11
The 20KVA:
Item
Input three phases
Battery
Output Single
phase
Ground
Symbol
Vin-N Vin-A Vin-B Vin-C BAT+ BATN BAT- Vout-L Vout-N
GND
Cable
diameter
30mm
2
16mm
2
The 30KVA:
Item
Input three phases
Battery
Output Single
phase
Ground
Symbol
Vin-N Vin-A Vin-B Vin-C BAT+ BATN BAT- Vout-L Vout-N
GND
Cable
diameter
45mm
2
25mm
2
The 50KVA:
Item
Input three phases
Battery
Output Single
phase
Ground
Symbol
Vin-N Vin-A Vin-B Vin-C BAT+ BATN BAT- Vout-L Vout-N
GND
Cable
diameter
75mm
2
35mm
2
The 100KVA:
Item
Input three phases
Battery
Output Single
phase
Ground
Symbol
Vin-N Vin-A Vin-B Vin-C BAT+ BATN BAT- Vout-L Vout-N
GND
Cable
diameter
150mm
2
Or 2*75mm
2
75mm
2
Note: “2*” means two cables are connected in parallel
CAUTION!
Protective earth cable: Connect each cabinet to the main ground
system. For Grounding connection, follow the shortest route
possible
。
WARNING!
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES
MAY RESULT IN ELECTROMAGNETIC INTERFERENCE OR IN
HAZARDS INVOLVING ELECTRIC SHOCK AND FIRE
3.8 Power cable connect
Once the equipment has been finally positioned and secured, connect the power