background image

Contents 

 

1. Safety

 ···································································································· 

2

 

1.1 Safety notes ·····································································································2 

1.2 Symbols used in this guide ···················································································2 

2. Main feature

 ···························································································· 

2.1 Summarization ··································································································3 

2.2 Functions and Features ·······················································································3 

3. Installation

 ······························································································ 

4

 

3.1 Unpack checking ·······························································································4 

3.2 

Cabinet Outlook

 ······························································································4 

3.3 UPS module appearance ·····················································································8 

3.4 UPS module LCD control panel ·············································································8 

3.5 Installation notes ································································································9 

3.6 External Protective Devices ················································································ 10 

3.7 Power Cables·································································································· 10 

3.8 Power cable connect ························································································· 11 

3.9

 

Battery connection ···························································································· 12 

3.10 Online UPS Modules Replacement ····································································· 13 

4. Operation

 ········································································································ 15 

4.1 Operation Modes······························································································ 15 

4.2 Turn on/off UPS ······························································································· 15 

4.2.1 Restart procedure ·························································································· 15 

4.2.2 Test procedure ······························································································ 17 

4.2.3 Black(Cold) start procedure ·············································································· 17 

4.2.4 Maintenance Bypass ······················································································ 17 

4.2.5 Shut down procedure ······················································································ 18 

4.3 The Display ···································································································· 19 

4.3.1 System LCD Display ······················································································· 19 

4.3.2 UPS module LCD display················································································· 26 

4.3.3 Monitoring module control panel ········································································ 28 

4.4 Display Messages/Troubleshooting ······································································ 30 

4.5 Options ·········································································································· 33 

Appendix 1 Specifications

 ························································································ 35 

Appendix 2

 

UPS message table

 ················································································· 36 

Appendix 3 Problems and Solution

 ············································································ 41 

Appendix 4

 

RS232 communication port definition 

 ······················································ 43 

 

 

 

Содержание YDC9300-RT Series

Страница 1: ......

Страница 2: ...ency online UPS designed by our R D team who is with years of designing experiences on UPS With excellent electrical performance perfect intelligent monitoring and network functions smart appearance c...

Страница 3: ...y connection 12 3 10 Online UPS Modules Replacement 13 4 Operation 15 4 1 Operation Modes 15 4 2 Turn on off UPS 15 4 2 1 Restart procedure 15 4 2 2 Test procedure 17 4 2 3 Black Cold start procedure...

Страница 4: ...strongly poisonous and do harmful to body 4 Please avoid short circuit between anode and cathode of battery otherwise it will cause spark or fire 5 Don t disassemble the UPS cover or there may be an...

Страница 5: ...h 50KVA as maximum and vice versa so the 2M cabinet for 10 modles can reach max 100KVA N X parallel redundancy This series UPS adopts N X parallel redundancy design user can set different redundancy a...

Страница 6: ...g 1 Don t lean the UPS when moving it out from the packaging 2 Check the appearance to see if the UPS is damaged or not during the transportation do not switch on the UPS if any damage found Please co...

Страница 7: ...in Switch for UPS Module 2 19 Main Switch for UPS Module 3 20 Main Switch for UPS Module 4 21 Main Switch for UPS Module 5 22 Cover for terminal block 23 Inter connecting port for Modules 24 Dry Conta...

Страница 8: ...6 2 2M 19 Rack Cabinet Front View Side View Rear View 1 front lock 2 LCD Display 3 Side Lock 4 Rear Lock 1 2 2 3 2 2 2 4 2...

Страница 9: ...in Switch for UPS Module 2 24 Main Switch for UPS Module 3 25 Main Switch for UPS Module 4 26 Main Switch for UPS Module 5 27 Main Switch for UPS Module 6 28 Main Switch for UPS Module 7 29 Main Switc...

Страница 10: ...4 fan 5 UPS Module input switch 3 4 UPS Module LCD control panel LCD control panel introduction 1 LCD Display Board 2 ESC 3 Off button 4 On button 5 right or down 6 Enter 7 left or up 8 Output Indicat...

