Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 27 of 48
26
27
11
2
26
27
GND
DO
GND
DO
26
27
11
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
0...10V
0V(GND)
2
AO: 0...10V
AO: OUT 0V(GND)
28
+24V
DI
28
11
71
81
A
B
C
D
5
Configuration of drive 2:
Nr.
Parameter
Change value to
Pre-settings by fac-
tory
2)
Changeable by
3-6-1
Type of Control
0 = OFF (Open-loop Control)
preset
ServiceTool, Display
3-2-2-1
Minimum Motor Speed
500 [1/min]
preset
ServiceTool, Display
3-2-2-2
Maximum Motor Speed
2950 [1/min]
preset
ServiceTool, Display
3-8-1-1
Analog Input 1 Signal
4 = 0…10V
0 = off
ServiceTool, Display
3-8-1-2
Analog Input 1 Function
1 = Setpoint/Control value
(Auto)
0 = No Function
ServiceTool, Display
3-8-1-3
Analog Input 1 Lower Limit
0 [1/min]
-
ServiceTool, Display
3-8-1-4
Analog Input 1 Upper Limit
2950 [1/min]
-
ServiceTool, Display
3-7-1
Role in multi pump operation
0 = Master
preset
ServiceTool, Display
3-7-2
Pumps running
2
1
ServiceTool, Display
3-8-6-1
Digital Input 1 Function
System Start
1)
preset
ServiceTool
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive
Nr.
Function
26
Enable power electronic
27
Ground for digital inputs
11
System start with DI
1)
2
Set point (open loop): 0…10V
28
Alarm
5
Tailor-made bus cable for double and multi pump operation
(color: purple, male: angled, male: angled)
Nr.
Function
71
M12 Module: Double and multi pump operation
81
M12 Module: PumpMeter
A
-
B
-
C
M12 Module female C: for Double and multi pump operation
(KSB-device bus)
D
M12 Module female D: Bus resistor
PDrv2 Eco
Or local
Or PLC
Drive