Pumps fail to start in automatic mode or cut out shortly after start-up. Lack of water
is indicated.
Pressure booster system does not start up.
Pumps running but not delivering water.
Insufficient delivery of pressure booster system.
Discharge-side pressure too low.
Discharge-side pressure too high.
Leakage at mechanical seal
One/several pumps/motors overheated.
Motor protection switch(es) triggered. Warning LED lit.
Pump(s) do(es) not stop.
Pumps start too often (more than 30 start-ups per pump and hour).
One/several pumps/motors overheated.
Table 10: Trouble-shooting
A B C D E F G H I
J K L Possible cause
Remedy
2)
-
-
✘ ✘
-
-
-
✘
-
✘
-
- Pumps and/or piping are not
completely vented or primed.
Vent and/or prime.
✘ ✘ ✘ ✘ ✘
-
-
✘
-
-
✘
- Shut-off valves (partially) closed
Check, open as necessary.
✘
-
-
✘ ✘
-
-
-
-
✘ ✘
- Strainer clogged (inlet-side pressure
reducer)
Clean.
✘
-
-
✘ ✘ ✘
-
-
-
✘ ✘
- Inlet-side pressure reducer set
incorrectly
Check, adjust as necessary.
-
-
✘ ✘ ✘
-
-
✘ ✘ ✘ ✘
-
-
Check valve in bypass line defective Replace.
✘ ✘
-
-
-
-
-
-
-
-
-
- Inlet-side shut-off valve closed
Check, open as necessary.
-
✘
-
-
-
-
-
✘
-
✘
-
- Discharge-side shut-off valve closed
or defective
Check, open as necessary.
✘
-
-
✘ ✘
-
-
✘
-
✘ ✘
- Inlet pressure lower than stated in
the purchase order
Contact KSB.
-
✘
-
-
-
✘
-
-
-
-
-
- Inlet pressure higher than stated in
the purchase order
Contact KSB.
✘
-
-
✘ ✘
-
-
-
-
✘
-
- Start-up pressure set too high
Check setting.
-
✘
-
-
✘ ✘
-
✘
-
✘
-
✘
Pressure transmitter set incorrectly
or defective
Check setting.
-
-
-
-
-
-
-
✘
-
-
✘ ✘
Pre-charge pressure of the
accumulator too low
Restore nitrogen cushion.
A
B
C
D
E
F
G
H
I
J
K
L
2)
The pump pressure must be released before attempting to remedy faults on parts which are subjected to pressure.
Disconnect the pump from the power supply!
9 Trouble-shooting
30 of 40
Surpress Feu SFE.3
Содержание Surpress Feu SFE.3
Страница 1: ...Fire fighting System Surpress Feu SFE 3 From series 2014w33 Installation Operating Manual...
Страница 39: ......