Hyamat K
17
Parameters
Display or
selection option
Factory setting
Authorisation
Read--only
Authorisation
Edit/submit
3--4--1--4 Level config
3--4--1--4--1 0 % level
0
All
Service
3--4--1--4--2 100 % level
200
All
Service
3--4--1--4--3 Sensor level
0
All
Service
3--4--1--4--4 Switch--off level
10
All
Service
3--4--1--4--5 Low level reset
15
All
Service
3--4--1--4--6 Critical water level
30
All
Service
3--4--1--4--7 High water level
105
All
Service
3--4--1--4--8 Threshold
3--4--1--4--8--1 Threshold 1: ON
50
All
Service
3--4--1--4--8--2 Threshold 1: OFF
50
All
Service
3--4--1--4--8--3 Threshold 2: ON
40
All
Service
3--4--1--4--8--4 Threshold 2: OFF
40
All
Service
3--4--1--4--9 Supply valve ON/OFF
3--4--1--4--9--1 Level 1 open
70
All
Service
3--4--1--4--9--2 Level 1 closed
90
All
Service
3--4--1--4--9--3 Level 1A open
40
All
Service
3--4--1--4--9--4 Level 1A closed
60
All
Service
3--4--1--4--10 Supply valve prop.
3--4--1--4--10--1 Level setpoint 1
80
All
Service
3--4--1--4--10--2 Level setpoint 1 A
40
All
Service
3--4--1--4--10--3 Hysteresis
15
All
Service
3--4--1--4--10--4 Sample time
10
All
Service
3--4--2 Discharge
3--4--2--1 Sensor press. 4mA
0
…
99
0
All
Service
3--4--2--2 Sensor press. 20mA
0
…
99
16
All
Service
3--4--2--3 Pumps ON sensor fail
0
…
6
0 = all pumps stop
1 = one pump running
6 = all 6 pumps running
0
All
Service
3--4--2--4 Max power
Number of pumps x
100 %
All
Service
3--4--3 Variable frequ. drive
1
)
3--4--3--1 Communication
Analog 4--20 mA
RS485 Danfoss
RS485 Lenze
PumpDrive
depends on the system All
Service
3--4--3--2 Proportional const.
0
…
999
depends on the system All
Service
3--4--3--3 Integral const.
0
…
999
depends on the system All
Service
3--4--3--4 Differential const.
0
…
999
depends on the system All
Service
3--4--3--5 No--flow detection
0
…
9
depends on the system All
Service
3--4--3--6 Relative pump load [%]
0
…
100
depends on the system All
Service
3--4--3--7 VFD Write slave nr.
1
…
6
depends on the system All
Service
3--4--3--8 Serial com.
Active
Inactive
depends on the system All
Service
3--4--3--9 VFD Ramp--up [s]
0,1
…
999
depends on the system All
Service
3--4--3--10 VFD Ramp--down [s]
0,1
…
999
depends on the system All
Service
3--4--3--11 VFD min. frequency
0
…
60
depends on the system All
Service
3--4--3--12 VFD max. frequency
0
…
60
depends on the system All
Service
3--4--3--13 P nominal of VFD [W]
0
…
100000
depends on the system All
Service
3--4--3--14 U nominal of VFD [V]
0
…
500
depends on the system All
Service
3--4--3--15 F nominal of VFD [Hz]
50
…
60
depends on the system All
Service
3--4--3--16 I nominal of VFD [A]
0...450
depends on the system All
Service
3--4--3--17 RPM nominal of VFD [rpm]
0
…
10000
depends on the system All
Service
1
) Configuration not possible for Hyamat K