Страница 11: ...thin the required specs Temperature is a major factor in determining battery life and capacity In a normal installation the battery temperature is maintained between 15 C and 25 C Keep batteries away...

Страница 12: ...Over current Protection device shall be installed at the distribution panel of the incoming main supply It may identify the power cables current capacity as well as the overload capacity of the syste...

Страница 13: ...ut N GND Cable diameter 75mm2 35mm2 The 100KVA Item Input three phases Battery Output Single phase Ground Symbol Vin N Vin A Vin B Vin C BAT BATN BAT Vout L Vout N GND Cable diameter 150mm2 Or 2 75mm2...

Страница 14: ...e input Line BAT BATN and BAT are connected to the external battery box output L N are connected to the equipment load which is supplied by the UPS WARNING If the load equipment is not ready to accept...

Страница 15: ...current could be adjusted automatically according to battery capacity selected Also charger current is selectable Please refer to Chapter 4 3 LCD display CAUTION Ensure correct polaritybattery string...

Страница 16: ...matically and parallel up the modules into whole system Remove UPS module Remove the coronal screws on the left side of the module to stop the module running completely and remove the module after fan...

Страница 17: ...he inverter supply to bypass supply without interruption to the critical load In the event that the inverter output is not synchronized with the bypass AC source the static switch will perform a trans...

Страница 18: ...wer switch must be OFF Turn ON the input switches of all UPS modules which locate at the modules rear panels When AC MAINS input voltage within the range the MAINS LED of the UPS modules will light up...

Страница 19: ...mum capacity during load test 4 2 3 Black Cold start procedure CAUTION Follow these procedures when the input AC Utility Failure but battery is normal Turn on the battery switch The battery will feed...

Страница 20: ...o the main power switches Switch ON the output breakers of the modules Switch ON the input breakers of the modules The UPS powers from the static bypass instead of the maintenance bypass then the bypa...

Страница 21: ...ted to advise service personnel that the UPS circuit is under maintenance WARNING Wait for about 5 minutes for the internal D C bus bar capacitors to be completely discharged 4 3 The Display 4 3 1 Sys...

Страница 22: ...A 22 12 2008 ID 01 08 30 Output Module Input Batt State Mains A B C Phase Voltage V 220 220 220 Phase Current A 2 2 2 Frequency HZ 50 Power Factor 0 99 0 99 0 99 Bypass Phase Voltage V 220 220 220 Fre...

Страница 23: ...Base Volt 2 25 Battery Protect Volt 1 70 Boost Charge Enable Back Boost Last Time 231 Min Max Charge Current 25A Next 30KVA 22 12 2008 ID 01 08 30 Setting Record Version 0001 12 21 15 00 26 On Line 0...

Страница 24: ...Next 30KVA 22 12 2008 ID 01 08 30 Setting Record Version Language Change Password Date Setting 2008 12 22 08 30 00 Back light Delay 10Min Contrast 20 Self Test Date STA 18 36 FOR 60min Back Timing of...

Страница 25: ...0 Next 30KVA 22 12 2008 ID 01 08 30 Setting Record Version Work Mode Single LBS Group Setting Master System Voltage Level 220V System Frequence Level 50HZ Auto Turn on Enable Bypass Frequence Range 2...

Страница 26: ...30KVA 22 12 2008 ID 01 08 30 Setting Record Version Parallel ID 01 M S Alternate Cyc 6 M UPS Output Ena Pre Alarm Time 14 Float Volt Revise 0 00 Parallel Amount 04 Parallel Redundancy 01 Back Next 30...

Страница 27: ...0 Setting Record Version Single Battery Volt 12V Battery Number 20 Battery Group 1 Single Battery Capa 100AH Boost Upper Limit Volt 2 31 Float Base Volt 2 25 Battery Protect Volt 1 70 Boost Charge Ena...

