8 Trouble-shooting
20 of 28
Cervomatic EDP.2
8 Trouble-shooting
WARNING
Improper work to remedy faults
Risk of injury!
▷
For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the
accessories manufacturer.
If problems occur that are not described in the following table, consultation with the
KSB
customer service is required.
A1
Lack of water
A2
Fill level sensor
A3
Pressure sensor damaged
A4
Overcurrent
A5
Pump fuse
A6
Accumulator
None
No display
Table 10:
Trouble-shooting
Display
Fault message
Description
System behaviour
Remedy
A1
A1
LACK OF WATER
Fault message:
LED "FAILURE" FLASHES (FAULT).
Fault message after acknowledgement:
LED "FAILURE" ILLUMINATED (FAULT).
If the automatic control unit detects a
lack of water at the automatic control
unit inlet for more than 10 seconds, the
pump is stopped and the ART logic is
triggered.
The ART logic restarts the pump
after 5 minutes and 30 seconds
have lapsed to reinstate the
function.
If there is still a lack of water,
the automatic control unit
restarts the function every
30 minutes over a period of
24 hours. If the system still
detects a lack of water after
several repeat attempts, the
pump is stopped permanently
until the fault has been
rectified.
No water is present at the inlet
and the safety system was
triggered as a result: Check the
water supply inlet. The pump
can be filled with water by
pressing the START/STOP button
(the AUTO On/Off LED should
not illuminate; if this is the case,
deactivate the LED by pressing
the button).
A2
A2
LEVEL
Fault message after acknowledgement:
LED "FAILURE" ILLUMINATED (FAULT).
If a float is installed in the inlet tank,
the float switch immediately stops the
pump as soon as a lack of water is
detected.
The system then outputs a lack-of-water
message (A1).
The pump remains stopped until
the fill level sensor detects
water in the tank again.
Check tank.
A3
A3
TRANSDUCER
Fault message after acknowledgement:
LED "FAILURE" ILLUMINATED (FAULT).
Damage to the pressure sensor is shown
on the LCD display of the automatic
control unit.
Call in customer service.
Operation of the automatic
control unit is interrupted.
Call in customer service.