INHIBITION SYSTEM STATUS INPUT
MICROWAVE SETTINGS
ANTI-MASKING ANALYSIS
To adjust the microwave sensibility/range, you can rotate the trimmer with a little screwdriver.
Turning clockwise, the sensibility of microwave will be increased.
Turning counter-clockwise, the sensibility of microwave will be decreased
Enabling /disabling of anti-masking analysis is possible with DIP-SWITCH “2”
When the DIP-SWITCH is in ON, the detection of a masking event makes the open collector output “F”
closed.
The analysis considers of both variables:
•
Microwave
•
Infrared
Note: In the particular case of the infrared, the analysis is performed by an active infrared LED.
TAMPER ANALYSIS
All’accensione del sensore la piattaforma inerziale (MEMS) si tara per la posizione acquisita, con
spostamenti di 3-4 gradi genera un allarme sull’uscita di sabotaggio (T-T).
Subito dopo un rilevamento di spostamento, il sensore inerziale si tara nuovamente sulla posizione
corrente.
•
Per disabilitare lo stato impianto fornire 12V all’ingresso “I”.
•
Nel passaggio da 12V a 0V (abilitazione utilizzo del LED) se si ha una memoria legata al sistema
Antimask e/o Accelerometro il sensore esegue una calibrazione.
•
Tale ingresso ha priorità rispetto al DIP-SWITCH 1.
FAULT / MASKING OUTPUT
•
In caso di “Guasto/Mascheramento” viene attivata tale uscita “F”.
•
In corrispondenza di Mascheramento oltre all’attivazione dell’uscita “F” si avrà anche il
lampeggio del LED di stato.
•
In caso di resistenze di fine linea (EoL) Ksenia il guasto viene segnalato con il relativo
bilanciamento.
WALK TEST
The Walk test procedure starts immediately after the Heating / calibration time, for maximum 10
minutes.
During this time it’s possible to test the coverage of microwave and infrared, using the RGB LED.
Please refer to page15
for LED reference.
Note: during the walk Test, the LED is always enabled (regardless the DIP SWITCH / “I” input settings).
INCREASE
DECREASE