Страница 28: ...he details by pressing them 5 Select and confirm the data information can view the details It contains the details of the AC input output inverter battery BUS parallel and temperature Shown as the pic...

Страница 29: ...and system setting Shown as the picture below setting menu 8 Select and confirm client setting then you may set the following User setting information Figure Invert 220 0V 50 0HZ Figure PBatt Dischar...

Страница 30: ...er inverter static bypass and battery operation 3 MAINS INDICATOR LED the status of the AC Input 4 INVERT INDICATOR LED the status of the inverter 5 OUTPUT INDICATOR LED the status of the output 6 BYP...

Страница 31: ...arity Reversed charger abnormal Off Battery and Converter Normal Battery charging Bypass indicator Green Load on Bypass power Flashing Green Bypass not available out of normal range Static bypass swit...

Страница 32: ...ifier Current Limit When the input voltage is at 208V 305V the output of the UPS will not be interrupted but it will be at current limit for example to reduce charge current When the load connected ex...

Страница 33: ...d module is removed Alarm Information No Display message Meaning 1 Rectifier Fault Rectifier detected faulty Rectifier and inverter and charger shut down 2 Rectifier Over Temperature The temperature o...

Страница 34: ...system load sharing fault If any unit in a parallel system has an unbalance load share that exceeds 30 this warning will occur 31 Bypass Site Wiring Fault Wrong phase rotation on the bypass side 32 S...

Страница 35: ...del set wrong Model setting of the UPS is incorrect 4 5 Options Network Management Card with Environmental Monitoring CAUTION For network management configuration and use refer to the separate user ma...

Страница 36: ...ages and is setup for web based auto language detection Typical topology of the UPS Network Management Relay card A 10 pin terminal is supported to offer the signals of Bypass Utility Failure Inverter...

Страница 37: ...4Wires Ground or 1Phase 2 Wires Ground Rated Voltage 380 400Vac or 220 230VAC Voltage Range 208 478Vac or 120VAC 276VAC Frequency Range 40 70Hz Power Factor 0 99 Bypass Voltage Range Max voltage 15 op...

Страница 38: ...atteries Operating Environment Temperature 0 40 Humidity 0 95 non condensing Storage temperature 25 55 Altitude 1500m Other Unit Dimensions W D H UPS cabinet 600 840 1400mm 600 840 2000mm UPS module 4...

Страница 39: ...D E F 4 5 6 7 C D E F 2 3 6 7 A B C E F 1 3 5 7 9 B D F BBBB BBBB Inverter State Byte 1 8 9 A B C D E F Int bypass Switch Closed 4 5 6 7 C D E F Int output Switch Closed 2 3 6 7 A B C E F Manu Bypass...

Страница 40: ...re 2 3 6 7 A B C E F Inverter over temperature 1 3 5 7 9 B D F Rectifier over current 8 9 A B C D E F Auxiliary power 1 fault 4 5 6 7 C D E F Auxiliary power 2 fault 2 3 6 7 A B C E F Input Thyristor...

Страница 41: ...D E F Bypass Thyristor short 4 5 6 7 C D E F Bypass Thyristor broken 2 3 6 7 A B C E F CAN comm Fault 1 3 5 7 9 B D F Parallel load sharing fault Byte 2 8 9 A B C D E F Bypass Site Wiring Fault 4 5 6...

Страница 42: ...active signal from monitoring board IO 2 3 6 7 A B C E F battery monitoring system connected 1 3 5 7 9 B D F system unregistered FF Monitoring Byte 1 8 9 A B C D E F Battery Falut from battery monito...

Страница 43: ...not powered ON Input power supply is not connected Input voltage low The input swith of the module is not switched on measure if the UPS input voltage frequency are within the window Check if all mod...

Страница 44: ...The UPS output is in short circuit Make sure the load is not in short circuit then restart the UPS 12 The LED of the Module with RED light The module is not inserted properly Pull out the module and i...

Страница 45: ...S232 port UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor UPS power status Monitor UPS alarm info Monitor UPS runn...

Отзывы: