KSB AS1-M Скачать руководство пользователя страница 6

Installation, Operating and Maintenance Instructions 

 

 

 

      6/7

 

for Alarm Switchgear AS1-M

 

 

 

 

 

 

 

 

 

 

 

 

2331.827/03-EN

 

 

 

 

Date: 2015/10/04 

standard 0100 and all associated ancillary and successor standards.

 

 
 

4.  Installing the AS1-M Alarm Switchgear

 

 

The AS1-M alarm switchgear is installed by connecting it to a C+E-type socket outlet. 
Attention must also be paid to ensure that the switchgear is seated properly.

 

 

 

5.  Connecting the M 1 (K) Alarm Contactor

 

 

The jack plug of the M 1 (K) alarm contactor must be inserted into the socket of the 
AS1-M alarm switchgear located on the underside of the housing.

 

In the process, attention must be paid to ensure that the plug is inserted all the way 
into the socket (i.e. up to the stop) and is firmly connected there so that it does not 
become loose or disconnected later on.

 

 

 

6.  Commissioning 

 

The installation position, mechanical attachment and electrical connection must be 
checked and verified a second time before commissioning is carried out. 

 

A further check must also be performed to ensure that dangerous or hazardous 
situations cannot arise as a result of not having followed one of the instructions, 
standards or legal provisions and requirements. 

 
If both of these checks are successful (i.e. no problems are detected), the device may 
then be commissioned.

 

 

 

7.  Maintenance 

 

The AS1-M alarm switchgear and the M 1 (K) alarm contactor connected to it require 
no maintenance. 

 

 

The rechargeable battery of the AS1-M alarm switchgear must be replaced by 
qualified staff every 7 years at the latest, however. When the battery is replaced, 
caution must be exercised to avoid compromising the safe galvanic isolation 
that separates the mains voltage from the jack socket.

 

 

A visual inspection and functional test of the alarm switchgear and alarm contactor 
must be carried out every three months (or sooner). 
In cases in which this is not sufficient, a monitoring schedule adapted in line with the 
application scenario must be observed. 
 

Содержание AS1-M

Страница 1: ...al must be handed to the fitter installer operator service personnel of our products together with all other relevant documentation and user information The manual must be carefully stored in a safe p...

Страница 2: ...of Application Page 3 2 Conditions for Safe Application Page 5 3 Installation Connection Commissioning and Maintenance Governing Rules and Regulations Page 5 4 Installing the AS1 M Alarm Switchgear Pa...

Страница 3: ...n turns the device off releasing the switch turns the device on When the AS1 M alarm switchgear is turned on an alarm is emitted as soon as the liquid level raises the float switch of the M 1 K alarm...

Страница 4: ...and followed without exception at all times Applications outside the envelope of the key technical data specified are prohibited This brochure must have been read and understood by the qualified speci...

Страница 5: ...y on the AS1 M Alarm Switchgear The AS1 M alarm switchgear must not be used in areas in which the device could be subjected to moisture and humidity Exclusion of Potentially Explosive Atmospheres The...

Страница 6: ...connection must be checked and verified a second time before commissioning is carried out A further check must also be performed to ensure that dangerous or hazardous situations cannot arise as a resu...

Страница 7: ...dards requirements local regulations and special circumstances and proceed accordingly prior to performing maintenance work 8 Repair Any opening of the alarm switchgear and alarm contactor and all rep...

Страница 8: ...tr 11 67466 Lambrecht declares that the following product which is new and designed for use in dry rooms Alarm Switchgear AS1 M complies with the Directives 2006 95 EC low voltage and 2004 108 EC EMC...

Отзывы: