Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 39 of 48
3-5-2-2
Pipe Diameter Discharge Pressure Measur-
ing Point
30 mm
Preset
ServiceTool
3-5-2-3
Height Difference_Pressure Measuring
Points
0,4 m
Preset
ServiceTool
3-5-2-4
Pressure Measuring Point Positions
Close to Pump
Preset
ServiceTool
3-9-3-1
Dynamic Pressure Setpoint Compensation
Method
2 = Flow rate
0 = OFF
ServiceTool, Display
3-9-3-2
Dyn Press Setpoint Comp Q Data Point
80.00 [m³/h]
0.00 [bar]
ServiceTool
3-9-3-4
Setpoint Compensation
1.00 [bar]
0.00 [bar]
ServiceTool
3-8-6-1
Digital Input 1 Function
System Start
1)
Preset
ServiceTool
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive and PumpMeter