-12-
C 6.9.3
Damp heat – steady state
+40
℃
, 95%RH, 48hrs
C 6.9.3
Humidity
+25
℃
95%RH 12hrs/
55
o
C 95%RH 12hrs, 2 cycles
C 6.9.3
Dry heat - storage
+85
℃
, 30%RH, 96hrs
C 6.9.3
Cold – storage
-40
℃
, 96hrs
IEC 61850-3 Mechanical Test Specifications
IEC 61850-3
Test
Specification
C 6.10
Vibration – resonant search
Class 2, 1Gn, 1/axis
C 6.10
Vibration – endurance
Class 2, 2Gn, 20/axis
C 6.10
Shock - responds
Class 2, 10Gn, 11ms, 3/axis
C 6.10
Shock - withstand
Class 2, 30Gn, 11ms, 3/axis
C 6.10
Shock – bump
Class 2, 20Gn, 16ms, 1000/axis
C 6.10
Seismic
Class 2, x – 2Gn, y – 1Gn, 10min.
C 6.10
Enclosure protection
Ingress of solid foreign subjects >=2.5mm
IEEE 1613 Test Specifications
IEEE 1613
Test
Level
Clause 4.1
DC rated control power inputs
80% 100% Max. DC IN
Clause 4.2
Ripple on DC power input
10%
Clause 4.3
AC rated control power inputs
N/A: No AC input in the device
Clause 5.2
Dielectric strength
DC IN vs. LAN ports: 2.8kV
Clause 5.3
Impulse voltage
DC IN vs. LAN ports: 1000Vac
Clause 6 / EMC
1Mhz oscillatory wave
DC IN & LAN: +/-2.5kV
Clause 6 / EMC
EFT
DC IN & LAN: +/-4kV
Clause 7 / EMC
RS
10V/m
Clause 8 / EMC
ESD
+/-15kV Air, +/-8kV Contact