions at Ctrl Out 2 OUTPUT POLARITY 2 Polarity for the switching condition of preselection 2 See chapter PRESELECTION ...

Страница 35: ...ARGET 3 Assignment of an output or relay for the switching condition of preselection 3 See chapter PRESELECTION 1 MENU see PRESELECTION 1 MENU 3 CTRL OUT 3 Assignment of switching conditions at Ctrl Out 3 OUTPUT POLARITY 3 Polarity for the switching condition of preselection 3 See chapter PRESELECTION 1 MENU OUTPUT LOCK 3 Latch for the switching condition of preselection 3 See chapter PRESELECTION...

Страница 36: ...ION 1 MENU OUTPUT TARGET 4 Assignment of an output or relay for the switching condition of preselection 4 See chapter PRESELECTION 1 MENU except default value see PRESELECTION 1 MENU 4 CTRL OUT 4 Assignment of switching conditions at Ctrl Out 4 OUTPUT POLARITY 4 Polarity for the switching condition of preselection 4 See chapter PRESELECTION 1 MENU OUTPUT LOCK 4 Latch for the switching condition of...

Страница 37: ...es the bit data format 0 7 EVEN 1 7 data Parity even 1 Stop 1 7 EVEN 2 7 data Parity even 2 Stops 2 7 ODD 1 7 data Parity odd 1 Stop 3 7 ODD 2 7 data Parity odd 2 Stops 4 7 NONE 1 7 data no Parity 1 Stop 5 7 NONE 2 7 data no Parity 2 Stops 6 8 EVEN 1 8 data Parity even 1 Stop 7 8 ODD 1 8 data Parity odd 1 Stop 8 8 NONE 1 8 data no Parity 1 Stop 9 8 NONE 2 8 data no Parity 2 Stops SERIAL INIT This ...

Страница 38: ...tched off The unit will send data upon a serial request or with command SERIAL PRINT 60 000 Cycle time in seconds SERIAL VALUE This parameter defines the value to be transmitted Setting Code Register contents 0 0 Value input 1 1 1 Value input 2 2 2 Result of the linking of input1 and input 2 3 3 Result totalizator 1 4 4 Result totalizator 2 5 5 Result of the linking of 1 and 2 with totalization 6 ...

Страница 39: ...e the reference source is input 1 9 MAXIMUM VALUE 1 maximum value he reference source is input 1 10 MINIMUM VALUE 2 minimum value the reference source is input 2 11 MAXIMUM VALUE 2 maximum value he reference source is input 2 The totalization depends on the operation mode See chart in chapter IN 1 Totalization ANALOG FORMAT This parameter defines the output characteristics The analogue output is p...

Страница 40: ...to a conversion of 10 2 V or 20 4 mA when the ANALOG END value is reached e g 95 00 corresponds to a conversion of 9 5 V or 18 mA when the ANALOG END value is reached 0 00 Smallest gain 100 00 Default value 110 00 Highest gain ANALOG OFFSET This parameter defines the zero offset of the analog output e g 0 20 result in an offset of 0 02 V or 0 04 mA at ANALOG START value 99 99 Smallest offset 0 Def...

Страница 41: ...ee chapter Screen structure in operation d 12 RESET MIN MAX Reset the Min Max values d s 13 CLEAR LOOP TIME N A 14 ACTIVATE N A 15 STORE DATA N A 16 TESTPROGRAM N A 17 SET RED COLOR Red display Event depending change of the display color by a switching condition is possible see PRESELECTION 1 4 MENU d 18 SET GREEN COLOR Green display Event depending change of the display color by a switching condi...

Страница 42: ... Activate at falling edge dynamic INPUT 2 ACTION This parameter defines the function of the input Ctrl In 2 See parameter INPUT 1 ACTION INPUT 2 CONFIG This parameter defines the switching characteristics of the input Ctrl In 2 See parameter INPUT 1 CONFIG INPUT 3 ACTION This parameter defines the function of the input Ctrl In 3 See parameter INPUT 1 ACTION INPUT 3 CONFIG This parameter defines th...

Страница 43: ... master 8 MINIMUM VALUE 1 minimum value the reference source is input 1 9 MAXIMUM VALUE 1 maximum value he reference source is input 1 10 MINIMUM VALUE 2 minimum value the reference source is input 2 11 MAXIMUM VALUE 2 maximum value he reference source is input 2 SOURCE DUAL TOP Reference source for two line display first line 0 INPUT 1 the reference source is input 1 1 INPUT 2 the reference sourc...

