Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 31 of 48
26
27
11
26
27
GND
DO
GND
26
27
DO
11
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
28
+24V
DI
28
11
71
81
D
C
B
A
6
5
Configuration of drive 2 (AuxMaster):
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Changeable by
3-6-1
Type of Control
3 = Differential Pressure
Preset
ServiceTool, Display
3-11-2-1 Minimum Pressure
-1.00 [bar]
Preset
ServiceTool
3-11-2-2 Maximum Pressure
10.00 [bar]
Preset
ServiceTool
3-11-2-3 Pressure Unit
bar
Preset
ServiceTool
1-3-2
Setpoint (Closed-loop Control)
4.00 [bar]
preset acc. specified Q,H
ServiceTool, Display
3-8-4-1
Function M12 Module Input A
1 = PMtr Suction/Dis-
charge Pressure
Preset
ServiceTool, Display
3-13-5
PumpMeter Master/Slave
Master
Preset for Etaline Z
ServiceTool
3-7-1
Role in multi pump operation
0 = master
Slave when Etaline Z
ServiceTool, Display
3-7-2
Pumps running
1
Preset
ServiceTool, Display
3-7-4-1
Automatic pump change
1 = Operating hours
Preset
ServiceTool, Display
3-7-4-2
Time pump running
24
Preset
ServiceTool, Display
3-8-6-1
Digital Input 1 Function
System Start
1)
Preset
ServiceTool
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive and PumpMeter
Nr.
Function
26
Enable power electronic
27
Ground for digital inputs
11
System start with DI
1)
28
Alarm
5
Tailor-made bus cable for double and multi pump operation (color: pur-
ple, male: angled, male: angled)
6
Actual value: tailor-made cross link bus cable for the redundant connec-
tion of PumpMeter (color: black, female: angled, male: angled)
Nr.
Function
71
M12 Module: Double and multi pump operation
81
M12 Module: PumpMeter
A
M12 Module female A: connection PumpMeter (Modbus)
B
M12 Module female B: cross link bus cable PumpMeter (Modbus)
C
M12 Module female C: Bus resistor
D
M12 Module female D: for Double and multi pump operation (KSB-de-
vice bus)
PDrv2 Eco
Or local
Or PLC
Drive