Страница 44: ...eference source is the result of the linking of input1 and input 2 with totalization 6 IO LINK VALUE 1 the reference source is the process data out value 1 sent by the IO Link master 7 IO LINK VALUE 2 the reference source is the process data out value 2 sent by the IO Link master 8 MINIMUM VALUE 1 minimum value the reference source is input 1 9 MAXIMUM VALUE 1 maximum value he reference source is ...

Страница 45: ...rcent 10 Min brightness 80 Default value 100 Max brightness CONTRAST This parameter defines the viewing angle 0 Viewing angle from top 1 Viewing angle from center 2 Viewing angle from bottom SCREEN SAVER S This parameter defines the time in seconds until the display is switched off after the last touch action A new touch action will activate the display again 0 No switch off 9999 Longest time to s...

Страница 46: ...AD1 AD2 C1 C2 ENQ EOT control character Hex 04 AD1 unit address High Byte AD2 unit address Low Byte C1 register code High Byte C2 register code Low Byte ENQ control character Hex 05 The following example shows the request string for readout of the actual input frequency of a monitor Code 1 from a unit with unit address 11 ASCII Code EOT 1 1 1 ENQ Hex Code 04 31 31 3A 31 05 Binary Code 0000 0100 00...

Страница 47: ...8 g 9 kg 10 oz 11 W 12 kW 13 VA 14 mm 15 cm 16 m 17 inch 18 feet 19 C 20 F 21 K 22 1 sec 23 1 min 24 1 h 25 gal min 26 Pa 27 kPa 28 29 Edit Unit A customized unit with up to 16 digits can be edited using this parameter Pressing the OK button opens the Edit Unit Menu A unit can be created using the arrow keys by pressing and holding the arrow keys the characters scroll fast The OK butten saves the ...

Страница 48: ...999999 99999999 0 23 IN 1 LINEARIZATION P1 Y A1 0 99999999 99999999 0 24 IN 1 LINEARIZATION P2 X A2 0 99999999 99999999 0 25 IN 1 LINEARIZATION P2 Y A3 0 99999999 99999999 0 26 IN 1 LINEARIZATION P3 X A4 0 99999999 99999999 0 27 IN 1 LINEARIZATION P3 Y A5 0 99999999 99999999 0 28 IN 1 LINEARIZATION P4 X A6 0 99999999 99999999 0 29 IN 1 LINEARIZATION P4 Y A7 0 99999999 99999999 0 30 IN 1 LINEARIZAT...

Страница 49: ...RIZATION P21 Y E1 0 99999999 99999999 0 64 IN 1 LINEARIZATION P22 X E2 0 99999999 99999999 0 65 IN 1 LINEARIZATION P22 Y E3 0 99999999 99999999 0 66 IN 1 LINEARIZATION P23 X E4 0 99999999 99999999 0 67 IN 1 LINEARIZATION P23 Y E5 0 99999999 99999999 0 68 IN 1 LINEARIZATION P24 X E6 0 99999999 99999999 0 69 IN 1 LINEARIZATION P24 Y E7 0 99999999 99999999 0 70 IN 1 TOTALIZATION BASE E8 0 0 3 0 71 IN...

Страница 50: ...99999 99999999 0 112 IN 2 LINEARIZATION P12 X J0 0 99999999 99999999 0 113 IN 2 LINEARIZATION P12 Y J1 0 99999999 99999999 0 114 IN 2 LINEARIZATION P13 X J2 0 99999999 99999999 0 115 IN 2 LINEARIZATION P13 Y J3 0 99999999 99999999 0 116 IN 2 LINEARIZATION P14 X J4 0 99999999 99999999 0 117 IN 2 LINEARIZATION P14 Y J5 0 99999999 99999999 0 118 IN 2 LINEARIZATION P15 X J6 0 99999999 99999999 0 119 I...

Страница 51: ...ER N2 0 99999999 9999999 9 1 155 IO LINK PROPERTIES IN1 ADDITIVE VALUE N3 0 99999999 9999999 9 0 156 IO LINK PROPERTIES IN1 DECIMAL POINT N4 0 0 7 0 157 IO LINK PROPERTIES IN1 SCALE UNITS N5 0 0 29 0 158 IO LINK PROPERTIES IN2 FACTOR N6 0 99999999 9999999 9 1 159 IO LINK PROPERTIES IN2 DEVIDER N7 0 99999999 9999999 9 1 160 IO LINK PROPERTIES IN2 ADDITIVE VALUE N8 0 99999999 9999999 9 0 161 IO LINK...

Страница 52: ... TIME 1 P4 0 0 60000 0 177 PRESELECTION 1 MENU OUTPUT TARGET 1 P5 0 0 6 1 178 PRESELECTION 1 MENU OUTPUT POLARITY 1 P6 0 0 1 0 179 PRESELECTION 1 MENU OUTPUT LOCK 1 P7 0 0 1 0 180 PRESELECTION 1 MENU START UP DELAY 1 P8 0 0 60000 0 181 PRESELECTION 1 MENU EVENT COLOR 1 P9 0 0 3 0 182 PRESELECTION 1 MENU __ Q0 0 0 0 0 183 PRESELECTION 1 MENU __ Q1 0 0 0 0 ...

Страница 53: ...RITY 3 R8 0 0 1 0 201 PRESELECTION 3 MENU OUTPUT LOCK 3 R9 0 0 1 0 202 PRESELECTION 3 MENU START UP DELAY 3 S0 0 0 1 0 203 PRESELECTION 3 MENU EVENT COLOR 3 90 0 0 3 0 204 PRESELECTION 3 MENU __ 91 0 0 0 0 205 PRESELECTION 3 MENU __ 92 0 0 0 0 206 PRESELECTION 4 MENU SOURCE 4 9 0 0 11 0 207 PRESELECTION 4 MENU MODE 4 S1 0 0 6 0 208 PRESELECTION 4 MENU HYSTERESIS 4 S2 0 0 99999 0 209 PRESELECTION 4...

Страница 54: ...MENU INPUT 2 ACTION V0 0 0 26 0 237 COMMAND MENU INPUT 2 CONFIG V1 0 0 3 2 238 COMMAND MENU INPUT 3 ACTION V2 0 0 26 0 239 COMMAND MENU INPUT 3 CONFIG V3 0 0 3 2 240 COMMAND MENU __ V4 0 0 0 0 241 COMMAND MENU __ V5 0 0 0 0 242 COMMAND MENU __ V6 0 0 0 0 243 COMMAND MENU __ V7 0 0 0 0 244 DISPLAY MENU START DISPLAY V8 0 0 1 0 245 DISPLAY MENU SOURCE SINGLE V9 0 0 11 0 246 DISPLAY MENU SOURCE DUAL ...

Страница 55: ...5 TARA INPUT 2 56 TARA INPUT 1 2 57 RESET TOTAL 1 58 RESET TOTAL 2 59 RESET TOTAL LINKAGE 60 TEACH PRESELECTION 1 61 TEACH PRESELECTION 2 62 TEACH PRESELECTION 3 63 TEACH PRESELECTION 4 64 SCROLL DISPLAY 65 CLEAR MIN MAX VALUES 66 CLEAR LOOP TIME 67 ACTIVATE DATA 68 STORE EEPROM 69 TESTPROGRAMM ...

Страница 56: ...iagram The parameters P1 X to P24 X are used to specify the coordinates on the x axis These are the measuring values that the unit normally would generate according to the actual input signal Now enter the attached values to parameter P1 Y to P24 Y These are the values that the unit will generate instead of the x values i e P5 Y replaces P5 X etc The X Coordinates must use continuously increasing ...

Страница 57: ...ty P01_x P10_x P15_x P16_x Pressure Sensor 0 20 mA P01_x P10_x P16_x P01_y P07_y P15_y P16_y Pressure Volume P15_x P10_y To solve the problem we divide the non linear part of the tank into 14 parts We enter the expected display values of the pressure sensor to registers P01_x to P15 _x For the linear part of the tank it is sufficient to store the final pressure value to register P16_x Now we can e...

Страница 58: ...R60726 0002 Index 4 EN page 58 6 5 Dimensions Dimension in mm inch ...

Страница 59: ...cy Reaction time current or voltage operation 10 10 V max 2 mA 0 4 20 mA burden max 270 Ohm 16 Bit 0 1 150 ms Control outputs Option Number of outputs Format level Output current Reaction time 4 5 30 V depends on the Com voltage PNP max 200 mA 1 ms Relay outputs Option Number of outputs Configuration Switching voltage Switching current Switching power Reaction time 2 potential free changeovers max...

Страница 60: ...R60726 0002 Index 4 EN page 60 Kübler Group Fritz Kübler GmbH Schubertstrasse 47 78054 Villingen Schwenningen Germany Phone 49 7720 3903 0 Fax 49 7720 21564 info kuebler com www kuebler com ...

Отзывы: